Skov DOL 199 silo weighing box Technical User Guide

Type
Technical User Guide
DOL 199 Silo Weighing Box
Technical User Guide
604328 • 2023-09-20
DOL 199 Silo Weighing Box
2 Technical User Guide
Product and Documentation Changes
SKOV A/S reserves the right to change this document and the product herein described without further notice.
In case of doubt, please contact SKOV A/S.
The date of change appears from the front and back pages.
Note
All rights belong to SKOV A/S. No part of this manual may be reproduced in any manner whatsoever without
the expressed written permission of SKOV A/S in each case.
All reasonable efforts have been made to ensure the accuracy of the information contained in this manual.
Should any mistakes or imprecise information occur in spite of this, SKOV A/S would appreciate being noti-
fied thereof.
Irrespective of the above, SKOV A/S shall not accept any liability with regard to loss or damage caused or
alleged to be caused by reliance on any information contained herein.
Copyright by SKOV A/S.
DOL 199 Silo Weighing Box
1 Product description ....................................................................................................................................... 4
2 Product survey ............................................................................................................................................... 5
2.1 Accessories................................................................................................................................ 5
3 Mounting guide............................................................................................................................................... 8
3.1 Recommended tools.................................................................................................................. 8
3.2 Assembly .................................................................................................................................... 8
4 Installation guide............................................................................................................................................ 9
4.1 Electrical connection................................................................................................................. 9
4.2 Cable routing.............................................................................................................................. 9
4.3 Main module ............................................................................................................................. 10
4.3.1 LED indication on the main module ........................................................................................... 11
4.4 Silo load cell module ............................................................................................................... 12
4.4.1 Assembly of the silo load cell module onto the main module .................................................... 13
4.5 Shield connection in the Silo weighing box.......................................................................... 14
4.6 Setting up the silo weighing box in the controller................................................................ 15
4.7 Electronic silo weigher calibration......................................................................................... 16
4.8 Cable plan................................................................................................................................. 17
4.9 Circuit diagram......................................................................................................................... 18
4.10 Display ...................................................................................................................................... 19
4.10.1 LED indication on display........................................................................................................... 20
4.10.2 Assembly of display main module.............................................................................................. 21
4.11 Operation .................................................................................................................................. 22
4.11.1 Normal operation ....................................................................................................................... 22
4.11.2 Delivery ...................................................................................................................................... 23
5 Cleaning ........................................................................................................................................................ 24
5.1 Recycling/Disposal .................................................................................................................. 24
6 Troubleshooting guide ................................................................................................................................ 25
7 Technical data .............................................................................................................................................. 26
7.1 Silo weighing box .................................................................................................................... 26
Technical User Guide
DOL 199 Silo Weighing Box
4 Technical User Guide
1 Product description
During the silo weighing process, a silo load cell registers the weight of the silo content and transmits it to the
DOL 199 silo weighing box. The DOL 199 converts the weight to digital signals and sends them to the controller
using CAN bus communication.
You can connect up to four silos to the DOL 199 silo weighing box. A silo has up to eight legs and a silo load
cell is placed under each leg. The DOL 199 can be connected to a total of four silos.
(A)
(B)
(D)
(E)
(E)
(E)
(E)
(C)
(A) Controller
(B) Silo weighing box
The DOL 199 is fitted with one silo load cell
as standard and one silo can be connected.
The DOL 199 can be extended with three
silo load cell modules, so that three extra si-
los can be connected.
(C) External 24 V DC power supply
(D) Connection box
The connection box is used for extending
cables from the silo load cells to the silo
weighing box. The silo load cells are con-
nected in parallel when there are more than
four of them. (SKOV A/S does not supply
the connection box).
(E) Silo load cell
DOL 199 Silo Weighing Box
Technical User Guide 5
2 Product survey
130185 DOL 199 silo weighing box
The silo weighing box is used for silo weighing. The DOL 199 converts the
weight from the silo load cells into digital signals and transmits them to the
controller using CAN bus communication.
The DOL 199 is fitted with one silo load cell module by default and you can
connect one silo with up to eight load cells.
The DOL 199 can be extended with three silo load cell modules (130187).
Additional silo load cell modules enable the DOL 199 to support four silos.
Note that CAN bus module (132245) must be mounted in the controller.
The DOL 199 must be powered using a 24 V DC external power supply
(135752).
Order one 135752 per DOL 199 silo weighing box.
130188 DOL 199 silo weighing box with display
Choose silo weighing box with display if displaying of silo content and deliv-
ery start is required on DOL 199. For floor feeding, information is provided
on the amount of time that is left until delivery can start.
