HK Instruments RHT Installation guide

Type
Installation guide
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
INSTALLATION
INSTRUCTIONS
HUMIDITY TRANSMITTERS
RHT Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstrucons
canresultinPERSONALINJURY,DEATHAND/ORPROPERTY
DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystem
whosespecicaonsandperformancecharacteriscsarenot
designedorcontrolledbyHKInstruments.Reviewapplicaons
andnaonalandlocalcodestoassurethattheinstallaonwill
befunconalandsafe.Useonlyexperiencedandknowledgeable
technicianstoinstallthisdevice.
•Fuseatloadsupply(normally6A,10A,16A)doesnotalwayslimit
 therelayoutputloadcurrentto6A.RelayMaximumLoad(250Vx
6Ares.)
•Addanexternalfusetorelaycommonconnector.Useame-lag
 fuse(max6A)thatisinaccordancewiththestandardIEC60127-2.
 Theproductdoesn’thaveaninternalfusefortherelay.
 CAUTION:Theproductmayonlybeconnectedtoovervoltage
 categoryIIelectricitynetworkaccordingtoIEC60664-1
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsRHTseriesrelavehu-
miditytransmier.TheRHTseriesisintendedforuseincommercial
environmentsinHVAC/Rapplicaons.
TheRHTseriesmeasuresrelavehumidity(rH)andtemperature(T).
Eachmeasurementparameter(rH,T)hasaseparateeldcongur-
ableoutput.
The RHT series relave humidity transmiers are available with
Modbusconguraon,relayandtouchscreendisplay.
RHTseriesdevicesarecommonlyusedtomonitor:
•humidityandtemperaturelevelsinoces,publicspaces,hospitals,
meengroomsandclassrooms
•humidityandtemperatureinvariouscommercialapplicaons
•humidityandtemperatureinHVAC/Renvironment
SPECIFICATIONS
Performance
Measurement ranges:
Temperature:0...50°C
Relavehumidity:0100%
Accuracy:
Temperature:<0.5ºC
Relavehumidity:±2...3%at0...50°Cand10–90%rH
Totalerrorbandincludesaccuracy,hysteresisand
temperatureeectover5...50°Cand10–90%rH.
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
°Cand%rH
Measuring element:
Temperature:Integrated
Relavehumidity: Thermosetpolymercapacive
sensingelement
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:99x90x32mm
Weight:
150g
Mounng:
3screwholessloed,3.8mm
Materials:
Case: ABS
Protecon standard:
IP20
Display (Oponal)
Touchscreen
Size:77.4x52.4mm
Electrical connecons:
Powersupply:
 5-screwterminalblock
 (24V,GND,rH,T,Maxvalue)
 0.2–1.5mm2(16–24AWG)
Relay out:
 3-screwterminalblock
 (NC,COM,NO)
 0.2–1.5mm2(16–24AWG)
Electrical
Input: 24VACorVDC,±10%
Currentconsumpon:max90mA(at24V)+ 
 10mAforeachvoltageoutputor20mAforeach
 currentoutput
Outputsignal(rH,temperature):
 0–10V,R>1kΩ
 210V,R>1kΩ(oponalvoltageoutput,displayrequired)
 4–20mA,R<500Ω
Relay out:
 SPDTRelay,250VAC/30VDC/6A
 Adjustableswitchingpointandhysteresis
Conformance
Meetsrequirementsfor:
CE:  UKCA:
EMC:  2014/30/EU S.I.2016/1091
RoHS:  2011/65/EU S.I.2012/3032
LVD/EESR: 2014/35/EU S.I.2016/1101
WEEE:  2012/19/EU S.I.2013/3113
INTRODUCTION WARNING
APPLICATIONS
RoHS
COMPLIANT
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Routethecablesandconnectthewires(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
Figure 1a - Surface mounng
Display locking
jumper
Jumpers
Contact pins for
relay terminal
Contact pins for
terminal block
Terminal block
Terminal block for relay
99.0
90.0
83.0
49.5
14.0
45.0
18.0
Ø 4.0
32.0
YES NO NO
Figure 1b - Mounng orientaon
1)Selectamounnglocaononthewallat1.21.8m(4–6)above
theoorandatleast50cm(20in)fromtheadjacentwall.Do
notblockdeviceairventsfromanydireconandleaveatleast
20cm(8in)gaptootherdevices.Locatetheunitinanareawith
goodvenlaonandanaveragetemperature,whereitwillbe
responsivetochangestotheroomcondions.TheRHTshouldbe
mountedonaatsurface.
DonotlocatetheRHTwhereitcanbeaectedby:
•Directsunlight
•Drasordeadareasbehinddoors
•Radiantheatfromappliances
•Concealedpipesorchimneys
•Outsidewallsorunheated/uncooledareas
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountthewallplatewithscrews.
