Indoor air quality transmitters Siro-MOD series

HK Instruments Indoor air quality transmitters Siro-MOD series User manual

  • Hello! I am an AI chatbot trained to assist you with the HK Instruments Indoor air quality transmitters Siro-MOD series User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What are the main applications of the Siro-MOD series devices?
    What types of air quality measurements can the Siro-MOD series devices provide?
    What is the accuracy of the CO2 measurement?
    What particulate matter (PM) size ranges can the Siro-MOD series devices measure?
    What is the accuracy of the PM measurement?
    What is the operating temperature range of the Siro-MOD series devices?
    What is the power consumption of the Siro-MOD series devices?
    What type of electrical input do the Siro-MOD series devices require?
Copyright HK Instruments 2021 www.hkinstruments. Installaon version 1.0 2021
INSTALLATION
INSTRUCTIONS
Indoor air quality transmitters
Siro-MOD series
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstrucons
canresultinPERSONALINJURY,DEATHAND/ORPROPERTY
DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystem
whosespecicaonsandperformancecharacteriscsarenot
designedorcontrolledbyHKInstruments.Reviewapplicaons
andnaonalandlocalcodestoassurethattheinstallaonwill
befunconalandsafe.Useonlyexperiencedandknowledgeable
technicianstoinstallthisdevice.
ThankyouforchoosinganHKInstrumentsSiro-MODseriesindoorair
quality transmier. The Siro-MOD series transmiers are intended for
useinbuildingautomaonsystemsintheHVAC/Rindustry.
Siro-MODisanindoorairqualitytransmierwithamoderndesign.The
transmier is available with several oponal air quality sensors. The
modulardevicecanbeequippedwithCO2concentraonandVOC(Vola-
leOrganicCompounds)measurementsoralternavelyPM(Parculate
Maer)measurementandinaddiontemperatureandhumiditymeas-
urements. It oers easy installaon and adjustment, several dierent
modeloponsandvariousoutputsignalsthatarecongurableseparately
foreachmeasurementparameter.
The Siro-MOD series devices are available with user interface that in-
cludesLCDdisplayandbuonsmakingtheconguraonofthedevice
quickandeasy.Anexternalconguraontoolisnecessaryforcommis-
sioning preparaons for Siro-MOD without user interface. Congura-
onisalsopossibleviaModbusnetwork.Siro-MODulizestheindustry
standardNDIRmeasurementprinciplewithself-calibrangABClogicTM
for CO2 measurement.
•PMconcentraontomeasuresthesizeandamountofparculates
intheindoorairforexampletoassesstheperformanceofairlters
•temperatureandhumidityinHVAC/Renvironment
SPECIFICATIONS
Performance
Measurement ranges:
CO2:  0–2000ppm/4002000ppm
 (selectableviajumper)
VOC:  CO₂eq:4002000ppm
 TVOCppm:0–30.0ppm
 TVOCµg/m3:0–10000µg/m3
 IAQindex:1–5(UBArang)
PM1/PM2.5/PM10: 0–50μg/m³/0–500μg/m³
 (selectableviajumper)
 IAQindex:1-5(WHOrang)
Temperature:  0...50°C
Relavehumidity: 0100%rH
Accuracy:
CO2:  ±30ppm+3%ofreading(typical),
 addional±60ppmforrstweeks
VOC*:  15%ofreading(typical)
*VOCsensoristunedfortypicalIAQMixof22VOCsas
denedbyMølhaveetal.(1997)
PM:
0…100µg/m3:
PM2.5:  ±15µg/m³(at25⁰C±5⁰C)
PM1/PM10*:  ±25µg/m³(at25⁰C±5⁰C)
100…1000µg/m3:
PM2.5:  ±15%(at25⁰C±5⁰C)
PM1/PM10*:  ±25%(at25⁰C±5⁰C)
*PM1andPM10valuesarecalculatedfromPM2.5
measurementreadingwiththedefaultparcledistribuon.
