FläktGroup DC_9210GB 20180413_R0 Specifications are subject to alteration without notice
MAINTENANCE
LQQA HUMIDIFIER,
FOR ONCE-THROUGH WATER,
B = 1, 2, C = 2
Fig. 1
aa 62–84
aa 60
1. Water supply pipe
2. Shut-off valve (not included)
3. LQAZ-08 water trap (accessory)
4. Drain pipe
5. Humidifier fill
6. Droplet eliminator
7. Spray pipe
8. End plug
9. Side wall
10. Water filter, max. 500 mm mesh (not included)
11. Hose connection for cleaning by flushing
12. Pulse valve and constant flow valve
MAINTENANCE ADJUSTMENTS
Check:
A. that the humidifier fill and the droplet eliminator are correctly fitted
for the direction of air flow. See the arrows.
B. that there are no water leaks at any of the couplings and
connections.
C. that water is being discharged from all holes in the spray pipe or
pipes. If any holes are clogged, use a needle to unclog them. If the
spray pipe(s) is/are extremely clogged, remove the end plugs, item
8, and clean inside the spray pipes using a round brush and then
flush them clean.
The water flow with the pulse valve open is:
600 mm broad fill 90%, 8 l/minute.
600 mm broad fill 60%, 4 l/minute.
Water consumption as shown in the table1. If the water flow is
incorrect, the constant-flow valve may be clogged. See ”Clean the
constant-flow valve” (12) on page 2.
Table 1. Water consumption, l/min
SPECIAL CONDITIONS
Drain and clean the water tray whenever the system is shut down
for an extended period, such as during the annual holiday and long
weekends.
If the humidifier is to be out of service for some time, the humidifier fills
should be removed, cleaned and stored in a place where they will not
sustain damage.
Size 90% 60%
60 14 7,0
62 20 10
64 26 13
71 20 10
73 20 10
73 26 13
80 20 10
82 26 13
84 28 14
1
11
10
9
8
7
6
5
4
3
2
9
12