FläktGroup EQAZ-08 water trap Installation and Maintenance Manual

Type
Installation and Maintenance Manual
EQAZ-08-01
WATER TRAP DESIGNED FOR PRESSURE BELOW
ATMOSPHERIC
EQAZ-08-02
WATER TRAP DESIGNED FOR PRESSURE ABOVE
ATMOSPHERIC
NOTE!
EUAZ-08 Not designed for pressure above
atmospheric. EQAZ-08-01 Not designed for
pressure above atmospheric. EQAZ-08-02
Not designed for pressure under atmos-
pheric.
Under pressure
Pa
Cut to size
(L)
Height
(H)
< 600 50 mm 40 mm
600-1000 70 mm 60 mm
1000-1400 110 mm 100 mm
1400-1800 150 mm 140 mm
1800-2200 190 mm 180 mm
2200-2600 200 mm 220 mm
Pa
H
L
WATER TRAP
EUAZ-08, EQAZ-08-01, EQAZ-08-02
INSTALLATION AND MAINTENANCE
FläktGroup DC_8644GB 20180122_R0 We reserve the right to make changes without prior notice
Installation and maintenance instruction
FläktGroup DC_8644GB 20180122_R0 We reserve the right to make changes without prior notice
2
CLEANING THE WATER TRAP
The water trap must be unscrewed and re-assembled by hand.
Check that the pipes/hoses are not blocked and cleanany dirt
and deposits from the water trap.
MAINTENANCE INTERVAL
6 months. Check and clean the water trap.
N.B.
The water trap and discharge pipe must not
be subjected to temperatures below freezing.
If the unit is installed outdoors, the drain pipe,
water trap and discharge pipe should be
insulated.
The water trap should not be exposed to
direct sunlight.
0°
°C