Wet Plaster
1 Wall heating dowel, 3-part, 70 mm
2 Danfoss wall heating metalgrid
3 BasicRail
4 Danfoss composite pipe 16 x 2 mm
5 Heating plaster, 35 mm
Technical Data
Wall heating with wet plastering
Wall covering 35 mm 15 mm heating plaster over composite pipe
Construction thickness 35 mm Dimensions without unfinished wall
Thermal resistance (R) - m²K/W This wall heating construction does not include
any insulation
Pipe spacing 120-200 mm EZ 2 = 120; EZ 3 = 150; CZ 1 = 200;
Requirements
and specialities
Heating plasters must show a good thermal conductivity. Light plasters and heat
insulation plasters are not suitable. Observe building regulation requirements
concerning thermal insulation. Moisture condensation can occur and should be
taken into consideration when planning wall heating on outer walls and walls
between heated and unheated rooms.
Wall coverings Heating plasters:
Cement-lime plaster e.g. Stud: MP75 G/F, MP75 G: Thermal conductivity: 0.58 W/
mk; single layer processing; max. VL temperature: 50°C; heating according to
report possible after 3rd day.
Loam rendering e.g. Claytec: Final coat (05.010 / 05.012 / 10.012); Thermal
conductivity: 0.65 W/mK; single layer processing; max. VL temperature: 50°C;
heating possible immediately.
Chalk-cement plaster e.g. MARMORIT ROTKALK; biorit 110: Thermal conductivity:
0.87 W/mK; two-layer processing; max. VL Temperature: 65 - 70°C; Heating
according to report possible after 8 days.
Construction Referring to EN 1264.
Construction number 621
Application Sheet
BasicRail Wall Heating - Wet Plaster
Danfoss Heating Solutions VAGHA202 © Danfoss 03/2011 1