Temperature:  ±0.4⁰C(typicalat20⁰C)
Relavehumidity: ±2.2%rH(typicalat20ºC,30%rH)
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
CO₂:  ppm
VOC: CO2eq:ppm
 TVOC:ppm,µg/m³
PM:  PM1/PM2.5/PM10:µg/m³
Temperature:  °C/°F
Relavehumidity: %rH
Measuring element:
CO2:Non-dispersiveinfrared(NDIR)
VOC:ComplementaryMetalOxide
Semiconductor(CMOS)
PM:Laser-basedlightscaeringparclesensing
Temperature:IntegratedtoCMOS
Relave humidity:Thermosetpolymercapacive
sensingelement
Calibraon:
Automacself-calibraonABCLogicTM for CO2
measurement
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions: Case:95x103x30mm
(widthxheightxdepth)
Weight: 130g
Mounng:
2screwholessloed,distancec/c60mm
Materials:
Case: ABS
Protecon standard: IP20
Display (oponal)
MonochromeLCD,38x23mm
Electrical connecons:
10-pinspringloadedterminalblock
0.2...1.5mm²(16-24AWG)
Electrical
Input:24VACorVDC,±10%
Powerconsumpon:2Wmax+25mWforeach
voltageoutputor50mWforeachcurrentoutput
Outputs:
4outputs,havetoselectvoltageorcurrent
Voltageoutputs:
0 –10 V
 210V/0–5V(oponal,displayor
 conguraontoolrequired)
Currentoutput:
 4–20mA(oponal)
Outputsignallimits:
 Voltageoutputs:R>1kΩ
 Currentoutput:R>20Ω,R<500Ω
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat11bits(10bitsifparitynone):
CodingSystem:8-bitbinary
BitsperByte:
1 start bit
 8databits,leastsignicantbitsentrst
 1bitforparity
 1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
INTRODUCTION
APPLICATIONS
WARNING
Siro-MODseriesdevicesarecommonlyusedtomonitorandcontrol:
•indoorairqualityinoces,publicspaces,meengroomsand
classrooms
CO2andVOCconcentraontoregulatedemand-controlled
venlaonandtokeeptheindoorairqualityinagoodlevel
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2021 www.hkinstruments. Installaon version 1.0 2021
Pin header Descripon
OUT1
OUT2
OUT3
OUT4
GND
Voltage / current output selecon
•Currentoutputisanoponal
Output1
Output2
Output3
Output4
Ground
SCHEMATICS DIMENSIONAL DRAWINGS
INSTALLATION
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Routethecablesandconnectthewires(seestep2).
3)ConnectthedisplaycabletothedisplayconnectoronthePCB.(See
schemacs)
4)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
PM SENSOR
CO₂ SENSOR
VOC SENSOR
A+
B–
24V
GND
GND
OUT1
OUT2
OUT3
OUT4
GND
OUT1
OUT2
OUT3
OUT4
21
6
5
TEMP OR
rH + TEMP
SENSOR
3
mA-MODULE
DISPLAY CONNECTOR
MODBUS-MODULE
4
Pin header Descripon
Open
Connected
Open
Connected
CO2 / PM output range selecon
400...2000ppm(CO2models)
0...2000ppm(CO2models)
0...500μg/m3(PMmodels)
0...50μg/m3(PMmodels)
Pin header Descripon
Open
Connected
Menu lock
Menulockdisabled
Menulockenabled
1
2
Connector Descripon
A+
B-
RS485 Modbus/RTU slave
DATA+
DATA-
24 V
GND
GND
Power supply
24VAC/DC±10%
Ground
Ground
3
Connector Descripon
OUT1
OUT2
OUT3
OUT4
GND
Voltage / current outputs
•Outputsengscanbemodiedfromthedisplay
menu
•Seethelidlabelforfactorydefaultsengs.
Output1
Output2
Output3
Output4
Ground
5
6
V
mA
Opening/closing the lid
1)Openthelidbypressingthecenterfromtheboomofthelidasin
thegure.
