Focal Point Covert Lite FCOLT Installation guide

  • Hello! I've reviewed the provided instructions for the Covert Lite FCOLT luminaire. This document covers installation, electrical connections, and clearance requirements. It includes instructions on securing housing to a cove, spacing and joining housings and making electrical connections. I'm ready to assist you with any questions you have about this product.
  • What is the recommended clearance above the cove?
    Who is responsible for reinforcing walls and/or ceilings?
    What is the maximum spacing for housings?
Contractor is responsible for adequately reinforcing walls and/or ceilings to support luminaire weight. Focal Point, LLC accepts no responsibility for inadequately reinforced walls
and/or ceilings. The information contained in this drawing is the sole property of Focal Point, LLC. Any reproduction in part or whole without the written permission of Focal Point, LLC
is prohibited.
IS0671 REV. B 2018 ©Focal Point, LLC 4141 S. Pulaski Rd., Chicago, IL 60632 | www.focalpointlights.com 1 of 2
Covert Lite®
FCOLT
2
1
key
Luminaires must be installed by a qualified electrician (check with local and national codes for proper installation).
To prevent electrical shock, disconnect electrical supply before installation or servicing.
power off
power on
attention
3
optional - secure housing to cove
HARDWARE BY OTHERS
4.12"
104.6mm
2.02"
51.3mm 1.72"
43.7mm
8” CLEARANCE ABOVE
COVE RECOMMENDED
FOR ALL APPLICATIONS
focal point
4
5b
optional - join housings
5a
optional - space housings
1” SPACING MAX
END CAP
individual installations skip to step 7
6
LENS LENGTH EXCEEDS
HOUSING LENGTH
Contractor is responsible for adequately reinforcing walls and/or ceilings to support luminaire weight. Focal Point, LLC accepts no responsibility for inadequately reinforced walls
and/or ceilings. The information contained in this drawing is the sole property of Focal Point, LLC. Any reproduction in part or whole without the written permission of Focal Point, LLC
is prohibited.
IS0671 REV. B 2018 ©Focal Point, LLC 4141 S. Pulaski Rd., Chicago, IL 60632 | www.focalpointlights.com 2 of 2
Q
7 8a
make electrical connections
INSIDE CORNERS
1
8b
make electrical connections
X2
DRIVER SERVICE
1
HOUSING CORNERS
SHOULD TOUCH
ELECTRICAL / EC FEED (MIDDLE OF RUN)
1 2 3
IF COVE IS 5.12” WIDE OR LESS
END FEED IS REQUIRED
make electrical connections
1” SPACING MAX
90° CONDUIT ELBOW
(BY OTHERS)
END FEED FRONT FEED
/