Trend IQ4NC/12 Installation Instructions Manual

Type
Installation Instructions Manual

This manual is also suitable for

IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 1
InstallationInstructions-Conguring
IQ422, IQ4NC/00, IQ4NC/12
Controllers
Important: Retain these instructions
These instructions shall be used by trained service
personnel only.
If the equipment is used in a manner not
speciedbytheseinstructions,theprotectionprovidedbythe
equipmentmaybeimpaired.
https://partners.trendcontrols.com
1
Isolate All Power (includinganyI/Osupplies)
1 BEFORE STARTING CONFIGURATION
CONTENTS
1 BeforeStartingConguration.......................................1
2 Conguration.................................................................1
3 Connect to IQ4xx........................................................10
4 Reset to Defaults.........................................................12
2 CONFIGURATION
Read&AgreetoEndUserLicenceAgreement
Additional Documentation Required
SETManual(TE200147)
IPToolManual(TE200638)
IQToolMonitorAppletManual(TE201298)
IQToolAddresserAppletManual(TE201299)
IQ4CongurationManual(TE201263)
Note: PDF copies are included with SET installation in the
following folder: C:\...\Trend Control Systems\Documentation
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions-Mounting(TG201264)
SETManual(TE200147)
Prepare Ethernet Network (ifusingEthernet)
Install DHCP Server
IftheIPaddresssettings(IPaddress,subnetmask,default
router,WINSandDNSservers’addresses)aretobesupplied
by a DHCP server, ensure one is installed onthe Ethernet
segment to which the IQ422, IQ4NC/00, IQ4NC/12 is
connected.
Install WINS Server
If host names are being used for IP addressing across a
router,aWINSservermustbeinstalled.
Install DNS Server
Ifemailalarmsarebeingsent,andtheemailserveraddress
isidentiedbyinternetdomainname,aDNSservermustbe
installed.
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions-Mounting(TG201264)
PSU
PSU
O
I
O
I
O
I
Install the IQ422, IQ4NC/00, IQ4NC/12 InstallSETonPC/Laptop
WARNING Connecting leads may be connected
topowersupplies.Isolatebeforetouching.
2 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
6
Select Terminator Switch Position (IQ4NCusingMS/TPnetworkonly)
3
PeelOTopSerialLabel&Retain
5
Disconnect All I/O
4
OpenRotatingCovers
2
Open Panel / Enclosure
2 CONFIGURATION (continued)
Serial
Number
nq4eyecp412345
Q422B_V53440388
O/S
Q422B_V53440388
nq4eyecp412345
00:10:70:0D:1E:92
MAC Addr
IQ411-1010U5000
Part No:
LAN
422
MAC
Addr
IP
Addr
LAN
Location
S/No:
MAC Addr
00.10.70.00.UD.BB
S/No:
Q3B____X73010003
IP Addr
Location
TerminatoroutofcircuitTerminatorincircuit
IQ422, IQ4NC/00, IQ4NC/12 Installation
Instructions - Mounting (TG201264) for
detailsofterminatoruse.
Leave Power, Ethernet, Current loop LAN, USB, RS232,
andMS/TPconnected(whereappropriate).
WARNING Opening the panel may expose
dangerousvoltages.
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 3
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
8
CloseRotatingCovers
10
CheckPower&WatchdogIndicators
9
Switch On Power to IQ4xx
7
ConnectPC/Laptop
11
Check Ethernet Indicators (ifEthernetisconnected)
2 CONFIGURATION (continued)
O
I
Either:viaEthernetHub/Switch Or:usingdirectconnection
Note: To connect with SET a vCNC is required (see step 14).
SETcanconnectwhenonadierentsubnet.
Note:Othermethodsofconnectionareavailablesee‘Connect
to IQ4xx’ on page 10.
Normal operation indication
Power
Watchdog
Fault indications
Power
Checkinputpowersupply
Watchdog
Devicefault.TryresettingtheIQ4xx
todefaultsettings(seepage12).
10s
Normal operation indication
OK
RX
or
Fault indications
OK
CheckEthernet
RJ45
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
RJ45
Hub/Switch
Router
Note: All LEDs illuminate for several seconds after switch on.
