Lutron Electronics LUT-ELI-3PH Installation guide

Category
Serial switch boxes
Type
Installation guide
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 1
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
System Ratings
• Voltage:100-347V 50/60Hz30mA
• Current:20Amaximumcircuitbreaker
ForusewithLutron®:GRAFIK Eye®GP,LP,andXP
panels;LCP128TMpanels;Softswitch128panels;
EcoSystem®lightingcontrolsystem;EnergiSavr
NodeTM units;Quantum® systems;GRAFIK EyeQS
units,andRadioTouch®lightingcontrollers.
Note:Thisdevicedoesnotprovideemergencypower.
AnEmergency(Essential)powersourcemustbe
provided.
Please read this guide before installing.
Contents Page
Ratingsandmodelnumberoverview............................1
MountingtheInterface.................................................2
WiringOverviewforLUT-ELI-3PHunitson:
RadioTouchSystems...............................................2
Panel-BasedSystems..............................................4
EcoSystemorQuantumbussupplies.......................8
GRAFIKEyeQSunits...............................................9
EnergiSavrNodeunits..........................................10
EmergencyPowerModeSetup:LCPPanels..............11
NECClass2/PELVWiringtoFireAlarm
ControlPanel(FACP).............................................12
Troubleshooting
RadioTouch ............................................................13
PanelBasedSystems............................................14
EnergiSavrNode Installations................................15
EcoSystemorQuantumSystem............................16
GrakEyeQSInstallation.......................................17
Listing
TheEmergencyLightingInterface–LUT-ELI-3PHis
UL924Listedas“EmergencyLightingandPower
Equipment”.Theinterfaceshallbeusedwith:Lutron
GRAFIK EyeGP,XP,andLPpanels;LCP128panels;
Softswitch128panels;EcoSystem;Quantum;GRAFIK
Eye QS,RadioTouchcontrollers,andEnergi Savr
Nodeunits.
Description
TheLUT-ELI-3PHunitsensesthelinevoltageon
allthreephasesorasinglephaseandcontrolsthe
emergencysignaltothefollowingcompatibleLutron
products/systems:
• CircuitSelectorforGP,LP,XPpanels
• LCP/XPScontrollerforLCP128,and
Softswitch 128panels
• EcoSystemBusSupply
• QuantumBusSupply
• Grafik EyeQSunit
• RadioTouchcontroller
• Energi Savr Nodeunit
Whenoneormorephasesofnormalpowerarelost,
theLUT-ELI-3PHunitsendsasignaltotheaffected
device(s),activatingtheemergencymode.Anylights
controlledbythesedeviceswillgototheemergency
lightlevelsetting(factorysetto100%intensity).When
normalpowerisrestored,thelightswillreturntotheir
previousintensities.
Important Safeguards
• Followallnationalandlocalelectricalcodesandsafety
standards.
• Turnoffpowerbeforeinstallation.
• LinevoltageinputtotheLUT-ELI-3PHunitmustbe
fromtheNORMAL(non-essential)powersource.
• Readandfollowallsafetyinstructions.
• Forindooruseonly.
• Equipmentshouldbemountedinlocationsand
atheightswhereitwillnotreadilybesubjectedto
tamperingbyunauthorizedpersonnel.
• Donotusethisequipmentforotherthanintendeduse.
• Allservicingshouldbeperformedbyqualiedservice
personnel.
System Limits (per / LUT-ELI-3PH)
• 32circuitselectors
• 100RadioTouchControllers
• 32EcoSystembussupplies
• 32Quantumbussupplies
• 32Energi Savr Nodeunits
• 32LCP/XPSControllers
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 2 LUT-ELI-3PH Installation Guide
Mounting the Interface
1. Turnpoweroff.
2. Wirethelinevoltageleadsthatprotrudefrombackof
LUT-ELI-3PHunitintothejunctionbox.
3. MounttheLUT-ELI-3PHunitontoa4x4-inch
(102x102mm)junctionbox(notincluded,but
available;Lutronpartnumber241-496).
4. Besureallthepowerwiresarecompletelyinsidethe
junctionboxbeforetighteningthemountingscrews.
5. Removefrontenclosurecovertoexposetheterminal
blocks,testswitch,andstatusLEDs.
6. InserttheNEC®Class2/PELVwiresthroughknockouts
intheLUT-ELI-3PHenclosureasshowninthediagram.
7. ConnecttheNECClass2/PELVwirestotheLutron®
productorsystem,whichtheLUT-ELI-3PHwillbe
controlling.Specicwiringtothesedeviceswillbe
describedinthefollowingsections.
8. Reinstallfrontenclosurecover.
Note:CalltheLutronTechnicalSupportCenterat
(800)523-9466forrestrictionsandwiringrequirements
foremergencyxtures(xturesthatneverturnoffor
haveabatterybackupballastinthexture).
InsertNECClass2/PELV
wiresthroughknockouts
4x4in
(102x102mm)
JunctionBox
SideView
(Cross-Section)
Installing a LUT-ELI-3PH Unit in a
RadioTouch® System
Line Voltage Connections
WARNING! Danger of shock. May result
in serious injury or death.DONOTWIRE
WHENLIVE!Switchoffpowertoallpower
feedsviacircuitbreakerorisolatorbefore
wiringorservicingtheLUT-ELI-3PHunitand
RadioTouchSystem
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a
certified electrician, following local codes.
Note: Providepropershort-circuitandovercurrent
protectionatthedistributionpanel.Maximumcircuit
breakerratingof20A.
Single-PhaseWiring
Ground
Neutral
Hot
Normal
Power
Normal
Lights
Red
Red
Red
White
Green
Three-PhaseWiring
Ground
Neutral
PhaseC
PhaseB
PhaseA
Normal
Power
Normal
Lights
Red
Red
Red
White
Green
WALL
LUT-ELI-3PH
UNIT
Figure #1 Figure #2
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 3
1234 5678 910111213141516
CLASS 2 LOW VOLTAGE WIRING
1 2345
Power
Status Program
Burn-In
123
378910 11 12 13 14 15 16
CLASS 2 LOW VOLTAGE WIRING
1 2345
Power
Status Program
Burn-In
123
4 5612
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
CLASS2LOWVOLTAGEWIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
RadioT o uch
TM
C o o p er sbur g, PA1 803 6 U S A
R T A-RX-F-SC
LISTED243C
Ind.Cont.Eq.
12
345678910
1 1
12 1 3 14
15 16
Occ.Com
OccSig
24V
CirCom
CCO1
CCO2
CCO3
CCO4
CCO5
CCOCom
+
_
PELV(Class2:USA)
PWR STAT
PROG
100Hr/100%
®
PSSig
P/N500-10634
©
2006LutronElectronicsCo.,Inc.
