Wet Plaster
1 Wall heating dowel, 3-part, 70 mm
2 Danfoss wall heating metalgrid
3 SpeedUp panel, 30 mm
4 Danfoss composite pipe 16 x 2 mm
5 Heating plaster over SpeedUp, 15 mm
Technical Data
Wall heating with wet plastering
Wall covering 15 mm Heating plasters; single layer plastering, edge
insulation strips required
Construction thickness 45 mm Dimensions without unfinished wall
Thermal resistance (R) 0.86 m²K/W Thermal resistance value for SpeedUp panel
Pipe spacing 125-250 mm EZ = 125; CZ = 250;
Requirements
and specialities
Heating plasters must show a good thermal conductivity. Light plasters and heat
insulation plasters are not suitable. Surface smoothness +/- 3 mm per 1 m.
Observe building regulation requirements concerning thermal insulation.
Moisture condensation can occur and should be taken into consideration when
planning wall heating on outer walls or walls between heated and unheated
rooms.
Wall coverings Heating plasters:
Cement-lime plaster e.g. Stud: MP75 G/F, MP75 G: Thermal conductivity: 0.58 W/
mk; single layer processing; max. VL temperature: 50°C; heating according to
report possible after 3rd day.
Loam rendering e.g. Claytec: Final coat (05.010 / 05.012 / 10.012); Thermal
conductivity: 0.65 W/mK; single layer processing; max. VL temperature: 50°C;
heating possible immediately.
Chalk-cement plaster e.g. MARMORIT ROTKALK; biorit 110: Thermal conductivity:
0.87 W/mK; two-layer processing; max. VL temperature: 65 - 70°C; heating
according to report possible after 8 days.
Construction Referring to EN 1264.
Construction number 603
Application Sheet
SpeedUp Wall Heating - Wet Plaster