TK 56910-11-IS Rev. A, 05/21 ©2021 Trane Technologies 7
STEP 4 - CAN Communication Procedures
Resistors are required at each end of the CAN network to prevent signal reflections. Two
resistors in entire harness will measure 60 ohms (two 120 ohm resistors, in parallel).
IImmppoorrttaanntt:: The following procedure must be followed to ensure the CAN communications work
properly.
1. With the power off, measure the resistance between CCAANN HHii and CCAANN LLooww (terminals 2 and
3) on the CAN_0, P2 connection.
a. You should have a measurement of between 60-120 ohms.
b. If you do not have a measurement between 60-120 ohms, communications may work
temporarily but will be unreliable and eventually fail. Continue to Step 2.
2. Check for correct value CAN termination resistance in the harness. Refer to your unit wiring
schematic for location of factory installed CAN resistors.
a. Add or remove termination resistance as necessary.
b. Repeat Step 1 above and confirm measurement is between 60-120 ohms.
3. Return to page 4, step 5.
Figure 6. The Correct CAN Network Configuration Shown
120 ohm
Optional HMI
TK BlueBox Module
Electronic Control Module
(ECM)
A second 120 ohm resistor
is required as shown
CAN Hi
CAN Low
RCS1774
NNoottee:: A 120 ohm termination resistor is located inside the TK BlueBox module across CAN Hi
and CAN Low on CAN_0. TK BlueBox Module DOES NOT contain a termination resistor on
CAN_1.
For Activation Procedures, refer to:
Connected Bus HVAC Operator’s Manual (TK 56773-3-OP)
This manual can be found at www.thermoking.com and Asset Library