12345
ON
PowerWiringCableadod ePoderC âblaged'alimentation
DistributionPanel
PaneldeDistribución
PanneaudeDistribution
Ground/Tierra/Terre
Neutral/Neutro/Neutre
Black/Negro/Noir
Green/V erde/V ert
White/Blanco/Blanc
Red/Rojo/RougeOR
Orange/Anaranjado/Orange*
SwitchedHot/InterruptorVivo/CourantCommuté
DimmedHot/AtenuadorVivo/CourantTamisé*
Dimmed Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10
ECO-series dimming ballasts.
El Atenuador V ivo es para ser utilizado únicamente con las series de balastos
de atenuaci ó n Hi-Lume FDB o Eco-10 ECO de Lutron.
Courant T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avec
le ballast de gradation Eco-10 ECO-series de Lutron.
P/N 500-10634
*
*
*
Hot/Vivo/Chargé
For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.
Blue/Bleu/Azul
120V277V
*
USA,Canada
1-800-523-9466
Mexico
1-888-235-2910
®
www .lutron.com
RTA-RX-F-SC
15V
CONFIGURACIONES
REGLAGES
SETTINGS
R e fertotheInstallersGuideformore
detailedinstructions.
ConsultelaGuíadeInstaladorespara
informaciónmásdetallada.
RéférerauGuided’installationpourplusde
renseignementsdétaillés.
120/277V60Hz
16AMax.
0-10
V
Red&Black/Rojo&Negro/Rouge&Noir
RadioT o uch
TM
C o o p er sbur g, PA1 803 6 U S A
R T A-RX-F-SC
LISTED243C
Ind.Cont.Eq.
12
345678910
1 1
12 1 3 14
15 16
Occ.Com
OccSig
24V
CirCom
CCO1
CCO2
CCO3
CCO4
CCO5
CCOCom
+
_
PELV(Class2:USA)
PWR STAT
PROG
100Hr/100%
®
PSSig
P/N500-10634
©
2006LutronElectronicsCo.,Inc.
12345
ON
PowerWiringCableadod ePoderC âblaged'alimentation
DistributionPanel
PaneldeDistribución
PanneaudeDistribution
Ground/Tierra/Terre
Neutral/Neutro/Neutre
Black/Negro/Noir
Green/V erde/V ert
White/Blanco/Blanc
Red/Rojo/RougeOR
Orange/Anaranjado/Orange*
SwitchedHot/InterruptorVivo/CourantCommuté
DimmedHot/AtenuadorVivo/CourantTamisé*
Dimmed Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10
ECO-series dimming ballasts.
El Atenuador V ivo es para ser utilizado únicamente con las series de balastos
de atenuaci ó n Hi-Lume FDB o Eco-10 ECO de Lutron.
Courant T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avec
le ballast de gradation Eco-10 ECO-series de Lutron.
P/N 500-10634
*
*
*
Hot/Vivo/Chargé
For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.
Blue/Bleu/Azul
120V277V
*
USA,Canada
1-800-523-9466
Mexico
1-888-235-2910
®
www .lutron.com
RTA-RX-F-SC
15V
CONFIGURACIONES
REGLAGES
SETTINGS
R e fertotheInstallersGuideformore
detailedinstructions.
ConsultelaGuíadeInstaladorespara
informaciónmásdetallada.
RéférerauGuided’installationpourplusde
renseignementsdétaillés.
120/277V60Hz
16AMax.
0-10
V
Red&Black/Rojo&Negro/Rouge&Noir
LUT-ELI-3PHUnit RadioTouchUnitA RadioTouchUnitB
120/277V
feedbackup/
Emergency
power
120/277V
feedbackup/
Emergency
power
FlipDip
Switch2to
thedown
position
FlipDip
Switch2to
thedown
position
(2)Signal
(6)CircuitCommon
Toadditional
RadioTouch
controllers
(100maximum)
AdditionalRadioTouchControllerforBackup/
EmergencyLight(s)
Availablepowerfromthisunit
fordaylightsensorsmustbe
deratedto15mA.
(8) (2)(7) (4)(1) (6)
Installing a LUT-ELI-3PH Unit in a
RadioTouch® System (continued)
NEC® Class 2/PELV Connections
Note: Whenwiringforabackup/emergencysourceof
power,theRadioTouchController(modelsRTA-RX-F,
RTA-RX-F-SC,RTA-RXSW),beingusedforthebackup/
emergencylights(UnitAandB)cannotbecontrolledby
anoccupancysensor.UnitsAandBDIPswitch2must
beinthedownposition.
NEC Class 2/PELV Wiring to RadioTouch
Controllers
OneLUT-ELI-3PHcanbeconnectedinparallelwithup
to100RadioTouchControllers.
1. FlipDIPswitch2ontheRadioTouchControllertothe
downposition.
2. Disconnectanyoccupancysensorswiredtothe
RadioTouchController.
3. Makethefollowingconnections.
From LUT-ELI-3PH Unit To RadioTouch Controller
Terminal8(+VInput) Terminal4(24V ),UnitAonly
Terminal7
(CircuitCommon)
Terminal6(CirCom)
Terminal1(Signal) Terminal2(OccSig)
Test the System
Pleaseperformthefollowingteststoensureproper
installation.
1. TurnoffoneoftheNormal(Non-Essential)phase(s)
breaker(s)thattheLUT-ELI-3PHunitismonitoring.
You should see the following:
•AlllightscontrolledbyEmergency(Essential)panel
willgotoFULLINTENSITY(factoryset).
•PHASEON/OFFstatusIndicator(green)willturn
OFFastheabovetestcreatesaphasefailure.
•Uponturningthebreakerbackon,alllightsshould
returntotheirpreviousintensity.
2. PressandholdswitchSW1ontheLUT-ELI-3PHunit.
You should see the following:
•TESTLED(orange)willturnON.
•AlllightscontrolledbyEmergencyRadioTouch
controllerwillgotoFULLINTENSITY(factoryset).
Note: PHASEON/OFFstatusindicator(green)will
notturnOFFastest#2doesnotcreateaphase
failure.
•UponreleasingswitchSW1,alllightswillreturnto
theirpreviousintensities.
Note:OnlyoneRadioTouchunitcanhaveits
24V (number4)terminalconnectedtoterminal
8(+VInput)ontheLUT-ELIunitregardlessofthe
numberofwiredRadioTouchunits.
(2) (6)
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 4 LUT-ELI-3PH Installation Guide
Installing a LUT-ELI-3PH Unit in a
Panel-Based System
Line Voltage Connections
WARNING! Danger of shock. May result
in serious injury or death.DONOTWIRE
WHENLIVE!Switchoffpowertoallpower
feedsviacircuitbreakerorisolatorbefore
wiringorservicingtheLUT-ELI-3PHunitand
Panel-BasedSystem.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a
certified electrician, following local codes.
Note: Providepropershort-circuitandovercurrent
protectionatthedistributionpanel.Maximumcircuit
breakerratingof20A.