2)Closethelidbyinserngthetopofthelidintothegroovesrstand
pushingtheboomedgeasinthegure.
Pin header Descripon
Open
Connected
Modbus terminaon
Notterminated
Terminated
4
Copyright HK Instruments 2021 www.hkinstruments. Installaon version 1.0 2021
Figure 2a - Roung the cables
Figure 2b - Wiring diagram: Power input & signal output
Figure 1a - Surface mounng
Figure 1b - Mounng orientaon
YES NO NO
1)Routethecablesthroughtheopeninginthebackplateorfor
surfacewiringselectaknockoutontheboomofthewallplate,
asshowninFigure2a.
2)ConnectthewiresasshowninFigure2band2c.
CAUTION!
•ForCEcompliance,aproperlygroundedshieldingcableisrequired.
•Usecopperwireonly.Insulateorwirenutallunusedleads.
•Careshouldbeusedtoavoidelectrostacdischargetothedevice.
•Thisunithasconguraonjumpers.Youmayneedtorecongure
thisdeviceforyourapplicaon.
STEP 2: WIRING DIAGRAMSSTEP 1: MOUNTING THE DEVICE
1)Selectamounnglocaononthewallat1.21.8m(4–6)above
theoorandatleast50cm(20in)fromtheadjacentwall.Do
notblockdeviceairventsfromanydireconandleaveatleast
20cm(8in)gaptootherdevices.Locatetheunitinanareawith
goodvenlaonandanaveragetemperature,whereitwillbe
responsivetochangestotheroomcondions.TheSiro-MOD
shouldbemountedonaatsurface.
DonotlocatetheSiro-MODwhereitcanbeaectedby:
•Directsunlight
•Drasordeadareasbehinddoors
•Radiantheatfromappliances
•Concealedpipesorchimneys
•Outsidewallsorunheated/uncooledareas
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountthewallplatewithscrews.
CAUTION!Incorrectinstallaonmaycauseashiinmeasurements.
Figure 1c - Mounng locaon
120 cm (4 ft)
180 cm (6 ft)
50 cm (20 in)
≥ 20 cm (8 in)
≥ 20 cm (8 in)
NOTE! When using long connecon wires it may be necessary to use a
separateGNDwireforvoltageoutputcurrenttopreventmeasurementdis-
toron.TheneedforanextraGNDwiredependsonthecrossseconand
lengthoftheusedconneconwires.Iflongand/orsmallcrossseconwires
areused,supplycurrentandwireresistancemaygenerateavoltagedropin
thecommonGNDwireresulnginadistortedoutputmeasurement.
When usingAC power supply, makesure thatthe groundpotenal ofthe
signalisthesameasthegroundpotenalofthesupplyvoltagetoavoidshort
circuitthroughtheaddionalGNDwire.
It is recommended to use shielded twisted pair cable for modbus cabling.
Thecableshieldmustbeearthedonlyinonepoint,normally,attheendof
themaincable.
OUT1
OUT2
OUT3
OUT4
GND
A+
B–
24V
GND
GND
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
+
Figure 2c - Wiring diagram: Extra GND wire
OUT1
OUT2
OUT3
OUT4
GND
A+
B–
24V
GND
GND
V
V
V
V
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
0-10V/2-10V/0-5V/4-20mA
+
STEP 3: CONFIGURATION
ConguraonoftheSiro-MODseriesdeviceconsistsof:
1)Conguringthejumpers(seestep4).
2)Conguraonmenuopons.
(Display(-D)orconguraontoolrequired.Seetheusermanual
forfurtherdetails.)
Copyright HK Instruments 2021 www.hkinstruments. Installaon version 1.0 2021
1)Conguraonoftheoutputmodes:
Selecttheoutputmode,current(4–20mA)(oponal)orvoltage(0–10V)
foreachoutput(1-4)byinstallingjumpersasshowninFigure4.
Onadisplayversionofthedevice,theoutputscalecanbechangedviathe
conguraonmenu.Anexternalconguraontoolisavailablefordevices
withoutuserinterface.
