Copyright HK Instruments 2022 www.hkinstruments. Installaon version 2.0 2022
INSTALLATION
INSTRUCTIONS
Indoor air quality transmitters
Siro series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstrucons
canresultinPERSONALINJURY,DEATHAND/ORPROPERTY
DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystem
whosespecicaonsandperformancecharacteriscsarenot
designedorcontrolledbyHKInstruments.Reviewapplicaons
andnaonalandlocalcodestoassurethattheinstallaonwill
befunconalandsafe.Useonlyexperiencedandknowledgeable
technicianstoinstallthisdevice.
Thank you for choosing an HK Instruments Siro series indoor air
qualitytransmier.TheSiroseriestransmiersareintendedforuse
inbuildingautomaonsystemsintheHVAC/Rindustry.
Sirois anindoor air qualitytransmierwitha moderndesign.The
transmierisavailablewithseveraloponalairqualitysensors.The
modulardevicecanbeequippedwithCO2concentraonandVOC
(Volale Organic Compounds) measurements or alternavely PM
(ParculateMaer)measurementandinaddion temperatureand
humiditymeasurements.Itoerseasyinstallaonandadjustment,
severaldierentmodeloponsandvariousoutputsignalsthatare
congurableseparatelyforeachmeasurementparameter.
TheSiroseriesdevicesareavailablewithuserinterfacethatincludes
LCDdisplayandbuonsmakingtheconguraonofthedevicequick
andeasy.Anexternalconguraontoolisavailablefordeviceswith-
outuserinterface.SiroulizestheindustrystandardNDIRmeasure-
mentprinciplewithself-calibrangABClogicTM for CO2 measurement.
•PMconcentraontomeasuresthesizeandamountofparculates
intheindoorairforexampletoassesstheperformanceofairlters
•temperatureandhumidityinHVAC/Renvironment
SPECIFICATIONS
Performance
Measurement ranges:
CO2: 0–2000ppm/400–2000ppm
(selectableviajumper)
VOC: CO₂eq:400–2000ppm
TVOCppm:0–30.0ppm
TVOCµg/m3:0–10000µg/m3
IAQindex:1–5(UBArang)
PM1/PM2.5/PM10: 0–50μg/m³/0–500μg/m³
(selectableviajumper)
IAQindex:1-5(WHOrang)
Temperature: 0...50°C
Relavehumidity: 0–100%rH
Accuracy:
CO2: ±43ppm+3%ofreading(typical),
addional±60ppmforrstweeks
VOC*: 15%ofreading(typical)
*VOCsensoristunedfortypicalIAQMixof22VOCsas
denedbyMølhaveetal.(1997)
PM:
0…100µg/m3:
PM2.5: ±15µg/m³(at25⁰C±5⁰C)
PM1/PM10*: ±25µg/m³(at25⁰C±5⁰C)
100…1000µg/m3:
PM2.5: ±15%(at25⁰C±5⁰C)
PM1/PM10*: ±25%(at25⁰C±5⁰C)
*PM1andPM10valuesarecalculatedfromPM2.5
measurementreadingwiththedefaultparcledistribuon.
Temperature: ±0.5⁰C(typicalat20⁰C)
Relavehumidity: ±2.4%rH(typicalat20ºC,30%rH)
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
CO₂: ppm
VOC: CO2eq:ppm
TVOC:ppm,µg/m³
PM: PM1/PM2.5/PM10:µg/m³
Temperature: °C/°F
Relavehumidity: %rH
Measuring element:
CO2:
Non-dispersiveinfrared(NDIR)
VOC:
ComplementaryMetalOxideSemiconductor
(CMOS)
PM:
Laser-basedlightscaeringparclesensing
Temperature:
IntegratedtoCMOS
Relave humidity:
Thermosetpolymercapacivesensingelement
Calibraon:
Automacself-calibraonABCLogicTM for CO2
measurement
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:95x103x30mm
(widthxheightxdepth)
Weight:
130g
Mounng:
2screwholessloed,distancec/c60mm
Materials:
Case: ABS
Protecon standard:
IP20
Display (oponal)
MonochromeLCD,38x23mm
Electrical connecons:
8-pinspringloadedterminalblock
0.2...1.5mm²(16-24AWG)
Electrical
Input:
24VACorVDC,±10%
Powerconsumpon:2Wmax+25mWforeach
voltageoutputor50mWforeachcurrentoutput
Outputs:
4outputs,havetoselectvoltageorcurrent
Voltageoutputs:
0 –10 V
2–10V/0–5V(oponal,displayor
conguraontoolrequired)
Currentoutput:
4–20mA(oponal)
Outputsignallimits:
Voltageoutputs:R>1kΩ
Currentoutput:R>20Ω,R<500Ω
Conformance
Meetsrequirementsfor:
CE: UKCA:
EMC: 2014/30/EU S.I.2016/1091
RoHS: 2011/65/EU S.I.2012/3032
WEEE: 2012/19/EU S.I.2013/3113
INTRODUCTION
APPLICATIONS
WARNING
Siroseriesdevicesarecommonlyusedtomonitorandcontrol:
•indoorairqualityinoces,publicspaces,meengroomsand
classrooms
• CO2andVOCconcentraontoregulatedemand-controlled
venlaonandtokeeptheindoorairqualityinagoodlevel
RoHS
COMPLIANT