WiringfromMainswithGP,LP,XP,andXPS/LCPPanels
PhaseA
Normal
Power
Normal
topanel
Red
Red
Red
White
Green
PhaseB
PhaseC
Neutral
Ground
WiringfromNormal(Non-Essential)GPPanel
DH1 SH1 H1 DH2 SH2 H2 DH3 SH3 H3
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
12 11 10 987654321
CLASS2LOWVOLTAGEWIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
Red
Red
Red
White
Green(togroundlug)
Typicalload
circuit
Control
wiringto
circuit
selector
GP3panelshown
Branch
circuit
breakers
Normalpower
feedwiring
Terminal
blocks
Neutral
block
Groundlug
N
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 5
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
NEC® Class 2/PELV: USA Connections
Notes
• PullNECClass2/PELVwiringforsystem
communications.
• NECClass2/PELVwiringmustbedaisy-chained.
• NECClass2/PELVwiringmustberunseparatelyfrom
line(mains)voltage.
• ALUT-ELI-3PHunitcanbeplacedanywhereonthe
powerpanellink.
Wiring Notes
• NECClass2/PELVwiringlinkis500to2000feet
(152to610m),useLutron®cableGRX-CBL-46L:
-Two12AWG(2.5mm
2
)forcontrolwiring
(+Vandcom)
-Onetwisted,shieldedpair22AWG(0.5mm
2
)
fordatalink
-One18AWG(1.0mm
2
)forsenselinebetween
panels.
• Lutronhasalsoapprovedsmaller-gaugecable
fromBelden®,LibertyWire&Cable®,AlphaWire
Company,andSignatureWireCorp.AskforLutron
GRAFIKEye®Cable.
Paneltopanelwiring
Seeaboveforwiringnotes
Dimmingpanel
Powerpanellink
LUT-ELI-3PHUnit
Processorpanel
Wallstationlinks
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 6 LUT-ELI-3PH Installation Guide
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
CLASS2LOWVOLTAGEWIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
DataAOKPower DataBOK
1234D5
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
1
2
3,4
5
1
2
3,4
DataAOKPower DataBOK
1234D5
CD
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
1234D5
S
ELECT
C
IRCUIT
S
ELECT
C
IRCUIT
Link
B
Link
A
Link
B
1234D5
CD
12 11 10 98765432112 11 10 987654321
Shield/
Drain
Tolightingcontrols
orprocessors
Control
Wiring:
(2)12AWG
(2.5mm
2
)
1:Common
2:24V
DataLink:
(1)shielded,
twistedpair
18AWG
(1.0mm
2
)
3:MUX
4:MUX
Sense:
(1)18AWG
(1.0mm
2
)
5:Senseline
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
NEC® Class 2/PELV Panel to Panel Wiring Notes
• EmergencyPower:Theadditional18AWG(1.0mm
2
)wire
isa“sense”linefromterminal12ontheLUT-ELI-3PH.This
senselineallowsanEmergency(Essential)lightingpanelto
“sense”whenNormal(Non-Essential)powerislost.Ifmore
thanoneemergencylightingpanelneedstosenseNormal
(Non-Essential)fromaspecicLUT-ELI-3PHunit,youmay
havetorunadedicatedwirebetweeneachLUT-ELI-3PH
unitandEmergency(Essential)panel(s).
• Shield/Drain:Connectshieldingasshownbelowinwiring
exampleA:
-DonotconnecttoGround(Earth)orcircuitselector.
-Connectthebaredrainwiresandcutofftheoutside
shield.
Connections
LUT-ELI-3PH Circuit Selector
Terminal12(Sense) Terminal5(Sense)
Terminal11(Drain) TerminalD(Drain)
Terminal10(MUX) Terminal4(MUX)
Terminal9(MUX) Terminal3(MUX)
Terminal8(+VInput) Terminal2(+24VFW)
Terminal7
(CircuitCommon)
Terminal1
(Common)
Panel1 Panel2
Data A OK
Data B OK
Power OK
12345D
2
1
Circuit
A B
Common
24VFW
MUX
MUX
Drain
Sense
Comm
Drain
MUX
MUX
C
1
234
D
5
D
Link Link
S
ELECT
C
IRCUIT
S
ELECT
V
ALUE
V
IEW
V
ALUE
(4)12AWG
(2.5mm
2
)
• EachNECClass2/PELVterminalcanacceptonly
two18AWG(1.0mm
2
)wires.Two12AWG
(2.5mm
2
)conductorswon'tt.Connectasshown
belowinwiringexampleB.
Wiring Example A
Wiring Example B
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 7
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
Setting the Circuit Selector Normal/Emergency
Switch (SW6) Position
PanelsareshippedwithSW6(locatedatthebaseofeach
CircuitSelector)inthemiddleposition.Terminal5(sense)
hasnoaffectonthecircuitselectoroperation.
All Emergency Panels
• MoveSW6totherightEmergency(Essential)position.In
thisarrangement,theLUT-ELI-3PHunitwillbetheonlyunit
controllingthesenseline.Ifoneormorephasesgodown,
theLUT-ELI-3PHunitsendsasignalthroughthesense
linetoEmergency(Essential)panel(s).Thelightscontrolled
bythesepanelswillgoto‘ord’overridelevels(factoryset
tofullintensity).Whennormalpowerisrestored,lightswill
returntotheirpreviousintensities.
Note: Whenin‘ord’overridemode(factorysettofull
intensity),‘ord’willappearonvaluedisplaytoconrmthat
Emergency(Essential)positionisineffect.
Test the System
Pleaseperformthefollowingteststoensureproper
installation.
1. TurnoffoneoftheNormal(Non-Essential)phase(s)
breaker(s)thattheLUT-ELI-3PHunitismonitoring.
You should see the following:
•PHASEON/OFFstatusIndicator(green)willturnOFFas
theabovetestcreatesaphasefailure.
•CircuitselectoronEmergency(Essential)panelwillgoto
‘ord’overridemode.
•AlllightscontrolledbyEmergency(Essential)panelwillgo
toFullIntensity(FactorySet).
•ThecircuitselectorinEmergency(Essential)panelwillread
‘ord’onthevaluedisplaywheninEmergencymode.
•AlllightscontrolledbyNormal(Non-Essential)panelwill
freezeattheirrespectiveintensities.
2. PressandholdswitchSW1ontheLUT-ELI-3PHunit.
 You should see the following:
• TESTLED(orange)willturnON.
 Note: PHASEON/OFFstatusindicator(green)willnotturn
OFFastest#2doesnotcreateaphasefailure.
• CircuitSelectoronEmergency(Essential)Panelwillgoto
‘ord’overridemode.
• AlllightscontrolledbyEmergency(Essential)panelwillgo
toFULLINTENSITY(factoryset).
• ThecircuitselectoronEmergency(Essential)panelwill
read‘ord’onthevaluedisplaywheninEmergencyMode.
• AlllightscontrolledbyNormal(Non-essential)panelwill
freezeattheircurrentintensities.
• UponreleasingswitchSW1,alllightswillreturntotheir
originalintensities.
