  • Hello! I am an AI chatbot trained to assist you with the HK Instruments RHT Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
INSTALLATION
INSTRUCTIONS
HUMIDITY TRANSMITTERS
RHT Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstrucons
canresultinPERSONALINJURY,DEATHAND/ORPROPERTY
DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystem
whosespecicaonsandperformancecharacteriscsarenot
designedorcontrolledbyHKInstruments.Reviewapplicaons
andnaonalandlocalcodestoassurethattheinstallaonwill
befunconalandsafe.Useonlyexperiencedandknowledgeable
technicianstoinstallthisdevice.
•Fuseatloadsupply(normally6A,10A,16A)doesnotalwayslimit
 therelayoutputloadcurrentto6A.RelayMaximumLoad(250Vx
6Ares.)
•Addanexternalfusetorelaycommonconnector.Useame-lag
 fuse(max6A)thatisinaccordancewiththestandardIEC60127-2.
 Theproductdoesn’thaveaninternalfusefortherelay.
 CAUTION:Theproductmayonlybeconnectedtoovervoltage
 categoryIIelectricitynetworkaccordingtoIEC60664-1
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsRHTseriesrelavehu-
miditytransmier.TheRHTseriesisintendedforuseincommercial
environmentsinHVAC/Rapplicaons.
TheRHTseriesmeasuresrelavehumidity(rH)andtemperature(T).
Eachmeasurementparameter(rH,T)hasaseparateeldcongur-
ableoutput.
The RHT series relave humidity transmiers are available with
Modbusconguraon,relayandtouchscreendisplay.
RHTseriesdevicesarecommonlyusedtomonitor:
•humidityandtemperaturelevelsinoces,publicspaces,hospitals,
meengroomsandclassrooms
•humidityandtemperatureinvariouscommercialapplicaons
•humidityandtemperatureinHVAC/Renvironment
SPECIFICATIONS
Performance
Measurement ranges:
Temperature:0...50°C
Relavehumidity:0100%
Accuracy:
Temperature:<0.5ºC
Relavehumidity:±2...3%at0...50°Cand10–90%rH
Totalerrorbandincludesaccuracy,hysteresisand
temperatureeectover5...50°Cand10–90%rH.
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
°Cand%rH
Measuring element:
Temperature:Integrated
Relavehumidity: Thermosetpolymercapacive
sensingelement
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:99x90x32mm
Weight:
150g
Mounng:
3screwholessloed,3.8mm
Materials:
Case: ABS
Protecon standard:
IP20
Display (Oponal)
Touchscreen
Size:77.4x52.4mm
Electrical connecons:
Powersupply:
 5-screwterminalblock
 (24V,GND,rH,T,Maxvalue)
 0.2–1.5mm2(16–24AWG)
Relay out:
 3-screwterminalblock
 (NC,COM,NO)
 0.2–1.5mm2(16–24AWG)
Electrical
Input: 24VACorVDC,±10%
Currentconsumpon:max90mA(at24V)+ 
 10mAforeachvoltageoutputor20mAforeach
 currentoutput
Outputsignal(rH,temperature):
 0–10V,R>1kΩ
 210V,R>1kΩ(oponalvoltageoutput,displayrequired)
 4–20mA,R<500Ω
Relay out:
 SPDTRelay,250VAC/30VDC/6A
 Adjustableswitchingpointandhysteresis
Conformance
Meetsrequirementsfor:
CE:  UKCA:
EMC:  2014/30/EU S.I.2016/1091
RoHS:  2011/65/EU S.I.2012/3032
LVD/EESR: 2014/35/EU S.I.2016/1101
WEEE:  2012/19/EU S.I.2013/3113
INTRODUCTION WARNING
APPLICATIONS
RoHS
COMPLIANT
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Routethecablesandconnectthewires(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
Figure 1a - Surface mounng
Display locking
jumper
Jumpers
Contact pins for
relay terminal
Contact pins for
terminal block
Terminal block
Terminal block for relay
99.0
90.0
83.0
49.5
14.0
45.0
18.0
Ø 4.0
32.0
YES NO NO
Figure 1b - Mounng orientaon
1)Selectamounnglocaononthewallat1.21.8m(4–6)above
theoorandatleast50cm(20in)fromtheadjacentwall.Do
notblockdeviceairventsfromanydireconandleaveatleast
20cm(8in)gaptootherdevices.Locatetheunitinanareawith
goodvenlaonandanaveragetemperature,whereitwillbe
responsivetochangestotheroomcondions.TheRHTshouldbe
mountedonaatsurface.
DonotlocatetheRHTwhereitcanbeaectedby:
•Directsunlight
•Drasordeadareasbehinddoors
•Radiantheatfromappliances
•Concealedpipesorchimneys
•Outsidewallsorunheated/uncooledareas
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountthewallplatewithscrews.