The silo weighing box with display has clear and legible numbers/letters
that can be seen from a distance, even in bright sunshine.
The silo weighing box is used for silo weighing. The DOL 199 converts the
weight from the silo load cells into digital signals and transmits them to the
controller using CAN bus communication.
The DOL 199 is fitted with one silo load cell module by default and you can
connect one silo with up to eight load cells.
The DOL 199 can be extended with three silo load cell modules (130187).
Additional silo load cell modules enable the DOL 199 to support four silos.
Note that CAN bus module (132245) must be mounted in the controller.
The DOL 199 must be powered using a 24 V DC external power supply
(135752).
Order one 135752 per DOL 199 silo weighing box.
2.1 Accessories
130187 Silo load cell module
This is used to extend the DOL 199 silo weighing box and enable the DOL
199 to support four silos.
Up to eight silo load cells can be connected to the silo load cell module.
Supplied with screws, spacers and M20 screwed flange.
One silo load cell module must be used for each silo.
DOL 199 Silo Weighing Box
6 Technical User Guide
135752 Power supply 24V, 2.1A in box
An external power supply is used if the current consumption of the chosen
24 V components exceeds 0.8 A, as the maximum supply of the internal
controller's power supply is 0.8 A.
Voltage 90–264 V
Frequency 47-63 Hz
Power 160 VA/80 W
Current 0.7 A
Output
Voltage 24 V +/- 10 %
Current 2.1 A
132245 CAN-bus module
Always use the CAN-bus module when using external CAN bus communi-
cation.
One for each controller.
130121 CAN bus cable 50 m
130125 CAN bus cable 100 m
130126 CAN bus cable 250 m
For indoor use.
Must be used with external units using CAN bus communication.
130123 CAN bus cable UV 50 m
130127 CAN bus cable UV 100 m
130128 CAN bus cable UV 250 m
For outdoor use.
Must be used with external units using CAN bus communication.
DOL 199 Silo Weighing Box
Technical User Guide 7
132907 DOL 199 cable 30 m f/load cell kit
Must be used between silo weighing box and DOL 199 lightning protection
or connection box.
The cable is supplied with stripped wire ends. The wire colors in the cable
are the same as the wire colors in the cable from the silo load cells to the
connection box.
DOL 199 Silo Weighing Box
8 Technical User Guide
3 Mounting guide
3.1 Recommended tools
Below follows a list of tools recommended for installation of the DOL 199.
Item Description
Cordless drill
Screwdriver bits
Utility knife
Multimeter
Tape measure
Side cutter
Long-nose pliers
Ladder
Screwdriver
Spirit level
3.2 Assembly
Mount the silo weighing box on the wall using four screws.
DOL 199 Silo Weighing Box
Technical User Guide 9
4 Installation guide
4.1 Electrical connection
Installation, servicing and troubleshooting of all electrical equipment must be carried out by quali-
fied personnel in compliance with the applicable national and international standard EN 60204-1
and any other EU standards that are applicable in Europe.
The installation of a power supply isolator is required for each motor and power supply to facilitate
voltage-free work on the electrical equipment. The power supply isolator is not included.
4.2 Cable routing
In order to prevent water from running into the silo
weighing box via cables and screwed connections, the
cabling must be made so that water does not gather
around the cable in the gasket of the screwed connec-
tion.
Supply cables
Silo load cell / extension cable
1 m
To avoid interference, the silo load cell / extension flex
must be separated from the power cables. Distance
must be at least 1 m.
DOL 199 Silo Weighing Box
10 Technical User Guide
4.3 Main module
(A)
(B)
(C)
(D)
(E)
(F) (G) (G)
(G)(G)
Item Function Description
(A) OPTIONS All switches should be OFF
(B) MODE Mode 0 = without display
Mode 1 = with display
(C) 1 GND
2 +24V
3 CAN_H
4 CAN_L
5 SHIELD
6 CAN GND
CAN bus connection
0 V
Power supply +24 VDC (max. 1.5 A)
CAN high (brown CAN bus)
CAN low (white CAN bus)
Shield (braided shield CAN bus)
(green CAN bus)
The terminal can also be used as a looped terminal strip to the next box.
(D) CAN ID CAN bus address (CAN ID). The address switches are used for setting the CAN ID.
The DOL 199 silo weighing box must have a specific CAN ID for the controller to
communicate with it. The address of the individual silo weighing box corresponds to
the number (41 or 42) in he controller under Technical | Setup | Installation | I/O
Modules | Silo weighing modules
The X10 address switches are set to 4.
