EUQA Humidifier, for once-through water, b = 1, 2, c = 2
Fläkt Woods 3236 GB 05.08 1 Specifications are subject to alteration without notice
EU Air handling unit INSTALLATION
To connect the humidifier to the water system
The water supply is regulated by a pulse valve and a con-
stant flow valve, Item 12.
Connect the supply pipe (1) to the inlet branch (Table 1).
Fit a shut-off valve (2) and water filter (10) in the water
supply pipe.
Table 1. Connection dimensions
1. Water supply pipe
2. Shut-off valve (not included)
3. EUAZ-08 water trap (accessory)
4. Drain pipe
5. Humidifier fill
6. Droplet eliminator
7. Spray pipe
8. End plug
9. Side wall
10. Water filter, max. 500 µm mesh (not included)
11. Flushing hose
12. Pulse valve and constant flow valve
9
8
7
9
5
6
2
10
11
121
3
4
Fig. 1
Ordering key
Humidifier, evaporative EUQA-aa-b-2-d-1
Size (aa)
11, 20, 21, 22, 30, 31, 32, 33,
40, 41, 42, 44, 50, 51, 52, 53,
60, 62, 64, 71, 73, 80, 82, 84
Degree of humidification (b)
1 = 90%
2 = 60%
Version (c)
2 = once-through water
Inspection side (d)
1 = right-hand, 2 = left-hand
Pre-commissioning adjustments
Check:
A. that the droplet eliminator fills are correctly fitted for the
direction of air flow, see the arrow.
B. that there are no water leaks at any of the couplings and
connections.
C. that water is being discharged from all holes in the spray
pipe or pipes. If any holes are clogged, use a needle to un-
clog them. If the spray pipe(s) is/are extremely clogged,
remove the end plugs (8), brush inside them using a
round brush and then flush them clean.
D. That the pulsing function operates open for ca. 150 sec.
And closed for ca. 100 sec.
Table 2, Supply water flow, l/min
Drain pipe should be fitted with a cleanable water trap
(3) (EUAZ-08) and should be run, without reduction in
diameter, to a floor gulley.
The shut-off valve, water trap and water filter are not
included in the EUQA.
aa 20–42
50, 51, 60
aa 44, 53
62–84
Size 90% 60%
11 5,0 2,5
20 5,0 2,5
21 8,0 4,0
22 9,0 4,5
30 8,0 4,0
31 9,0 4,5
32 12 6,0
33 13 6,5
40 9,0 5,0
41 12 6,0
42 13 7,0
44 20 10
Supply water flow, l/min
Size 90% 60%
50 13 6,5
51 14 7,0
52 17 8,5
53 20 10
60 14 7,0
62 20 10
64 26 13
71 20 10
73 26 13
80 20 10
82 26 13
84 28 14
Supply water flow, l/min
Connection data – pulse valves
Size Number of
valves Data
11-62, 71, 80
64, 73, 82, 84
Connection data 100-230V
Current 0,5 A
Frequency 50-60 Hz
Protection class IP 65
Output 8 watt
Function Normaly closed
2
1
Connection size/diameter
Size 60%, b = 2 Inlet
11–42
50, 51, 60
44, 52, 53, 62–84
90%, b = 1 Outlet
11–42
50, 51, 60
44, 52, 53, 62–84