Danfoss SpeedUp Eco Wall Heating - Wet plaster User guide

Type
User guide
Application Sheet
SpeedUp Eco Wall Heating
Wet plaster
1
2
3
4
5
1 Wall heating dowel, 3-part, 70 mm
2 Danfoss wall heating metalgrid
3 SpeedUp Eco panel, 30 mm
4 Danfoss composite pipe 16 x 2 mm
5 Heating plaster over SpeedUp, 15 mm
Technical Data Wall heating with wet plastering
Wall covering 15 mm Heating plasters over SpeedUp; single layer plastering, edge
insulation strips required
Constructional thickness 45 mm Dimensions without unfinished wall, without tiles
Thermal resistance R 0.75 m²K / W Thermal resistance value for SpeedUp Eco panel
Pipe spacing 125-250 mm EZ = 125; CZ = 250;
Requirements and specialities Heating plasters must show a good thermal conductivity. Light plasters and heat insula-
tion plasters are not suitable.
Surface smoothness +/- 3 mm per 1m. Observe building regulation requirements con-
cerning thermal insulation. Moisture condensation can occur and should be taken into
consideration when planning wall heating on outer walls and walls between heated and
unheated rooms.
Wall coverings Heating plasters
Cement-lime plaster e.g. Stud: MP75 G/F, MP75 G: Thermal conductivity: 0.58 W/mk;
single layer processing; max. VL temperature: 50°C; heating according to report possible
after 3rd day.
Loam rendering e.g. Claytec: Final coat (05.010 / 05.012 / 10.012); Thermal conductivity:
0.65 W/mK; single layer processing; max. VL temperature: 50°C; heating possible im-
mediately.
Chalk-cement plaster e.g. MARMORIT ROTKALK; biorit 110: Thermal conductivity: 0.87
W/mK; two-layer processing; max. VL temperature: 65 - 70°C; heating according to
report possible after 8 days.
Construction Refering to EN 1264
Construction number 613
VAEUL102 © Danfoss 06/2010