DataAOK
DataBOK
PowerOK
12345D
Load Type (See Instructions)
High-End Trim
Circuit Level
Low-End Trim
5
4
3
Value
Link A
Link B
2
1
Circuit
A B
Common
24VFW
MUX
MUX
Drain
Sense
Comm
Drain
MUX
MUX
C
1
234
D
5
D
Link Link
1-1
2-1
2-2
3-1
4-1
Incandescent
Neon / CC
Non-Dim
---
Unassigned
Fluorescent Lutron Tu-Wire
TM Ballast
Address ('Ad' displayed)
Zone Assignment w/ Circuit Schedule
Zone Assignment w/ Zone CaptureTM
Warning - Read instructions to set the Load
Type. Instructions show more load types.
Load Type Quick Reference:
S
ELECT
C
IRCUIT
S
ELECT
V
ALUE
V
IEW
V
ALUE
S
ELECT
V
ALUE
D
ISPLAYED
Normal Emergency
(Essential)(Non-Ess)
Fluorescent Lutron Hi-lume
R FDB Ballast
LINK 1 LINK 2
DataAOK
DataBOK
PowerOK
12345D
Load Type (See Instructions)
High-End Trim
Circuit Level
Low-End Trim
5
4
3
Value
Link A
Link B
2
1
Circuit
A B
Common
24VFW
MUX
MUX
Drain
Sense
Comm
Drain
MUX
MUX
C
1
234
D
5
D
Link Link
1-1
2-1
2-2
3-1
4-1
Incandescent
Neon / CC
Non-Dim
---
Unassigned
Fluorescent Lutron Tu-Wire
TM Ballast
Address ('Ad' displayed)
Zone Assignment w/ Circuit Schedule
Zone Assignment w/ Zone CaptureTM
Warning - Read instructions to set the Load
Type. Instructions show more load types.
Load Type Quick Reference:
S
ELECT
C
IRCUIT
S
ELECT
V
ALUE
V
IEW
V
ALUE
S
ELECT
V
ALUE
D
ISPLAYED
Normal Emergency
(Essential)(Non-Ess)
Fluorescent Lutron Hi-lume
R FDB Ballast
LINK 1 LINK 2
CircuitSelectorinNormal
(Non-Emergency)Panel
CircuitSelectorin
Emergency(Essential)Panel
Switchis
incenter
position
Switchis
movedto
theright
(emergency)
position
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 8 LUT-ELI-3PH Installation Guide
Installing a LUT-ELI-3PH Unit in an
EcoSystem® or Quantum® System
Line Voltage and NEC® Class 2/PELV Connections
WARNING! Danger of shock. May result in
serious injury or death.DONOTWIREWHEN
LIVE!Switchoffpowertoallpowerfeeds
viacircuitbreakerorisolatorbeforewiringor
servicingtheLUT-ELI-3PHunitandEcoSystem
lightingcontrolsystemorQuantumsystem.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when
accessing buttons and LEDs, the unit must be
accessed by a certified electrician, following
local codes.
Note: Providepropershort-circuitandovercurrent
protectionatthedistributionpanel.Maximumcircuit
breakerinstallationof20A.
ALutron®PP-120HorPP-277Hpowerpackmustbe
usedtopowertheLUT-ELI-3PHunitwhenusedwitha
bussupply.Boththepowerpackandthebussupplies
mustbefedfromanormal/emergencysupply.
E2
E1
1
2
3
4
5
6
7
8
E2
E1
24V
(Red)
Common
(Black)
Hot
Neutral
From120or277V
Normal/Emergencysupply
Common
Emerg.
signal
Connectupto8
Quantumhubs
100-277V
Normal/Emergency
supply
Power
pack*
WiringtoQuantumsystems
*PP-120HorPP-277H
WiringtoEcoSystemBusSupply
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
100-347V
50/60Hz
3-phase
normalsupply
SeeFigure#1
orFigure#2
onpage2of
thisguide.
Common
24V
24V
(Red)
Common
(Black)
Common
(pin5)
Emerg.
signal
(pin6)
Hot
Neutral
Power
pack*
From120or277V
Normal/Emergency
supply
Bussupply Bussupply
Connectupto32
bussupplies
100-277V
Normal/
Emergency
supply
*PP-120HorPP-277H
(8) (7) (1)
(8) (7) (1)
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 9
Installing a LUT-ELI-3PH Unit in a
GRAFIK Eye® QS Unit
NEC® Class 2/PELV Connections
WARNING! Danger of shock. May result in
serious injury or death.DONOTWIREWHEN
LIVE!Switchoffpowertoallpowerfeeds
viacircuitbreakerorisolatorbeforewiringor
servicingtheLUT-ELI-3PHunitandGRAFIK Eye
QSunit.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when
accessing buttons and LEDs, the unit must be
accessed by a certified electrician, following
local codes.
WiringtoaGRAFIK EyeQSControlUnit
Notes
• Providepropershort-circuitandovercurrent
protectionatthedistributionpanel.Maximum
circuitbreakerinstallationof20A.
• Whennormalpowerlossisdetectedatthe
LUT-ELI-3PHunit,allzonesintheGRAFIK EyeQS
unitswillgototheiremergencystates.
• TheGRAFIK EyeQSunitMUSTbepoweredfroma
normal/emergencypowerfeed.
Note:For1-phase2-wireapplication,connectphaseA,B,andCwireson
LUT-ELI-3PHtogetherforphasesensing.
´FACP´N/O
CONTACTS
TAGEWIRING
GND
SENSE
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 987654321
´FACP´
CP´N/O
C
CONTACTS
TAGEWIRING
S
ENS
E
N
O
T
US
E
D
LED
RADI
O
T
OUC
H
1
2
876543
7
98765432
1
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
CLASS2LOWVOLTAGEWIRING
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED3
RADIOTOUCH
12 11 10 9 87654321
Signal
+24V
Common
(3)18AWG
GRAFIK EyeQSunitQSGRJmodel(backview)
Normal/Emergency
20A120V
1-Phase2-Wire
powerfeed
(3)12AWG(2.5mm²)
120-127V
or
220-240V
distributionpanel
100-347V 
50/60Hz
3-phaseNormalsupply
SeeFigure#1orFigure#2
onpage2ofthisguide.
CCI SIG
24 V
CCI Com
(8) (7) (1)
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 10 LUT-ELI-3PH Installation Guide
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
Installing a LUT-ELI-3PH Unit with an
Energi Savr NodeTM Unit(s)
NEC® Class 2/PELV Connections
WARNING! Danger of shock. May result
in serious injury or death.DONOTWIRE
WHENLIVE!Switchoffpowertoallpower
feedsviacircuitbreakerorisolatorbefore
wiringorservicingtheLUT-ELI-3PHand
Energi Savr Nodeunit.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a
certified electrician, following local codes.
Notes: Providepropershort-circuitandovercurrent
protectionatthedistributionpanel.Maximumcircuit
breakerinstallationof20A.
• ALutron®PP-120HorPP-277Hpowerpackmustbe
usedtopowertheLUT-ELI-3PHunitwhenusedwithan
Energi Savr Nodeunit(s).Boththepowerpackandthe
Energi Savr Nodeunit(s)mustbefedfromanormal/
emergencysupply.
