HK Instruments CDT2000 Installation guide

Type
Installation guide
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
INSTALLATION
INSTRUCTIONS
CARBON DIOXIDE TRANSMITTERS
CDT2000 Duct Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
Thank you for choosinganHKInstruments CDT2000 Ductseries
carbon dioxide transmier. The CDT2000 Duct series is intended
foruseincommercialenvironmentsinHVAC/Rapplicaons.
TheCDT2000Ductseriesmeasurescarbondioxide(CO2),ulizing
theindustrystandardNDIRmeasurementprinciple,andtempera-
ture(T).Illuminateddisplayensureseasyreadabilityalsofromadis-
tance.TheCDT2000Ducthasascrewlesslidandaneasilyadjust-
ablemounngangethatmaketheinstallaonofthedeviceeasy.
TheCDT2000 Duct series transmierscalibratethemselves auto-
macallyusingABCTMlogic.TheABCTMlogicrequiresthatthespace
inwhichthetransmierisusedneedstotobeunoccupiedforfour
hours per day so that the indoor CO2 concentraon drops to the
outside level. CDT2000-DC Duct is a dual channel model with a
measuringchannelandareferencechannelthatmakesaconnuous
comparisonandthenecessaryadjustmentaccordingly.CDT2000-
DCDuctisalsosuitableforbuildingsthatareconnuouslyoccupied.
CDT2000Ductseriesdevicesarecommonlyusedtomonitor:
CO2levelsofincomingandreturnairinvenlaonsystem
•CDT2000-DCDuctseriesdevicescanalsobeusedinapplicaons
wherethereisaconstantsourceofcarbondioxidepresent(for
examplehospitalsandgreenhouses)
SPECIFICATIONS
Performance
Measurement ranges:
CO2:400–2000ppm
Temperature:0...50°C
Accuracy:
CO2:±40ppm+3%ofreading,DCmodel:75ppmor
10%ofreading(whicheverisgreater)
Temperature:<0.5ºC
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
ppmand°C
Measuring element:
CO2:Non-dispersiveinfrared(NDIR)
Temperature:NTC10k
Calibraon:
Automacself-calibraonABCLogicTMorconnuous
comparison(DC)
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:119x95.5x45mm
Probe:L=186mm,d=12mm
Mounng:
Withange,adjustable40...155mm
Weight:
150g
Materials:
Case:ABS
Cover:PC
Probe:ABS
Protecon standard:
IP54
Electrical connecons:
4springloadedterminals
(24V,GND,CO2, T)
0.2–1.5mm2(16–24AWG)
A-model:
6springloadedterminals
(24V,GND,Voltage_CO2,Voltage_T,
mA_CO2,mA_T)
0.2-1.5mm2(16-24AWG)
Electrical
Supplyvoltage:24VACorVDC±10%
Currentconsumpon:max230mA(at24V)+35mA
foreachvoltageoutput
Outputsignals
0/2...5/10VDC,LoadRminimum1kΩ
OnlyA-model:
4...20mA,LoadRmaximum500Ω,minimum20Ω
Outputcalibratedwithin±0.08mA
Conformance
Meetsrequirementsfor:
CE:  UKCA:
EMC:  2014/30/EU S.I.2016/1091
RoHS:  2011/65/EU S.I.2012/3032
WEEE:  2012/19/EU S.I.2013/3113
INTRODUCTION
APPLICATIONS
WARNING
RoHS
COMPLIANT
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
Schematics
dimensional drawings
INSTALLATION
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Routethecablesandconnectthewires(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(onaduct).
2)Usethemounngangeofthedeviceasatemplateandmarkthe
screwholes.
3)Mounttheangeontheductwithscrews(notincluded).(Figure1a)
4)Adjusttheprobetothedesireddepth.Ensurethattheendofthe
probereachesthemiddleoftheduct.(Figure1b)
5)Tightenthescrewontheangetoholdtheprobeinposion.
119.0
95.5
119.0
45.0
88.5
186.0
Figure 1a - Mounng a ange
Figure 1b - Mounng the probe in a ange
Air flow direcon Air flow direcon
Air flow direcon Air flow direcon Air flow direcon
Strain relief facing down
Figure 1c - Mounng orientaon
Display connecon
TE
24 V
GND
Joysck 1
Joysck 2
Joysck 3
Select
Up
Down
Menu buons CO2/RH
mA Out (oponal)
CO2/RH
TE
Tighten the
screw
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
STEP 3: CONFIGURATION
ConguraonoftheCDT2000Ductseriesdeviceconsistsof:
Conguraonmenuopons.(Displayversionsonly.)
