6©2021 Trane Technologies TK 56990-11-IS Rev. A
Step 4 – Setup Procedures
NNoottee:: See the IntelligAIRE III Diagnostic Manual TK 54650 for detailed information on flash
loading and connecting using the CANDiag software.
1. Reconnect power to the bus HVAC unit before proceeding.
2. Flash load firmware version 4.02.05 or later into main module.
3. Connect CANDiag and open Main Module window.
4. Go to Setup Parameter tab and click Read Data.
5. When upload is complete, the Customized Configuration box will show the current
configuration number loaded in the module.
6. Go to the APS Panel Count parameter and select the correct number of panels installed:
• RLF Series Units:5
7. Go to Cont Evap Blower parameter and click the check box to enable.
8. Go to APS Fail Indicator – This is an optional selection:
•IIff bbooxx iiss sseelleecctteedd:: the AC Fail Indicator lamp on the control panel wwiillll iilllluummiinnaattee when
aallaarrmm ccooddee 008844 is detected.
•IIff bbooxx IISS NNOOTT sseelleecctteedd:: The AC Fail Indicator lamp on the control panel wwiillll nnoott
iilllluummiinnaattee when aallaarrmm ccooddee 008844 is detected. This is the default setting.
9. Go to Basic Parameters and adjust the following evaporator speed value %:(RLF – Series
units with brushless motors only).
• Evap Max Speed: Values % set to 9955
• Evap Max Speed H: Values % set to 9955
• Evap Med Speed: Values % set to 8800
• Evap Min Speed: Values % set to 6677
10.Click Send Data to download the modified configuration back into the module.
11.The configuration process for Air Purification is now complete.
12.Reinstall air filter and grille and return bus to service.