• WhennormalpowerlossisdetectedattheLUT-ELI-3-
PHunit,allzonesintheEnergi Savr Nodeunitwillgoto
theiremergencystates.
• TheEnergi Savr NodeunitMUSTbepoweredfroma
normal/emergencypowerfeed.
WiringfromEnergi Savr NodeUnits
Note: For1-phase2-wireapplication,connect
phaseA,B,andCwiresonLUT-ELI-3PHtogether
forphasesensing.
Connections
LUT-ELI-3PH Energi Savr Node Unit Power Pack
Terminal8(+VInput) ------------------------- RedWire
Terminal7
(CircuitCommon)
Com
(EmergencyCCIInput)
BlackWire
Terminal1(Signal) Emerg(EmergencyCCIInput) ---------------
*NECClass2/PELVWiring
18AWG(1.0mm²)
Note:
Upto32QSN-4T16-Sor
QSN-4S16-Sunitscanbe
connectedto1LUT-ELI-3PH
*Signal
*Common(Black)
*+24V (Red)
PP-120Hor
PP-277H
*Signal
*Common
*Common
2#12
InputPower
(120or277V )
Normal/EmergencyPower
(8) (7) (1)
100-347V 
50/60Hz
3-phaseNormalsupply
SeeFigure#1orFigure#2
onpage2ofthisguide.
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 11
Emergency Power Mode
Setup: LCP128TM / Softswitch128®
with LUT-ELI-3PH
Thisstepisonlyperformedifanemergencypattern*is
neededwhennormalpowerislost.Allcontroldevice
inputsandtimeclockeventsareignoredwhilein
emergencypowermode.Thisstepwilldeneifthe
panelhasemergencycircuitsandhowtocongurethe
emergencypattern.
•Foralltheemergency(essential)lightingpanels,move
theemergency switchestotherightposition(see
illustrationbelow).
•Theessentialandnon-essentialpanelsmustbecon-
nectedbyasenselinewiredtoterminal 5onthelink
connectorontheLCP128/Softswitch128controller(see
illustrationbelow).Forwiringdetails,seetheInstallation
Guide.
*Inthisconguration,theemergency(essential)lighting
panelwill“sense”thenormalpanels’power.When
normalpowerislost,theemergencypanelwillgotothe
emergencypattern(factorysettoallcircuitsOn).When
normalpowerisrestored,lightingcircuitsandcontact
closureoutputsreturntotheirpreviousstate.
UseTerminal5toconnectasenseline
betweenemergencyandnormalpanels,
orbetweentheLUT-ELI-3PHunitandone
ormoreemergencypanels.An#18AWG
wireisrecommendedforthesenseline.
ThreepositionEmergency Switchislocatedatthe
bottomoftheLCP128/Softswitch128controller.
12345D
TopoftheLCP128/Softswitch128Controller
LeftPosition
RightPosition
(Non-Essential)
(Essential)
CenterPosition
(NoresponsetoEmergency)
Notes:
•IfUL924certicationisrequired,theLutron®
EmergencyLightingInterface(LUT-ELI-3PH)maybe
usedtomeetcode.TheLUT-ELI-3PHunitsenses
thenormal(non-essential)linevoltageonallthree
phases(3PH)ofnormalpower.Whenoneormore
phasesofpowerarelost,theLUT-ELI-3PHunitwill
sendasignaltoterminal 5ontheLCP128/Soft-
switch128controller(s).Whentheemergency
switchissettotherightposition(essential)the
emergencypatternwillberecalled.TheLUT-ELI-3-
PHunitcanbeusedwithoneormultiplepanel
systems.
•Lossofnormalpowercanbesimulatedbyturning
offallconnectednormal(non-essential)panelcontrol
breakers.
•Whentheemergencyswitchisinitscenterposition
(asshipped),terminal5thepaneldoesnotrespond
toemergency.
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 12 LUT-ELI-3PH Installation Guide
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
CLASS2LOWVOLTAGEWIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
NormallyOpen
FACPInput
LUT-ELI-3PHunit
To24V power
FireAlarmControlPanel
(providedbyothers)
Common
Normally
open
NEC® Class 2/PELV Wiring to
Fire Alarm Control Panel (FACP)
• Useonlywithnormallyopen(terminals3and4)ornormally
closed(terminals5and6)drycontactclosure.Whenthe
propercontactstateistriggered,itmustbemaintained
fortheLUT-ELI-3PHunittogointoEmergencyMode.
Oncethecontactisreleased,theLUT-ELI-3PHunitwill
returntheGRAFIKSystemsTMGP,LP,XPpanels,XPS,
LCP,RadioTouch®controller,EcoSystem®BusSupply,
EnergiSavrNodeTMunit,orQuantum®BusSupplybackto
Normaloperationmode.
• TheLUT-ELI-3PHunitwillhaveafactoryinstalled
jumpertoprovidethenormallyclosedinputsignal
forthesupervisorycircuitwhenanormallyclosed
FACPinputisnotprovided.
• ConsultyourFireAlarmControlPanel’sinstruction
manualbeforeconnectingtotheLUT-ELI-3PHunit.
• DonotconnectanyvoltagesourcetotheFACP
inputsontheLUT-ELI-3PHunit.Ifvoltageis
providedbytheFACPandconnectedtotheLUT-
ELI-3PHunit,itcandamagetheLUT-ELI-3PHunit.