Presstheselectbuontoacceptchanges.Movetothenextset-
ngbypressingthedownbuon.
1)AcvatethedeviceMenubypushingtheselectbuonfor2
seconds.
ForCEcomplianceaproperlygroundedshieldingcableis
required.
1)Unscrewthestrainreliefandroutethecable(s).
2)Connectthewiresasshowningure2a.
3)Tightenthestrainrelief.
CO2
T
24 V
GND
+ Power Supply
24VDC / 24VAC
Output 0/2...5/10 V
Output 0/2...5/10 V
CO2
T
Output 4...20 mA
Output 4...20 mA Oponal mA output
3)SelecttheCO2highlimitforoutputband:500...2000ppm.
CO2 OUT MAX
2000 CO
2 ppm
SELECT
UP
DOWN
4)Selectthetemperaturelowlimitforoutputband:0...45.0°Cor
32...112°F.
TE OUT MIN
0.0 °C
SELECT
UP
DOWN
5)Selectthetemperaturehighlimitforoutputband:5...50.0°C
or42...122°F.
6)Selecttheoutputmaximumvoltage:5V/10V.
NOTE!WhenusingmAoutputs,10Vmustbeselected.
TE OUT MAX
50.0 °C
SELECT
UP
DOWN
MAX OUTPUT V
10 V
SELECT
UP
DOWN
7)Selecttheoutputminimumvoltage:0V/2V.
NOTE!WhenusingmAoutputs,0Vmustbeselected.
MIN OUTPUT V
0 V
SELECT
UP
DOWN
STEP 2: WIRING DIAGRAMS
NOTE!Whenusinglongconneconwiresitmaybenecessarytousea
separateGNDwireforvoltageoutputcurrenttopreventmeasurement
distoron.TheneedforanextraGNDwiredependsonthecrosssec-
onandlengthoftheusedconneconwires.Iflongand/orsmallcross
seconwiresareused,supplycurrentandwireresistancemaygener-
ate avoltage drop in the common GND wire resulng ina distorted
outputmeasurement.
CO2
T
24 V
GND
+Power Supply
24VDC / 24VAC
Output 0/2...5/10 V
Output 0/2...5/10 V
V
V
Figure 2a - Wiring diagram
Figure 2b - Wiring diagram: Extra GND wire
CONFIGURATION CONTINUED
10)Pushtheselectbuontoexitmenu.
SELECT
EXIT MENU SELECT
8)SelectCO2oset:±200CO2ppm,Osetfeatureenables
eldcalibraon.Thisisnecessaryindemandingapplicaons
requiringannualcalibraon.
CO2 OFFSET
0 CO
2ppm
SELECT
UP
DOWN
9)Selecttemperatureoset:±5°Cor±9°F
TE OFFSET
0.0 °C
SELECT
UP
DOWN
CO2 OUT MIN
400 CO
2 ppm
SELECT
UP
DOWN
2)SelecttheCO2lowlimitforoutputband:0...1900ppm.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
WARRANTY POLICY
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsoraproduconawisfound,thesellerisobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
and installaonworknotdoneby theseller.Theseleconofmateri-
alsfordevicespronetocorrosionisthebuyer’sresponsibility,unless
otherwise is legally agreed upon. Should the manufacturer alter the
structureofthedevice,thesellerisnotobligatedtomakecomparable
changestodevicesalreadypurchased.Appealingforwarrantyrequires
thatthebuyerhascorrectlyfullledhis/herduesarisenfromthede-
liveryandstatedinthecontract.Thesellerwillgiveanewwarrantyfor
goodsthathavebeenreplacedorrepairedwithinthewarranty,how-
everonlytotheexpiraonoftheoriginalproduct’swarrantyme.The
warrantyincludestherepairofadefecvepartordevice,orifneeded,
anewpartordevice,butnotinstallaonorexchangecosts.Underno
circumstanceisthesellerliablefordamagescompensaonforindirect
damage.
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.