The X01 address switches are set so they correspond to the number on the silo
weighing box. 1 or 2.
(E) CAN EXTER-
NAL TERM
CAN bus termination (external)
The DOL 199 silo weighing box is controlled by the CAN bus communication. To
ensure secure communication between the boxes, it is important that the CAN ter-
mination jumpers are set correctly.
If the DOL 199 silo weighing box is the last node in the CAN bus communication,
the jumper must be set to (ON).
(F) Shield terminal Terminals for the shield. Strip the cable to connect the shield to the shield terminal.
(G) M701-M704 Location of the silo load cell module.
DOL 199 Silo Weighing Box
Technical User Guide 11
4.3.1 LED indication on the main module
(A)
(B)
(C)
(D)
(E) (F) (G)
Item Function LED color Description
(A) LED + 24 VDC Green ON: 24 V DC power supply OK.
(B)
CPU LED 1 Green FLASHES: OK
OFF: not ready for operation.
CPU LED 2 Yellow States the CAN bus status
ON: operate
OFF: pre-operate
CPU LED 3 Red OFF: CAN bus OK.
FLASHES: CAN bus error.
CPU LED 4 Red ON: internal error
Boot mode
CPU LED 1-4
CPU LED 1: flashes
CPU LED 2-3: ON
(C)
CAN bus RX LED Yellow ON: receiving data
CAN bus TX LED Blue ON: transmitting data
(D) Silo load cell module LED
1
M701
Green ON: silo load cell module 1 active
(E) Silo load cell module LED
2
M702
Green ON: silo load cell module 2 active
(F) Silo load cell module LED
3
M703
Green ON: silo load cell module 3 active
(G) Silo load cell module LED
4
M704
Green ON: silo load cell module 4 active
DOL 199 Silo Weighing Box
12 Technical User Guide
4.4 Silo load cell module
Connection of the load cells.
DOL 199 silo load cell module. Load cell
Connection terminal no. Function Wire color
1+ OUT / O+ Red
2- IN / I- White
3+ IN / I+ Green
4- OUT / O- Black
5SHIELD / SHD Shield
Four silo load cells can be connected directly to the P3, P4, P5, and P6 terminals using one four-core cable per
silo load cell.
If the distance from the silo load cells exceeds 10 m or if there are six or eight silo load cells, the silo load cells
are connected in parallel in the connection box, see section Circuit diagram.
Wire colors
1 - Red
2 - White
3 - Green
4 - Black
5 - Shield
DOL 199 Silo Weighing Box
Technical User Guide 13
4.4.1 Assembly of the silo load cell module onto the main module
(A)
(B)
(B)
(B)
(C)
(D)
(D)
1. Disconnect the +24 V DC (A) power supply to the silo weighing box.
2. Mount the three plastic spacers (B).
3. Press the silo load cell module onto the plug-in terminals (C) and plastic spacers (B). See picture below.
4. Assemble the silo load cell module on the two metal spacer (D) using M3 screws.
5. Connect the power supply (A) again.
The silo load cell modules are assembled from the left to the right.
Place module 1 at location M701
Place module 2 at location M702
Place module 3 at location M703
Place module 4 at location M704
DOL 199 Silo Weighing Box
14 Technical User Guide
4.5 Shield connection in the Silo weighing box
24 V DC power supply
1 GND = 0 V
2 +24 V = Power supply +24 VDC (max. 1.5 A)
CAN bus connection (brown, white, green and shield) see mea-
surements below.
3 CAN_H = CAN high (brown CAN bus)
4 CAN_L = CAN low (white CAN bus)
6 CAN GND = (green CAN bus)
Strip the cable so the shield can be connected to the shield
clamp.
The connection terminal can also be used as a looped terminal
strip to the next box.
DOL 199 Silo Weighing Box
Technical User Guide 15
4.6 Setting up the silo weighing box in the controller
Make sure the CAN protocol is set to CANopen.
Technical | Installation | Manual installation | CAN protocol
Select the number of DOL 199, for each DOL 199 the number of silos
must be selected.
The software supports up to four electronic silo weighers.
Technical | Installation | Manual installation | Silo weighing
boxes
Here you see the CAN bus address (CAN ID) and if it is connected.