´FACP´N/C
CONTACTS
´FACP´N/O
CONTACTS
CLASS2LOWVOLTAGEWIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOTUSED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
SupervisoryCircuit
(NormallyClosed
FACPInput)
LUT-ELI-3PHunit
To24V power
FireAlarmControlPanel
(providedbyothers)
Common
Normally
closed
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 13
Troubleshooting RadioTouch®
Symptom Possible Cause Solution
Lightsareatfull
intensityandcan
notbecontrolled
byanaddressed
transmitter
LUT-ELI-3PHunitisnotconnected
toSignalontheRadioTouch
Controller
Connectterminal2‘OccSig’fromtheRadioTouch
Controllertoterminal1‘Signal’ontheLUT-ELI-3PHunit
Oneormoreofthephasesfeeding
theLUT-ELI-3PHunitareoff(phase
LEDontheLUT-ELI-3PHunitwill
beoff)
TurnONallnormalpowerphasestoLUT-ELI-3PHunit
Neutralisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectneutral
24V isnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectterminal4‘24V ’fromRadioTouchControllerto
terminal8‘+VInput’ontheLUT-ELI-3PHunit
ThereisashortacrossFACPand
normallyopencontact(FACPLED
willbeON)
Removeshort
Lightsdonot
turnONanddo
notgotohigh
endwhenthe
testswitchis
pressed
DIPswitch2ontheRadioTouch
ControllerisintheUPposition
MoveDIPswitch2ontheRadioTouchControllertothe
DOWNposition
24V andsignalwiresare
swapped
Connectterminal4‘24V ’fromtheRadioTouch
Controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal2‘OccSig’fromtheRadioTouch
Controllertoterminal1‘Signal’ontheLUT-ELI-3PHunit
24V andcommonwiresare
swapped
Connectterminal4‘24V ’fromtheRadioTouch
Controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal6‘CirCom’fromtheRadioTouch
Controllertoterminal7‘CircuitCommon’ontheLUT-ELI-
3PHunit
Commonandsignalwiresare
swapped
Connectterminal6‘CirCom’fromtheRadioTouch
Controllertoterminal7‘CircuitCommon’ontheLUT-
ELI-3PHunitandconnectterminal2‘Occsig’fromthe
RadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-
3PHunit
Lightsdonot
turnONanddo
notgotohigh
endwhenone
ormoreofthe
normalpower
phasesare
turnedOFF
DIPswitch2ontheRadioTouch
ControllerisintheUPposition
MoveDIPswitch2ontheRadioTouchControllertothe
DOWNposition
24V andsignalareswapped Connectterminal4‘24V ’fromtheRadioTouchController
toterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectterminal2‘OccSig’fromtheRadioTouchController
toterminal1‘Signal’ontheLUT-ELI-3PHunit
ThatRadioTouchControllerisnot
poweredbytheemergencycircuit
power
PowertheRadioTouchControllerfromtheemergency
circuitandnotfromnormal
Theemergencytransferswitchis
notswitchingover
Consulttransferswitchmanufacturefortroubleshooting
LUT-ELI-3PHunitisconnectedto
theemergencycircuit
ConnecttheLUT-ELI-3PHunittonormalpower
24V andcommonwiresare
swapped
Connectterminal4‘24V ’fromtheRadioTouch
Controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal6‘CirCom’fromtheRadioTouch
Controllertoterminal7‘CircuitCommon’ontheLUT-ELI-
3PHunit
Commonandsignalwiresare
swapped
Connectterminal6‘CirCom’fromtheRadioTouch
Controllertoterminal7‘CircuitCommon’ontheLUT-
ELI-3PHunitandconnectterminal2‘OccSig’fromthe
RadioTouchControllertoterminal1‘Signal’ontheLUT-ELI-
3PHunit
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 14 LUT-ELI-3PH Installation Guide
Troubleshooting Panel Based Systems
Symptom Possible Cause Solution
Lightsareat
fullintensity
andcannotbe
controlledby
thewallstation
(Circuitselector/
controller
reads“ord”),or
controllerreads
Emergency
Mode
Sensewireisnotconnectedfrom
theCircuitselector/controllertothe
LUT-ELI-3PHunit
Connectterminal5‘Sense’fromtheCircuitselector/
controllertoterminal12‘Sense’ontheLUT-ELI-3PHunit
Oneormoreofthephasesfeeding
theLUT-ELI-3PHunitareoff(phase
LEDontheLUT-ELI-3PHunitwill
beOFF)
TurnONallnormalpowerphasestoLUT-ELI-3PHunit
Neutralisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectneutral
24VFWisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectterminal2‘24VFW’fromtheCircuitselector/
controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
ThereisashortacrossFACPand
normallyopencontact(FACPLED
willbeON)
Removeshort
24VFWandsensewiresare
swapped
Connectterminal2‘24VFW’fromtheCircuitselector/
controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal5‘Sense’fromtheCircuitselector/
controllertoterminal12‘Sense’ontheLUT-ELI-3PHunit
Commonandsensewiresare
swapped
Connectterminal1‘Common’fromtheCircuitselector/
controllertoterminal7‘CircuitCommon’ontheLUT-ELI-
3PHunitandconnectterminal5‘Sense’fromtheCircuit
selector/controllertoterminal12‘Sense’ontheLUT-ELI-
3PHunit
Lightsdonot
turnONanddo
notgotohigh
endwhenthe
testswitchis
pressed
SW6ontheCircuitselector/
controllerisinthemiddlepositionor
farleftposition
MoveSW6ontheCircuitselector/controllertothefarright
position
24V andcommonwiresare
swapped
Connectterminal2‘24VFW’fromtheCircuitselector/
controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal1‘Common’fromtheCircuitselector/
controllertoterminal7‘CircuitCommon’ontheLUT-ELI-
3PHunit
Lightsdonot
turnONanddo
notgotohigh
endwhenone
ormoreofthe
normalpower
phasesare
turnedOFF
SW6ontheCircuitselector/
controllerisinthemiddlepositionor
farleftposition
MoveSW6ontheCircuitselector/controllertothefarright
position
24V andcommonwiresare
swapped
Connectterminal2‘24VFW’fromtheCircuitselector/
controllertoterminal8‘+VInput’ontheLUT-ELI-3PHunit
andconnectterminal1‘Common’fromtheCircuitselector/
controllertoterminal7‘CircuitCommon’ontheLUT-ELI-
3PHunit
ThatEmergencyPanelisnot
poweredbytheemergencycircuit
PowertheEmergencyPanelfromtheemergencycircuitand
notfromnormalpower
Theemergencytransferswitchis
notswitchingover
Consulttransferswitchmanufacturefortroubleshooting
LUT-ELI-3PHunitisconnectedto
theemergencycircuit
ConnecttheLUT-ELI-3PHunittonormalpower
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 15
Troubleshooting Energi Savr NodeTM Installations
Symptom Possible Cause Solution
Lightsareatfull
intensity.Unitwill
notrespondto
localcontrolor
inputsignals.
Signalwireisnotconnectedfrom
theLUT-ELI-3PHunittotheEnergi
Savr Nodeunit
Connect‘Emerg’terminalfromtheEnergi Savr Nodeunitto
terminal1‘Signal’ontheLUT-ELI-3PHunit
Oneormoreofthephasesfeeding
theLUT-ELI-3PHunitareoff(phase
LEDontheLUT-ELI-3PHunitwill
beOFF)
TurnONallnormalpowerphasestoLUT-ELI-3PHunit
Neutralisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectneutral
24VFWisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDon
theLUT-ELI-3PHunitwillbeOFF)
Connectredwire(24V )fromthePP-120HorPP-277H
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunit
ThereisashortacrossFACPand
normallyopencontact(FACPLED
willbeON)
Removeshort
Lightsdonot
turnONanddo
notgotohigh
endwhenthe
testswitchis
pressed
24V andcommonwiresare
swapped
Connectredwire(24V )fromthePP-120HorPP-277H
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectblackwire(Common)fromthePP-120Hor
PP-277Hunittoterminal7‘CircuitCommon’onthe
LUT-ELI-3PHunit
Lightsdonot
turnONanddo
notgotohigh
endwhenone
ormoreofthe
normalpower
phasesare
turnedOFF
24V andcommonwiresare
swapped
Connectredwire(24V )fromthePP-120HorPP-277H
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectblackwire(Common)fromthePP-120Hor
PP-277Hunittoterminal7‘CircuitCommon’onthe
LUT-ELI-3PHunit
EmergencyPanelisnotpoweredby
theemergencycircuit
PowertheEmergencyPanelfromtheemergencycircuitand
notfromnormalpower
Theemergencytransferswitchis
notswitchingover
Consulttransferswitchmanufacturerfortroubleshooting
LUT-ELI-3PHunitisconnectedto
theemergencycircuit
ConnecttheLUT-ELI-3PHunittonormalpower
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
Lutron® | 16 LUT-ELI-3PH Installation Guide
Troubleshooting EcoSystem® or Quantum® System Installations
Symptom Possible Cause Solution
Lightsareatfull
intensity.System
willnotrespond
tolocalcontrol
orinputsignals.
