Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
INSTALLATION
INSTRUCTIONS
CARBON DIOXIDE TRANSMITTERS
CDT2000 Duct Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
Thank you for choosinganHKInstruments CDT2000 Ductseries
carbon dioxide transmier. The CDT2000 Duct series is intended
foruseincommercialenvironmentsinHVAC/Rapplicaons.
TheCDT2000Ductseriesmeasurescarbondioxide(CO2),ulizing
theindustrystandardNDIRmeasurementprinciple,andtempera-
ture(T).Illuminateddisplayensureseasyreadabilityalsofromadis-
tance.TheCDT2000Ducthasascrewlesslidandaneasilyadjust-
ablemounngangethatmaketheinstallaonofthedeviceeasy.
TheCDT2000 Duct series transmierscalibratethemselves auto-
macallyusingABCTMlogic.TheABCTMlogicrequiresthatthespace
inwhichthetransmierisusedneedstotobeunoccupiedforfour
hours per day so that the indoor CO2 concentraon drops to the
outside level. CDT2000-DC Duct is a dual channel model with a
measuringchannelandareferencechannelthatmakesaconnuous
comparisonandthenecessaryadjustmentaccordingly.CDT2000-
DCDuctisalsosuitableforbuildingsthatareconnuouslyoccupied.
CDT2000Ductseriesdevicesarecommonlyusedtomonitor:
• CO2levelsofincomingandreturnairinvenlaonsystem
•CDT2000-DCDuctseriesdevicescanalsobeusedinapplicaons
wherethereisaconstantsourceofcarbondioxidepresent(for
examplehospitalsandgreenhouses)
SPECIFICATIONS
Performance
Measurement ranges:
CO2:400–2000ppm
Temperature:0...50°C
Accuracy:
CO2:±40ppm+3%ofreading,DCmodel:75ppmor
10%ofreading(whicheverisgreater)
Temperature:<0.5ºC
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
ppmand°C
Measuring element:
CO2:Non-dispersiveinfrared(NDIR)
Temperature:NTC10k
Calibraon:
Automacself-calibraonABCLogicTMorconnuous
comparison(DC)
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:119x95.5x45mm
Probe:L=186mm,d=12mm
Mounng:
Withange,adjustable40...155mm
Weight:
150g
Materials:
Case:ABS
Cover:PC
Probe:ABS
Protecon standard:
IP54
Electrical connecons:
4springloadedterminals
(24V,GND,CO2, T)
0.2–1.5mm2(16–24AWG)
A-model:
6springloadedterminals
(24V,GND,Voltage_CO2,Voltage_T,
mA_CO2,mA_T)
0.2-1.5mm2(16-24AWG)
Electrical
Supplyvoltage:24VACorVDC±10%
Currentconsumpon:max230mA(at24V)+35mA
foreachvoltageoutput
Outputsignals
0/2...5/10VDC,LoadRminimum1kΩ
OnlyA-model:
4...20mA,LoadRmaximum500Ω,minimum20Ω
Outputcalibratedwithin±0.08mA
Conformance
Meetsrequirementsfor:
CE: UKCA:
EMC: 2014/30/EU S.I.2016/1091
RoHS: 2011/65/EU S.I.2012/3032
WEEE: 2012/19/EU S.I.2013/3113
INTRODUCTION
APPLICATIONS
WARNING
RoHS
COMPLIANT