Select type of electronic silo weigher in the menu
| Technical | Installation | Manual installation | Production |
Feed control settings | Feed weigher 1 | Electronic silo weigher or
Electronic silo weigher common auger
Select number of silos for feed weigher max. 4.
| Technical | Installation | Manual installation | Production |
Feed control settings | Silos feed weigher 1
The DOL 539/535 installation menu specifies which silo load cell mod-
ule and in which silo weighing box the silo load cells must be con-
nected.
For correct connection of silo load cells, see menu | Technical
| Installation | Show connection
WM#1 M701 = Silo 1 weighing module - module location M701
WM#1 M701 = Silo 2 weighing module - module location M701
DOL 199 Silo Weighing Box
16 Technical User Guide
4.7 Electronic silo weigher calibration
See the menu Technical | Calibration | Production | Silo | Silo.
Start calibration by setting the Calibrate/Set tara to Calibrate.
Enter the current weight in the silo in Calibration tare amount.
Enter the weight available for the calibration (Calibration load amount).
The more weight that is available, the more precise the calibration is. Min.
100 kg.
Place the calibration weight on the silo.
Wait until it is stable.
The calibration state changes to: Ready to end calibration
Select Finish.
If there is uncertainty about the silo content (Calibration tare amount), it
can still be calibrated and the menus continuously show how much of the
feed is being used. However, the indication of the silo content may be in-
correct.
It is possible to set the calibration tare amount at a different time when
you know the exact contents of the silo. You do not have to use calibra-
tion weights for calibration and subsequently correct the entry; instead
you set Calibrate/Set tare to Set tare and the known silo weight is en-
tered at .
Increase the value of Weighing stable, if the weight is not stabilized.
This should only be relevant if the silo is influenced by outside conditions, such as strong wind. The elec-
trical installation should be checked, if the silo is not stabilizing under normal conditions.
DOL 199 Silo Weighing Box
Technical User Guide 17
4.8 Cable plan
Use this cable plan if there are more than 10 m between the silo load cells and the silo weighing box, or if more
than four silo load cells are required per silo.
(A)
(B)
(D)
(E)
(F)
(F)
(F)
Max. 10 m
DOL 199 cable max. 30 m
CAN bus cable max. 400 m
Power supply
Power supply
(C)
(F)
(G)
Use this cable plan if there are less than 10 m between the silo load cells and the silo weighing box, or if four
silo load cells are required per silo.
(A)
(B)
(D)
(F)
(F)
(F)
Max. 10 m
CAN bus cable max. 400 m
Power supply
Power supply
(C)
(F)
(A) Power supply to the controller two-wire cable, including earthing contact.
(B) Max. 400 m CAN bus cable between the silo weighing box and the controller.
(C) 24 VD C power supply to silo weighing box.
(D) Power supply two-core wire with earthing.
(E) Max. 30 m DOL 199 cable between the connection box and silo weighing box.
(F) Max. 10 m four-core cable including shield between the silo load cell and the connection box or silo weighing
box.
(G) Connection box (Not supplied by SKOV A/S).
DOL 199 Silo Weighing Box
18 Technical User Guide
4.9 Circuit diagram
Use this circuit diagram if there are more than 10 m between the silo load cells and the silo weighing box, or if
more than four silo load cells are required per silo.
Silo load cell
Wiring box
Silo load cell
Silo weighing box
Use this circuit diagram if there are less than 10 m between the silo load cells and the silo weighing box, or if
four silo load cells are required per silo
Silo weighing box
Silo load cell Silo load cell
DOL 199 Silo Weighing Box
Technical User Guide 19
4.10 Display
(A)
(B) (C)
Item Function Description
(A) CAN termination
jumper
CAN termination jumper ON
(B) MODE 0 = normal operation
(C) CAN ID CAN bus address (CAN ID). The address switches are used for setting the
CAN ID.
The X10 address switches = 1.
The X01 address switches = 0.
When mounting the display, Mode on the main module must be set to 1.
DOL 199 Silo Weighing Box
20 Technical User Guide
4.10.1 LED indication on display
(A)
(B)
(C)
Item Function LED color Description
(A) LED + 24 VDC Green ON: 24 V DC power supply OK.
(B)
CPU LED 1 Green FLASHES: the processor works (firmware OK).
OFF: assembly group not ready to operate.
CPU LED 2 Yellow States CAN bus status
ON: operation (assembly group ready to operate).
OFF: preparation (assembly group has not been initialized).
CPU LED 3 Red OFF: CAN bus OK.
FLASHES: CAN bus error.
CPU LED 4 Red ON: Internal error
(C)
CAN bus RX LED Yellow ON: receiving data
CAN bus TX LED Blue ON: transmitting data
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28