Watchdog
(red)
Power
(green)
OK
(green)
RX
(yellow)
4 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
12
Connect to the IQ4xx
13
SetupIPAddressingDetails(ifusingEthernet)
2 CONFIGURATION (continued)
nq4eyecp412345
Q422B_V53440388
O/S
00:10:70:0D:1E:92
MAC Addr
IQ422-1010U5000
Part No:
LAN
IP
Addr
422
Then nd the IQ4NC, IQ422by its MAC
addressasshownonseriallabel
SETManual(TE200147)
IPToolManual(TE200638)
UseIPTool–seestep12–tochooseeitherstatic(xed)or
dynamic(DHCP)addressing:
Dynamic(DHCP)Addressing(default)
Parameter Value
DeviceMode
Static(Fixed)Addressing
Parameter Value
DeviceMode
IPAddress
Enterrequiredvalueinformat:
xxx.xxx.xxx.xxx
SubnetMask
Default Router
WINSServer
Whensettodynamic(DHCP)addressingtheunitautomatical
obtains its IP addressing details (IP address, subnet mask,
default router, WINS server and DNS server) from the
network’s DHCP (Dynamic Host Conguration Protocol)
server. If no DHCPserver isfound, theunitdefaults to link/
localmodewhereitautonegotiatesitsIPaddresswithother
devicesonitsEthernetsegment,
Note: It is recommended that link/local only be used on a
single segment system.
When set to static (xed) addresssing the IP addressing
detailsmustbeconguredmanually.
Note: If email alarms are being sent, and the email server
address is identied by internet domain name, then a DNS
servermustalsobespeciedusingTextComms.
IPToolManual(TE200638)
UsingthePC/laptop(seestep7)runSET/IPTool
14
Set up Virtual CNCs (ifrequired)
Bydefault,IQ4NCshave4enabledvCNCs(4,5,6,and7)and
IQ422s have 3 disabled vCNCs. A vCNC must be enabled
if connection to a supervisor, tool or display is required. If
necessarydisable/congurethemtoavoidaddressconicts.
Use IP Tool – seestep12– to set up theaddressandport
numberofeachvCNC.
Parameter Range
Address
0(disabled),1,4to9,11to119
PortNumber
1to32767
Default = 10000 plus the address
(e.g.address23setsportto10023)
OncethevCNCsetupinIPTooliscomplete,useIQSETto
congurethevCNCs.
UsingIQSETconnecttooneofthecontrollersvCNCs.
Youwillbe promptedtopresstheservicebutton on the
controller.OncepressedtheSecureSiteConguration
dialogueboxisdisplayed.
Congure the vCNCs as required, and enter the
credentialsfortheCNCUsermodule.
Note: conguring the vCNCs require physical access to
the controller ensure this is done before leaving site.
SETManual(TE200147)
IPToolManual(TE200638)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-20185
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
15
Set up IQ4NC Communication Mode (ifusingIQ4NC)
16
CheckTrendCurrentLoopNetworkIndicators(ifcurrentloopnetworkbeingused)
17
Check MS/TP Network Indicators (IfIQ4NCusingMS/TPnetwork)
ConnectaPCdirectlytotheIQ4usinganEthernetcable,
see‘ConnecttoIQ4’onpage10.
Usinga web browser, e.g. Internet Explorer, access the
controllerswebpagesandselectModules>Networks to
displaytheNCCongurationWizard.
Click required mode, and if necessary specify any
parameterse.g.LANnumber.
Click
;thecontrollerwillrestart.
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
BACnet
MSTP
Can be enabled e.g. for
connectionofPEHAdevices
Internetwork
Note:Addressnolongerneedstobe>100.
Parameter Notes
LANnumber
1,4to9,11to119
BACnetIP
Canbedisabled
BACnet
MSTP
Can be enabled e.g. for
connectionofPEHAdevices.
InternetworkplusMS/TPLan
2 CONFIGURATION (continued)
IQ4WebUserGuide(TC201256).
Note: The IQ4NC always has a LAN to connect to the
internetwork so cannot join another LAN on the internetwork.
Normal operation indication
TX
RX
Fault indications
TX
Checkconnectiontodownstreamdevice
RX
Checkconnectiontoupstreamdevice
Normal operation indication
RX
TX
Fault indications
RX
Signal not reaching RX on downstream
deviceonnetwork–checkdevice/wiring
TX
No TX signal from upstream device on
network–checkdevice/wiring
TX
(yellow)
RX
(yellow)
TX
(yellow)
RX
(yellow)
6 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
19
SetupTrendAddressing
18
Set up Ethernet Access Across Routers (ifrequired)
20
WriteAddressDetailsonLabel
2 CONFIGURATION (continued)
IftheLANistobebuiltacrossarouter(s)detailsofdevices
(on each subnet) must be specied to enable cross-router
communications.