First,selecttheoutputmodebyjumper,thenselecttheoutputscale(4–
20mA(oponal)/0–10V/210V/0–5V)viatheconguraonmenu.
Pleaseseetheusermanualformoredetails.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliveredgoods
regardingmaterialandmanufacturing.Thewarrantyperiodisconsideredtostart
onthedeliverydateoftheproduct.Ifadefectinrawmaterialsoraproducon
awisfound,thesellerisobligated,whentheproductissenttothesellerwithout
delayorbeforeexpiraonofthewarranty,toamendthemistakeathis/herdis-
creoneitherbyrepairingthedefecveproductorbydeliveringfreeofcharge
tothebuyeranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturncostsbythe
seller.Thewarrantydoes notcomprisedamagescausedbyaccident,lightning,
oodorothernaturalphenomenon,normalwearandtear,improperorcareless
handling,abnormaluse,overloading,improperstorage,incorrectcareorrecon-
strucon,orchangesandinstallaonworknotdonebytheseller.Theselecon
of materials fordevices prone to corrosion is the buyer’sresponsibility,unless
otherwiseislegallyagreedupon.Shouldthemanufactureralterthestructureof
the device, the seller is not obligated to make comparable changes to devices
alreadypurchased.Appealingforwarrantyrequiresthatthebuyerhascorrectly
fullled his/herduesarisenfromthedeliveryandstatedinthecontract.The
seller will give a new warranty for goods that have been replaced or repaired
withinthewarranty,howeveronlytotheexpiraonoftheoriginalproduct’swar-
rantyme.Thewarrantyincludestherepairofadefecvepartordevice,orif
needed,anewpartordevice,butnotinstallaonorexchangecosts.Underno
circumstanceisthesellerliablefordamagescompensaonforindirectdamage.
Figure 4
STEP 4: Jumper settings
RECYCLING/DISPOSAL
The parts le over from installaon should be re-
cycledaccordingtoyourlocalinstrucons.Decom-
missioned devices should be taken to a recycling
sitethatspecializesinelectronicwaste.
WARRANTY POLICY
Figure 3 - Jumper installaon
A+
B–
24V
GND
GND
OUT1
OUT2
OUT3
OUT4
GND
OUT1
OUT2
OUT3
OUT4
3
12
4
OUT1
OUT2
OUT3
OUT4
V
mA
NOTE! When using mA output, do not use Vout scalings from the menu.
Using2-10Voutputinsomeapplicaonsitiscricaltoknowimmidiatelyif
thewireisbrokenorthedeviceisdamaged.Inthesecases,a2-10voltage
outputisrecommended.
2)OutputrangeseleconwithCO2-andPM-models:
 Installthejumper1(gure3)tochangeoutputrange.Thisfeatureis
intendedtouseonlyondeviceswithoutdisplay.Onadisplayversionof
thedevice,theoutputrangecanbeselectedviatheconguraonmenu.
Pleaseseetheusermanualformoredetails.
Pin header Descripon
Open
Connected
Open
Connected
CO2 / PM output range selecon
400...2000ppm(CO2models)
0...2000ppm(CO2models)
0...500μg/m3(PMmodels)
0...50μg/m3(PMmodels)
1
3)Lockingthedisplay:
Installthejumper2(gure3)tolockthedisplaytopreventaccesstothecon-
guraonmenuaerinstallaoniscompleted.
4)Modbusterminaon:
Installajumper4(gure3)toterminateModbus.
In order toavoidsignalreecons,Modbus terminaon jumper must be
installedincaseifthedeviceisthelastoneofthebus.
