Fläkt Woods 3235 GB 03.01 1 Specifications are subject to alteration without notice
EU Air Handling Unit INSTALLATION
Telpher EULZ-29, size 51–84
Dismantle the panel and pillar over the door for
sizes 71–84.
Slide the telpher EULZ-29 onto the telpher beam
EULZ-25.
Assemble the extension beam with a nut and
bolt .
Secure the telescopic upright to the extension
beam with a screwed joint .
Adjust the height of the supporting uprights with a scre-
wed joint .
Check that the telpher runs freely along the entire telpher
beam. Fit the telpher with a tackle dimensioned for the
counterweight. Undo the motor and lift it. In certain cases
the telpher cannot be aligned directly above the motor.
Place a pallet between the unit and the supporting upright
for transport of the motor.
Dismantling and reassembly take place in the reverse
order.
Max. load 1000 kg.
7
11
59
4
12
8
10
1 2
3
4
56
789
10 11
4
3
6
EU 51, 53
EU 60–84
Existing telpher beam EULZ-25
EULZ-29
EU 71–84
/