•Incorrectinstallaonmaycauseashiintemperatureoutput
•Securethelidwithalockingscrew,iftherelayisconnectedtothe
mainspower.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
CAUTION!
•ForCEcompliance,aproperlygroundedshieldingcableis
required.
•Usecopperwireonly.Insulateorwirenutallunusedleads.
•Supplyaseparatecableforrelayandsignaloutwhenusingline
voltagetopowertherelay.
•Anywiringmaycarrythefulloperanglinevoltagecurrentbased
oneldinstallaon.Thecoverlockingscrewmustbeinstalledif
thelinevoltageissuppliedtotherelay.
•Careshouldbeusedtoavoidelectrostacdischargetothedevice.
•Thisunithasconguraonjumpers.Youmayneedtorecongure
thisdeviceforyourapplicaon.
1)Routethecablesthroughthesquareopeninginthebackplateor
forsurfacewiringselectaknockoutonthetoporboomofthe
wallplate,asshowninFigure2a.
2)ConnectthewiresasshowninFigure2band2c.
STEP 3: CONFIGURATION
WIRING DIAGRAMS CONTINUED
ConguraonoftheRHTseriesdeviceconsistsof:
1)Conguringthejumpers(seestep4).
2)Conguraonmenuopons.(Display-andModbusversions
only.Seetheusermanualforfurtherdetails.)
Figure 2a - Roung the cables
24 V
GND
Max
rH
Temp
+
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Figure 2b - Wiring diagram: Power input & signal output
Wires can be routed through the square opening in the back plate
Wires can be routed through the top knockouts
Wires can be routed through the boom knockouts
NC
COM
NO
STEP 2: WIRING DIAGRAMS
Figure 2d - Wiring diagram: Relay
24 V
GND
Max
rH
+
Temp
V V V
Output 0/2...10 V
Output 0/2...10 V
Output 0/2...10 V
Figure 2c - Wiring diagram: Extra GND wire
NOTE!Whenusinglongconneconwiresitmaybenecessaryto
useaseparateGNDwireforvoltageoutputcurrenttoprevent
measurementdistoron.TheneedforanextraGNDwiredepends
onthecrossseconandlengthoftheusedconneconwires.Iflong
and/orsmallcrossseconwiresareused,supplycurrentandwire
resistancemaygenerateavoltagedropinthecommonGNDwire
resulnginadistortedoutputmeasurement.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
1)Conguraonoftheoutputmodesof:
•Maxvalue
•Relavehumidity(rH)
•Temperature(Temp)
Selecttheoutputmode,current(4–20mA)orvoltage(0–10V),
byinstallingjumpersasshowninFigure4.Eachoutputarecongured
separately.
Toselect210Voutputmodeonadisplayversiondevice:
First,select010Voutputbyjumper(s),thenchangethevoltage(V)
outputfrom0–10Vto210Vviatheconguraonmenu.Please
seetheusermanualformoredetails.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsoraproduconawisfound,thesellerisobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
and installaon worknotdonebytheseller. The seleconofmateri-
alsfordevicespronetocorrosionisthebuyer’sresponsibility,unless
otherwise is legally agreed upon. Should the manufacturer alter the
structureofthedevice,thesellerisnotobligatedtomakecomparable
changestodevicesalreadypurchased.Appealingforwarrantyrequires
thatthebuyerhascorrectlyfullledhis/herduesarisenfromthede-
liveryandstatedinthecontract.Thesellerwillgiveanewwarrantyfor
goodsthathavebeenreplacedorrepairedwithinthewarranty,how-
everonlytotheexpiraonoftheoriginalproduct’swarrantyme.The
warrantyincludestherepairofadefecvepartordevice,orifneeded,
anewpartordevice,butnotinstallaonorexchangecosts.Underno
circumstanceisthesellerliablefordamagescompensaonforindirect
damage.
2)Lockingthedisplay:
Installthejumpertolockthedisplaytopreventaccesstothecongu-
raonmenuaerinstallaoniscompleted(seetheschemacsforthe
locaonofthepins).
Jumper installed to the le side pins:
0–10 V output selected
Max value
rH
Temp
0–10 V 4–20 mA
Jumper installed to the right side pins:
4–20 mA output selected
Max value
rH
Temp
0–10 V 4–20 mA
First jumper installed to the le side pins:
0-10 V output selected for Max value
Second jumper installed to the right side pins:
4–20 mA output selected for rH
Third jumper installed to the le side pins
0–10 V output selected for temperature
Max value
rH
Temp
0–10 V 4–20 mA
Figure 4
STEP 4: Jumper settings
WARRANTY POLICY
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
(Grey colour indicates that a jumper is installed)
No jumper
Circuit open
Jumper installed
Circuit closed
Jumper stored
Figure 3 - Jumper installaon
/