FläktGroup LQQA Humidifier for once-through water Installation guide

Type
Installation guide
FläktGroup DC_9210GB 20180413_R0 Specifications are subject to alteration without notice
MAINTENANCE
LQQA HUMIDIFIER,
FOR ONCE-THROUGH WATER,
B = 1, 2, C = 2
Fig. 1
aa 62–84
aa 60
1. Water supply pipe
2. Shut-off valve (not included)
3. LQAZ-08 water trap (accessory)
4. Drain pipe
5. Humidifier fill
6. Droplet eliminator
7. Spray pipe
8. End plug
9. Side wall
10. Water filter, max. 500 mm mesh (not included)
11. Hose connection for cleaning by flushing
12. Pulse valve and constant flow valve
MAINTENANCE ADJUSTMENTS
Check:
A. that the humidifier fill and the droplet eliminator are correctly fitted
for the direction of air flow. See the arrows.
B. that there are no water leaks at any of the couplings and
connections.
C. that water is being discharged from all holes in the spray pipe or
pipes. If any holes are clogged, use a needle to unclog them. If the
spray pipe(s) is/are extremely clogged, remove the end plugs, item
8, and clean inside the spray pipes using a round brush and then
flush them clean.
The water flow with the pulse valve open is:
600 mm broad fill 90%, 8 l/minute.
600 mm broad fill 60%, 4 l/minute.
Water consumption as shown in the table1. If the water flow is
incorrect, the constant-flow valve may be clogged. See ”Clean the
constant-flow valve” (12) on page 2.
Table 1. Water consumption, l/min
SPECIAL CONDITIONS
Drain and clean the water tray whenever the system is shut down
for an extended period, such as during the annual holiday and long
weekends.
If the humidifier is to be out of service for some time, the humidifier fills
should be removed, cleaned and stored in a place where they will not
sustain damage.
Size 90% 60%
60 14 7,0
62 20 10
64 26 13
71 20 10
73 20 10
73 26 13
80 20 10
82 26 13
84 28 14
1
11
10
9
8
7
6
5
4
3
2
9
12
2
Maintenance
FläktGroup DC_9210GB 20180413_R0 Specifications are subject to alteration without notice
CLEANING THE HUMIDIFIER FILLS AND DROPLET ELIMINATOR
A. Shut off the water supply.
B. Open the inspection door.
C. Withdraw the droplet eliminator and the humidifier fills straight out
of the humidifier as shown in Fig. 2.
Important!
The internal fills can be reached by carefully stepping inside on the
edge of the basin. Do not step on the guides or the bottom of the
basin.
D. The fills are relatively delicate and should accordingly be handled
with great care. Clean by spraying with a jet of clean water, possibly
containing a cleaning agent such as LQROKRAFT L (Elektrolux).
E. Refit the components in the reverse order.
F. Check the position of the side walls and close the inspection door.
When replacing humidifier blocks, separate instructions are supplied
for the new blocks.
CLEANING THE CONSTANT-FLOW VALVE
A. Remove the valve
B. Check that the rubber membrane is free from contamination. If
necessary, clean carefully.
C. Refit the valve and check the water flow.
Fig. 3
EUQAS 7
Constant flow valve,
internally positioned
Fig. 2
3
Maintenance
FläktGroup DC_9210GB 20180413_R0 Specifications are subject to alteration without notice
MAINTENANCE INTERVAL
Apparatus part Procedure Interval
months
Casing (basin, end wall, ceiling, guides) Empty the basin. Clean internally by washing, wiping or, if necessary, brushing. 3
Humidifier fills
Droplet eliminator Clean by washing with water, possibly containing a cleaning agent such as LQROKRAFT L (Elektrolux). 3
Water filter Clean or replace the filter cartridge, if required. (Porosity max. 500 μm.) 3
Constant flow valve Check that no contamination is present on the rubber membrane; if so, clean with care. 3
Water flow Clean the sprinkler tubes, if necessary. 3
Water trap Cleaning and charging. 6
Water quality The pH-value of the water should not be less than 5 or greater than 8.5. Water of drinking quality is