UseIPTool–seestep12–tospecifyIPsettingsforupto20
devicesintheRemoteTrendDeviceslist:
Parameter
Value
IPAddress
If using dynamic (DHCP) addressing:
Enterthehostnameoftheremotedevice.
Ifusingstatic(xed)addressing:
EntertheIPAddressoftheremotedevice,
intheformat:xxx.xxx.xxx.xxx
SubnetMask
Thesubnetmaskfortheremotedevice,in
theformat:xxx.xxx.xxx.xxx
IPToolManual(TE200638)
It is recommended that atleasttwodevicesfromeachsubnet
are specied. For increased reliability details of additional
devicesshouldbespecied.
IfstaticIPaddressingisbeingusedthelistshouldcontainthe
deviceswiththelowestIPaddresses.
ThesamelistmustbecopiedtootherEINCtypedeviceson
thenetwork.
Hint:TickingthecheckboxnexttotheRemoteTrendDevices
listretainsthelistinIPTool,allowingittobeeasilycopiedto
other devices:
nq4eyecp412345
Q422B_V53440388
O/S
00:10:70:0D:1E:92
MAC Addr
IQ422-1010U5000
Part No:
LAN
IP
Addr
422
IPToolManual(TE200638)
IQTool Addresser Applet Manual
(TE201299)
IfconnectingtoaLANonEthernet(orstandalonemode):
UseIPTool–seestep12–tosetthedeviceaddressand
LANnumber.
IQ4xx controllers are given a default device address and
LANnumberinthefactory.Thedeviceaddressissetinthe
range11to119onarollingbasiswiththeLANnumbersetto
20. Therefore it may be necessary to set the address/LAN
numberasrequired.
Parameter Value
LocalAddress
1,4to9,11to119
(mustbeuniqueonLAN)
LocalLAN
1,4to9,11to119
(must be the same for all devices
requiredtoformaLAN).
Note:ChangingtheLAN numberand/ordeviceaddress will
causethecontrollertoreboot.
IfconnectingtoaLANoncurrentloop(withonlyIQ4type
controllers):
Use SET’s IQTool Addresser Applet, and run the
DiscoveryWizard.
Select either ‘Automatic Discovery’ (recommended) or
‘Manual Discovery’. If ‘Automatic Discovery’ is chosen
youshouldthenselect‘DuplicateAddressResolution’.
Automatic Discovery: Thetoolwilldiscoverthedevices,
andattempttoresolveanyduplicateaddresses.
Manual Discovery: Either scan the bar code, or press
theServiceButtonforeachcontroller.
WARNING For /230 variants hazardous
voltagesexistwhentheunitispowered.Take
suitableprecautionsifpressingservicebutton.
Note: If the LAN is not as expected after discovery it could
bebecauseofinstallationrelatedreasons,e.g.wiringfaults,
powerfailure,etc.Checkthedevicesareoperatingcorrectly
and repeat discovery. If there are duplicate addresses add the
devicestothegridmanually,usingnetworkaddressandserial
number.IfnecessaryuseSET’sSystemViewtosettheLAN
number,andIQTooltosettheaddress.
If connecting to a LAN on current loop (with pre IQ4
controllers):
UseSET’sIQToolAddresserApplettomanuallyaddthe
IQ4tothegridusingtheserialnumberandaddress.
UseSETsSystemViewtosettheLANnumber.
Deviceaddress(O/S)
LANnumber
FixedIPAddress
orHostname(ifDCHP)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-20187
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
21
SetCurrentLoopBaudRate(IQ4NCor../LANvariantsonly,ifcurrentloopnetworkbeingused)
22
SetupRS232/USBPortAddressing(ifrequired)
23
CheckLANOKIndicator(notIQ4NC)
2 CONFIGURATION (continued)
IQTo ol Mo nit orA pp letM an ual( T E 2012 98)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
Parameter Range
Supervisorport
0,4to9,11to119
Default=0localaccessonly
USB
Engineeringport
0,4to9,11to119
Default=0temporarilytakesaddress125
UseSETsIQToolMonitorApplettosettheSupervisorPortor
USBEngineeringPortasrequired.
IQTo ol Mo nit orA pp letM an ual( T E 2012 98)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
If the IQ4xx is to provide connection to the network for
supervisors and tools it is necessary to setup the RS232
SupervisorPortorUSBEngineeringPortasrequired.
Normal operation indication
LANbuiltOK
AttemptingtobuildLAN
Note:ItisnormalbehaviourforLANOKindicatortoextinguish
forupto1minafterdetectingbaudrate,thenilluminate.
Fault indication (EthernetLAN)
UnabletocommunicateonLAN.