Signalwireisnotconnectedfromthe
LUT-ELI-3PHunittotheEcosystem
bussupply
Connect‘CCI-EMERG’terminalfromtheEcosystembus
supplytoterminal1‘Signal’ontheLUT-ELI-3PHunit
Signalwireisnotconnectedfromthe
LUT-ELI-3PHunittotheQuantum
bussupply
Connect‘EM’terminalfromtheQuantumbussupplyto
terminal1‘Signal’ontheLUT-ELI-3PHunit
Oneormoreofthephasesfeeding
theLUT-ELI-3PHunitareoff(phase
LEDontheLUT-ELI-3PHunitwillbe
OFF)
Turnonallnormalpowerphasesto
LUT-ELI-3PHunit
NeutralisnotconnectedontheLUT-
ELI-3PHunit(phaseLEDontheLUT-
ELI-3PHunitwillbeOFF)
Connectneutral
24VFWisnotconnectedontheLUT-
ELI-3PHunit(phaseLEDontheLUT-
ELI-3PHunitwillbeOFF)
Connectredwire(24V )fromthePP-120HorPP-
277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PH
unit
ThereisashortacrossFACPand
normallyopencontact(FACPLED
willbeON)
Removeshort
Lightsdonot
turnONanddo
notgotohigh
endwhenthe
testswitchis
pressed
24V andcommonwiresare
swapped
Connectredwire(24V )fromthePP-120HorPP-
277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PH
unitandconnectblackwire(Common)fromthePP-120H
orPP-277Hunittoterminal7‘CircuitCommon’onthe
LUT-ELI-3PHunit
Lightsdonot
turnONanddo
notgotohigh
endwhenone
ormoreofthe
normalpower
phasesare
turnedOFF
24V andcommonwiresare
swapped
Connectredwire(24V )fromthePP-120HorPP-
277Hunittoterminal8‘+VInput’ontheLUT-ELI-3PH
unitandconnectblackwire(Common)fromthePP-120H
orPP-277Hunittoterminal7‘CircuitCommon’onthe
LUT-ELI-3PHunit
EmergencyPanelisnotpoweredby
theemergencycircuit
PowertheEmergencyPanelfromtheemergencycircuit
andnotfromnormalpower
Theemergencytransferswitchisnot
switchingover
Consulttransferswitchmanufacturerfortroubleshooting
LUT-ELI-3PHunitisconnectedto
theemergencycircuit
ConnecttheLUT-ELI-3PHunittonormalpower
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide Lutron® | 17
Troubleshooting a GRAFIK Eye® QS Installation
Symptom Possible Cause Solution
Lightsareat
fullintensity.
Systemwillnot
respondto
localcontrolor
inputsignals.
LUT-ELI-3PHunitisnotconnected
to‘CCISIG’ontheGRAFIK EyeQS
unit
Connectthe‘CCISIG’terminalfromtheGRAFIK EyeQS
unittoterminal1‘Signal’ontheLUT-ELI-3PHunit
Oneormoreofthephasesfeeding
theLUT-ELI-3PHunitareoff(phase
LEDontheLUT-ELI-3PHunitwillbe
off)
TurnonallnormalpowerphasestoLUT-ELI-3PHunit
Neutralisnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDonthe
LUT-ELI-3PHunitwillbeOFF)
Connectneutral
24V isnotconnectedonthe
LUT-ELI-3PHunit(phaseLEDonthe
LUT-ELI-3PHunitwillbeOFF)
Connectthe‘24V ’terminalfromtheGRAFIK EyeQS
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunit
ThereisashortacrossFACPand
normallyopencontact(FACPLED
willbeON)
Removeshort
Lightsdonot
turnONanddo
notgotohigh
endwhenthe
testswitchis
pressed
24V andsignalareswapped Connectthe‘24V ’terminalfromtheGRAFIK EyeQS
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectthe‘CCISIG’terminalfromtheGRAFIK EyeQS
unittoterminal1‘Signal’ontheLUT-ELI-3PHunit
24V andcommonwiresare
swapped
Connectthe‘24V ’terminalfromtheGRAFIK EyeQS
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectthe‘CCICom’terminalfromtheGRAFIK EyeQS
unittoterminal7‘CircuitCommon’ontheLUT-ELI-3PH
unit
Commonandsignalareswapped Connectthe‘CCICom’terminalfromtheGRAFIK EyeQS
unittoterminal7‘CircuitCommon’ontheLUT-ELI-3PH
unitandconnectthe‘CCISIG’terminalfromtheGRAFIK
EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit
GRAFIK EyeQSunit‘CCISIG’input
hasnotbeensetupasanemer-
gencyinput
RefertoprogrammingguidefortheGRAFIK EyeQSunit
onhowtoprogramthe‘CCISIG’inputasanemergency
input.
Lightsdonot
turnONanddo
notgotohigh
endwhenone
ormoreofthe
normalpower
phasesare
turnedOFF
24Vandsignalareswapped Connectthe‘24V ’terminalfromtheGRAFIK EyeQS
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectthe‘CCISIG’terminalfromtheGRAFIK EyeQS
unittoterminal1‘Signal’ontheLUT-ELI-3PHunit
TheGRAFIK EyeQSunitisnotpow-
eredbytheemergencycircuitpower
PowertheGRAFIK EyeQSunitfromtheemergencycircuit
andnotfromnormal
Theemergencytransferswitchis
notswitchingover
Consulttransferswitchmanufacturefortroubleshooting
LUT-ELI-3PHunitisconnectedto
theemergencycircuit
ConnecttheLUT-ELI-3PHunittonormalpower
24V andcommonwiresare
swapped
Connectthe‘24V ‘terminalfromtheGRAFIK EyeQS
unittoterminal8‘+VInput’ontheLUT-ELI-3PHunitand
connectthe‘CCICom’terminalfromtheGRAFIK EyeQS
unittoterminal7‘CircuitCommon’ontheLUT-ELI-3PH
unit
Commonandsignalwiresare
swapped
Connectthe‘CCICom’terminalfromtheGRAFIK EyeQS
unittoterminal7‘CircuitCommon’ontheLUT-ELI-3PH
unitandconnectthe‘CCISIG’terminalfromtheGRAFIK
EyeQSunittoterminal1‘Signal’ontheLUT-ELI-3PHunit
GRAFIK EyeQSunit‘CCISIG’input
hasnotbeensetupasanemer-
gencyinput
RefertoprogrammingguidefortheGRAFIK EyeQSunit
onhowtoprogramthe‘CCISIG’inputasanemergency
input.
