Copyright HK Instruments 2022 www.hkinstruments. Installaon version 2.0 2022
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-CR-MOD Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
ThankyouforchoosinganHKInstrumentsDPT-CR-MODseriesdif-
ferenalpressuretransmier.DPT-CR-MODseriesisdesignedspe-
ciallyforcleanroommonitoring.Inaddiontodierenalpressure,
thedeviceenablesmonitoringtemperatureandrelavehumidity.
A 0…10 V voltage input of an external humidity and temperature
transmiercanbeconnectedtotheinputterminalofthedevice.In
thiscase,all three measuredvalues(dierenalpressure,relave
humidity,temperature)willbeshownsimultaneouslyonthedisplay.
Alternavely,apassivetemperaturesensorcanbeconnectedtothe
inputterminal.
DPT-CR-MOD is compable with Modbus serial communicaon
protocol.
DPT-CR-MODseriesdevicesarecommonlyusedinHVAC/R
systems for:
•pressure,temperatureandhumiditymonitoringincleanrooms
SPECIFICATIONS
Performance
Measurement range:
-250...2500Pa
Accuracy (from applied pressure):
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
(Including:generalaccuracy,linearity,
hysteresis,longtermstabilityandrepeonerror)
Input accuracy:
Temperature:±0.25°Ctypical@25°C+accuracyof
externaltransmier
Humidity:±0.5%rHtypical@25°C+accuracyof
externaltransmier
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
ManualpushbuonorviaModbus
Response me:
1...20sselectableviamenu
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
CodingSystem:8-bitbinary
BitsperByte:
1 start bit
8databits,leastsignicantbitsent
rst
1bitforparity
1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Selectableviamenu
(Pa,kPa,mbar,inchWC,mmWC,psi)
Measuring element:
MEMS,noow-through
Environment:
Operangtemperature:-20...50°C
Temperaturecompensatedrange0...50°C
Storagetemperature:-40...70°C
Humidity:0to95%rH,non-condensing
Physical
Dimensions:
Case:102x71.5x36mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case: ABS
Lid:PC
Pressure inlets: Brass
Protecon standard:
IP54
Display:
2-linedisplay(12characters/line)
Line1:pressuremeasurement
Line2:relavehumidityandtemperature(ifexternal
measurementsareconnected)
Electrical Connecons:
4+4springloadterminals,max1.5mm2
Cableentry:M20
Pressure ngs:
Maleø5.2mm
+Highpressure
-Lowpressure
Electrical
Supply voltage:
24VACorVDC±10%
Power consumpon:
<1.3W
Output signal:
viaModbus
Input signals:
Temperatureinput:0−10VorNTC10k,Pt1000,
Ni1000/(-LG)
RHinput:0−10V
Conformance
Meetsrequirementsfor:
CE: UKCA:
EMC: 2014/30/EU S.I.2016/1091
RoHS: 2011/65/EU S.I.2012/3032
WEEE: 2012/19/EU S.I.2013/3113
INTRODUCTION
APPLICATIONS
WARNING
RoHS