18 User Manual
• No voltage = no feed requirement
• 220V = feed requirement from the house
The motor which supplies feed A to the weigher is controlled from the terminals V15 and V18.
The motor which supplies feed B to the weigher is controlled from the terminals V15 and V16.
When feed supply is required, these terminals will be supplied with 220V.
NB NOTE that the terminals V13 and V15 are connected internally.
The terminals V19 and V20 can be connected to remote counter or to other external registration
equipment for remote reading of the weigher (e.g. the DOL 91 or DOL 92 computers). The relay has a
potential free contact which closes 1.2 sec. for each weight impulse (10 kg) of feed type B and 2.4 sec.
for each weight impulse of feed type A.
The system which transfers the signal of feed requirement to the weigher can be based on a capacitive
sensor (DOL 33R), placed in the vessel under the weigher.
By mounting separate switches for the DOL 99-2 weigher and the feed supply system, emergency
operation will be possible, if the weigher should be out of operation.
Switch off DOL 99-2 and make sure that the drum turns upside down. Short-circuit terminals V14 and
V16, and the DOL 33R sensor will alone control the feed supply to the vessel.
IMPORTANT: The position of the sensor in the vessel should allow room for at least one
entire portion of weighed feed above it. This is important because, if not,
the drum of the weigher would be blocked by accumulated feed.
For the sake of the auger which carries the feed away from the weigher, it is
also important that there is sufficient room for feed below the sensor in
order not to empty the vessel entirely.
When resetting the weigher, the button should be activated for at least 5 seconds. When the button is
released, the drum rotates once.
1) Remount the screen plate and the plug in the panel.
2) Connect the cable to the screen plate.
3) Remount the panel and the weigher is ready for use.
7 Alarm
By means of an extra sensor, DOL 33R, DOL 99-2 may be connected to an alarm system. The alarm is
given in connection with e.g. lack of feed in the house, owing to, say, an empty silo, defect auger or
weigher. If the vessel under the weigher is empty for more than 5 minutes, the sensor causes an alarm
to be given. In connection with power failure the sensor will not release any alarm.
Placing: See figure 10. The sensor, DOL 33R, is placed in the vessel below the feed
requirement sensor DOL 33R.
Setting: The time lag of the sensor is set to approx. 5 minutes.
Connection: The supply wire of the sensor is connected to 220V permanently.
Wires 1 and 4 are normally ON but will be OFF in case of alarm. To be
connected to an alarm system, e.g. DOL 2000.
8 Remote control of DOL 99-2
If the control panel of the weigher is not easily accessible for daily operation due to the position of the
weigher, the entire control box can be moved away from the weigher. The distance between the
weigher and the control box should not exceed 25 metres. The connection between the weigher and