Modbus registers continued
Register Parameter descripon Data type Min value Max value Range
4x0001 OsetCO2 16bit -200 200 -200..200ppm
4x0002 OsetHumidity 16bit -10 0 100 -10.0..10.0%
4x0003 OsetCelsius*1 16bit -50 50 -5.0..5.0°C
4x0004 OsetFahrenheit*1 16bit -90 90 -9.0..9.0°F
4x0005 OsetTVOCppm 16bit -300 300 -3.00..3.00ppm
4x0006 OsetTVOCug/m3 16bit -1000 1000 -1000..1000ug/m3
4x0007 OsetCO2EQ 16bit -20 0 200 -200..200ppm
4x0008 OsetPM 16bit 30 200 0.3..2.0coecient
4x0009 Backlightintensity 16bit 0100 0..100%
4x0010 DisplayCelsius*2 16bit 06 Posionnumber,0=notused
4x0011 DisplayFahrenheit*2 16bit 06 Posionnumber,0=notused
4x0012 DisplayHumidity 16bit 06 Posionnumber,0=notused
4x0013 DisplayCO2 16bit 06 Posionnumber,0=notused
4x0014 DisplayCO2 EQ 16bit 06 Posionnumber,0=notused
4x0015 DisplayPM2.5hour 16bit 06 Posionnumber,0=notused
4x0016 DisplayPM10hour 16bit 06 Posionnumber,0=notused
4x0017 DisplayIAQ 16bit 06 Posionnumber,0=notused
Register Parameter descripon Data type Min value Max value Range
3x0001 Programversion 16bit 19999 0.01..99.99
3x0002 CO2reading 16bit 02500 0..2500ppm
3x0003 rHreading 16bit 01000 0.0..100.0%
3x0004 TemperatureCelsius 16bit 0500 0.0..50.0°C
3x0005 TemperatureFahrenheit 16bit 320 1220 32.0..122.0°F
3x0006 TVOCppmreading 16bit 03200 0.00..32.00ppm
3x0007 TVOCug/m3reading 16bit 010000 0..10000ug/m3
3x0008 CO2_eqreading 16bit 012000 0..12000ppm
3x0009 IAQreadingTVOC 16bit 15 1..5IAQindex
3x0010 IAQreadingPM 16bit 15 1..5IAQindex
3x0011
3x0012 PM1reading 16bit 01000 0..1000ug/m3
3x0013 PM2.5reading 16bit 01000 0..1000ug/m3
3x0 014 PM10reading 16bit 01000 0..1000ug/m3
3x0015 PM2.51haverage 16bit 010000 0.0..1000.0ug/m3
3x0016 PM2.524haverage 16bit 010000 0.0..1000.0ug/m3
3x0017 PM101haverage 16bit 010000 0.0..1000.0ug/m3
3x0018 PM1024haverage 16bit 010000 0.0..1000.0ug/m3
3x0 019
3x0020 Error status 16bit 065535 Seetablebelow
STEP 5: Modbus registers
Bit0temperaturesensordetected,  0=notdetected,1=detected
Bit1humiditysensordetected,  0=notdetected,1=detected
Bit2co2sensordetected,  0=notdetected,1=detected
Bit3vocsensordetected,  0=notdetected,1=detected
Bit4pmsensordetected,  0=notdetected,1=detected
Bit5displaymoduledetected,  0=notdetected,1=detected
Bit6current(mA)moduledetected,  0=notdetected,1=detected
Bit8sensorwarmup  0=normaloperaon,1=warmup
Bit9rhtstatus  0=normaloperaon,>0readingerror
Bit10CO2status  0=normaloperaon,>0readingerror
Bit11pmstatus  0=normaloperaon,>0readingerror
Bit12vocstatus  0=normaloperaon,>0readingerror
3x0020 Error status bits
Funcon code 03 - Read holding registers, Funcon code 06 - Write single register,
Funcon code 16 - Write mulple registers, Broadcast supported with address 0
Funcon code 04 - Read input register
*1=CelsiusandFahrenheitlimitsareinterdependent,andthusachange inonelimitofameas-
urementwillalsochangethelimitsoftheothermeasurement.UseFunconcode06(writesingle
register)forCelsiusorFahrenheit.
*2=UseFunconcode16(writemulpleregisters)fordisplayconguraon.Validvalue(0/1...6)
neededforalldisplayconguraonregisters.(seeSiroUserGuideSTEP1.1:Displayview)
/