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide
NOTES:
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide
NOTES:
Emergency Lighting Interface LUT-ELI-3PH
|
Installation Guide
LUT-ELI-3PH Installation Guide
PrintedintheU.S.A.
P/N031-353Rev.A09/10
Internet:www.lutron.com
WORLD HEADQUARTERS
LutronElectronicsCo.,Inc.
7200SuterRoad
Coopersburg,PA18036-1299U.S.A.
TOLLFREE:1.800.523.9466
(U.S.A.,Canada,andtheCaribbean)
Tel:+1.610.282.3800
Fax:+1.610.282.1243
EUROPEAN HEADQUARTERS
LutronEALtd.
LutronHouse
6SovereignClose
Wapping
London,E1W3JF,UK
FREEPHONE:0800.282.107(U.K.)
Tel:+44.(0)20.7702.0657
Fax:+44.(0)20.7480.6899
ASIAN HEADQUARTERS
Singapore
LutronGL,Ltd.
15HoeChiangRoad
#07-03TowerFiteen
Singapore089316
TOLLFREE:800.120.4491
Tel:+65.6220.4666
Fax:+65.6220.4333
HONG KONG SALES OFFICE
Tel:+852.2104.7733
Fax:+852.2104.7633
LutronElectronicsCo.,Inc.,reservestherighttomake
improvementsorchangesinitsproductswithoutprior
notice.Althougheveryattemptismadetoensurethat
thisinformationisaccurateanduptodate,please
checkwithLutrontoconrmproductavailability,latest
specicationsandsuitabilityforyourapplication.
Lutron Electronics Co., Inc.
One Year Limited Warranty
For a period of one year from the date of purchase, and subject to the exclusions and restrictions
described below, Lutron warrants each new unit to be free from manufacturing defects. Lutron
will, at its option, either repair the defective unit or issue a credit equal to the purchase price of
the defective unit to the Customer against the purchase price of comparable replacement part
purchased from Lutron. Replacements for the unit provided by Lutron or, at its sole discretion,
an approved vendor may be new, used, repaired, reconditioned, and/or made by a different
manufacturer.
If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron
commissioned lighting control system, the term of this warranty will be extended, and any credits
against the cost of replacement parts will be prorated, in accordance with the warranty issued
with the commissioned system, except that the term of the unit’s warranty term will be measured
from the date of its commissioning.
EXCLUSIONS AND RESTRICTIONS
This Warranty does not cover, and Lutron and its suppliers are not responsible for:
1. Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party
as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident,
interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit
breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions
provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety
Standards of Underwriter's Laboratories; (c) use of incompatible devices or accessories; (d)
improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g)
an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems
beyond Lutron’s control.
2. On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/
or reprogram the unit or any of its components.
3. Equipment and parts external to the unit, including those sold or supplied by Lutron (which may
be covered by a separate warranty).
4. The cost of repairing or replacing other property that is damaged when the unit does not work
properly, even if the damage was caused by the unit.
EXCEPT AS EXPRESSLY PROVIDED IN THIS WARRANTY, THERE ARE NO EXPRESS OR
IMPLIED WARRANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY. LUTRON DOES NOT
WARRANT THAT THE UNIT WILL OPERATE WITHOUT INTERRUPTION OR BE ERROR
FREE.
NO LUTRON AGENT, EMPLOYEE OR REPRESENTATIVE HAS ANY AUTHORITY TO BIND
LUTRON TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY CONCERNING THE
UNIT. UNLESS AN AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY AN AGENT,
EMPLOYEE OR REPRESENTATIVE IS SPECIFICALLY INCLUDED HEREIN, OR IN STANDARD
PRINTED MATERIALS PROVIDED BY LUTRON, IT DOES NOT FORM A PART OF THE BASIS
OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE
ENFORCEABLE BY CUSTOMER.
IN NO EVENT WILL LUTRON OR ANY OTHER PARTY BE LIABLE FOR EXEMPLARY,
CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, DAMAGES FOR LOSS OF PROFITS, CONFIDENTIAL OR OTHER INFORMATION, OR
PRIVACY; BUSINESS INTERRUPTION; PERSONAL INJURY; FAILURE TO MEET ANY DUTY,
INCLUDING OF GOOD FAITH OR OF REASONABLE CARE; NEGLIGENCE, OR ANY OTHER
PECUNIARY OR OTHER LOSS WHATSOEVER), NOR FOR ANY REPAIR WORK UNDERTAKEN
WITHOUT LUTRON’S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED
TO THE INSTALLATION, DEINSTALLATION, USE OF OR INABILITY TO USE THE UNIT OR
OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY, OR
ANY AGREEMENT INCORPORATING THIS WARRANTY, EVEN IN THE EVENT OF THE FAULT,
TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, BREACH OF CONTRACT OR BREACH
OF WARRANTY OF LUTRON OR ANY SUPPLIER, AND EVEN IF LUTRON OR ANY OTHER
PARTY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
NOTWITHSTANDING ANY DAMAGES THAT CUSTOMER MIGHT INCUR FOR ANY REASON
WHATSOEVER (INCLUDING, WITHOUT LIMITATION, ALL DIRECT DAMAGES AND ALL
DAMAGES LISTED ABOVE), THE ENTIRE LIABILITY OF LUTRON AND OF ALL OTHER
PARTIES UNDER THIS WARRANTY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN
CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR,
OR REPLACEMENT OF THE UNIT, OR ANY AGREEMENT INCORPORATING THIS WARRANTY,
AND CUSTOMER'S SOLE REMEDY FOR THE FOREGOING, WILL BE LIMITED TO THE
AMOUNT PAID TO LUTRON BY CUSTOMER FOR THE UNIT. THE FOREGOING LIMITATIONS,
EXCLUSIONS AND DISCLAIMERS WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY
APPLICABLE LAW, EVEN IF ANY REMEDY FAILS ITS ESSENTIAL PURPOSE.
TO MAKE A WARRANTY CLAIM
To make a warranty claim, promptly notify Lutron within the warranty period described above
by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion,
will determine what action, if any, is required under this warranty. To better enable Lutron to
address a warranty claim, have the unit's serial and model numbers available when making the
call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is
necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a
representative from a Lutron approved vendor to Customer's site, and/or coordinate a warranty
service call between Customer and a Lutron approved vendor.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.
Belden is a registered trademark of Belden, Inc., Richmond, Indiana. Liberty Wire & Cable is a
registered trademark of Liberty Wire & Cable, Colorado Springs, Colorado.
Lutron, EcoSystem, GRAFIK Eye, Quantum, RadioTouch, Softswitch128, and the sunburst logo are
registered trademarks and Energi Savr Node and LCP128 are trademarks of Lutron Electronics
Co., Inc.
© 2010 Lutron Electronics Co, Inc.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20