•Incorrectinstallaonmaycauseashiintemperatureoutput
•Securethelidwithalockingscrew,iftherelayisconnectedtothe
mainspower.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
CAUTION!
•ForCEcompliance,aproperlygroundedshieldingcableis
required.
•Usecopperwireonly.Insulateorwirenutallunusedleads.
•Supplyaseparatecableforrelayandsignaloutwhenusingline
voltagetopowertherelay.
•Anywiringmaycarrythefulloperanglinevoltagecurrentbased
oneldinstallaon.Thecoverlockingscrewmustbeinstalledif
thelinevoltageissuppliedtotherelay.
•Careshouldbeusedtoavoidelectrostacdischargetothedevice.
•Thisunithasconguraonjumpers.Youmayneedtorecongure
thisdeviceforyourapplicaon.
1)Routethecablesthroughthesquareopeninginthebackplateor
forsurfacewiringselectaknockoutonthetoporboomofthe
wallplate,asshowninFigure2a.
2)ConnectthewiresasshowninFigure2band2c.
STEP 3: CONFIGURATION
WIRING DIAGRAMS CONTINUED
ConguraonoftheRHTseriesdeviceconsistsof:
1)Conguringthejumpers(seestep4).
2)Conguraonmenuopons.(Display-andModbusversions
only.Seetheusermanualforfurtherdetails.)
Figure 2a - Roung the cables
24 V
GND
Max
rH
Temp
+
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Figure 2b - Wiring diagram: Power input & signal output
Wires can be routed through the square opening in the back plate
Wires can be routed through the top knockouts
Wires can be routed through the boom knockouts
NC
COM
NO
STEP 2: WIRING DIAGRAMS
Figure 2d - Wiring diagram: Relay
24 V
GND
Max
rH
+
Temp
V V V
Output 0/2...10 V
Output 0/2...10 V
Output 0/2...10 V
Figure 2c - Wiring diagram: Extra GND wire
NOTE!Whenusinglongconneconwiresitmaybenecessaryto
useaseparateGNDwireforvoltageoutputcurrenttoprevent
measurementdistoron.TheneedforanextraGNDwiredepends
onthecrossseconandlengthoftheusedconneconwires.Iflong
and/orsmallcrossseconwiresareused,supplycurrentandwire
resistancemaygenerateavoltagedropinthecommonGNDwire
resulnginadistortedoutputmeasurement.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
1)Conguraonoftheoutputmodesof:
•Maxvalue
•Relavehumidity(rH)
•Temperature(Temp)
Selecttheoutputmode,current(4–20mA)orvoltage(0–10V),
byinstallingjumpersasshowninFigure4.Eachoutputarecongured
separately.
Toselect210Voutputmodeonadisplayversiondevice:
First,select010Voutputbyjumper(s),thenchangethevoltage(V)
outputfrom0–10Vto210Vviatheconguraonmenu.Please
seetheusermanualformoredetails.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsoraproduconawisfound,thesellerisobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
and installaon worknotdonebytheseller. The seleconofmateri-
alsfordevicespronetocorrosionisthebuyer’sresponsibility,unless
otherwise is legally agreed upon. Should the manufacturer alter the
structureofthedevice,thesellerisnotobligatedtomakecomparable
changestodevicesalreadypurchased.Appealingforwarrantyrequires
thatthebuyerhascorrectlyfullledhis/herduesarisenfromthede-
liveryandstatedinthecontract.Thesellerwillgiveanewwarrantyfor
goodsthathavebeenreplacedorrepairedwithinthewarranty,how-
everonlytotheexpiraonoftheoriginalproduct’swarrantyme.The
warrantyincludestherepairofadefecvepartordevice,orifneeded,
anewpartordevice,butnotinstallaonorexchangecosts.Underno
circumstanceisthesellerliablefordamagescompensaonforindirect
damage.
2)Lockingthedisplay:
Installthejumpertolockthedisplaytopreventaccesstothecongu-
raonmenuaerinstallaoniscompleted(seetheschemacsforthe
locaonofthepins).
Jumper installed to the le side pins:
0–10 V output selected
Max value
rH
Temp
0–10 V 4–20 mA
Jumper installed to the right side pins:
4–20 mA output selected
Max value
rH
Temp
0–10 V 4–20 mA
First jumper installed to the le side pins:
0-10 V output selected for Max value
Second jumper installed to the right side pins:
4–20 mA output selected for rH
Third jumper installed to the le side pins
0–10 V output selected for temperature
Max value
rH
Temp
0–10 V 4–20 mA
Figure 4
STEP 4: Jumper settings
WARRANTY POLICY
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
(Grey colour indicates that a jumper is installed)
No jumper
Circuit open
Jumper installed
Circuit closed
Jumper stored
Figure 3 - Jumper installaon
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4