Note: Only applies if current loop is
disabledorisnottted.
Fault indication (CurrentLoopLAN)
every15s
Longerthan2minutesindicates
LAN/internetworkcannotbebuilt.
Checkbaudsettingsofalldevicesoncurrentloop–see
step21,andcheckalldeviceconnections.
Ifstillashing,tloopback:
85
84
86 87
RX-
RX+
TX-
TX+
IfindicatorturnsOFF,deviceisfaulty.IfON,reconnect
networkandswitchoallotherdevicesonthenetwork.
IfstillOFF,checknetworkcablingforshortcircuitswith
amultimeter(NOTMegger).
IfONswitchonotherdevicesinturnuntilfaultydevice
found (i.e. LAN OK goes OFF),inspect thatdeviceto
determineandandcorrectthefault.
BydefaulttheIQ4xxwillautodetectthebaudrateinuseon
thecurrentloop.Ifalldevicesaresettoautodetectthebaud
rate chosen cannot be guaranteed,in which caseit maybe
necessarytomanuallysetonedevicetoaknownrate.
Use SET’s IQTool Monitor Applet to disable autobaud and
specifythebaudrate.
Module Parameter Range
IQ Lan
network
Autobaud
0(disabled)or1(enabled)
Baud Rate
1k2,4k8,9k6,19k2,38k4
LANOK
(green)
8 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
24
DownloadStrategy
25
Check IQ422 or IQ4NC on BACnet (If/BACorIQ4NCandBACnetprotocolcommunicationsrequired)
26
Test Inputs (NotIQ4NC/.../00)
2 CONFIGURATION (continued)
SETManual(TE200147)
IQ4CongurationManual(TE201263)
SETManual(TE200147)
O
I
Switcho Re-connect inputsOpencovers
Closecovers
O
I
Switchon
Note: An Ethernet connection is required to download both
strategyandbackdroples.Otherconnectiontypesonlyallow
downloadofstrategyles.
Note: strategy download is not recommended over current
loopwithbaudrate<9k6.
Note: SET will set up the controller’s date and time to that of
thePCduringdownload.However,theymaybesetupfroma
controllerconguredastimemaster.
ConguretheIQ4xxstrategyusingSET,andtestusingSET’s
simulationmode.
Use SET to download the strategy and backdrop le (if
required).
Use SET to check that the IQ4 BACnet functionality is
operatingbycheckingitappearscorrectlyintheSystemView
onitsBACnetnetwork.
S
Checkdigitalinputs Checkanalogueinputs
LED(yellow)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018
9
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
28
Test Outputs (NotIQ4NC/.../00)
29
Connect Supervisors/Tools/Display
Panels (ifrequired)
31
BackupStrategy
33
Close Panel / Enclosure
32
CloseRotatingCovers
30
CongureWebServer
2 CONFIGURATION (continued)
Connect PCs (e.g. for supervisors/tools) and displays as
describedin‘ConnecttoIQ4xx’onpage10.
Connectionofsupervisors,tools,displaypanelsetccanbe
madedirectlytocontrollerviatheRS232Localsupervisor
Port,USBLocalEngineeringPort,WallbusPort,orEthernet
port.ConnectioncanalsobemadeovertheTrendnetwork
overEthernetorthecurrentloop.
Use SET to upload the strategy and compare it with the
strategyheldbySET.
Note: An Ethernet connection is required to upload strategy
andbackdroples.Otherconnectiontypesonlyallowupload
ofstrategyles.
SETManual(TE200147)
O
I
Switcho Re-connect outputsOpencovers
Closecovers
O
I
Switchon Checkdigitaloutputs Checkanalogueoutputs
LED(yellow)
LOAD
LED(yellow)
LOAD
ConnectiontotheIQ4webservercanbemadeviaHTTP
and/or HTTPS protocol. Where HTTPS is used it will be
necessarytocongureSSLcerticates.
Ifwebaccessisnotrequireditisrecommendedthattheweb
serverisdisabledforsecurity.
IQ4CongurationManual(TE201263)
SETManual(TE200147)
10 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
1
SwitchOPowertoIQ4xx
2
Open Top Cover (ifrequired)
3
Make Connection
O
I
PCviaLocalEngineeringPort(USB)
Connect Directly to Controller
PCviaEthernetPort
RJ45
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
Connection use
Notes
IPTool
ü
SET
ü
RequiresvCNC
WebBrowser
ü
Supervisor
ü
RequiresvCNC
PCviaLocalSupervisorPort(RS232)
CABLE/EJ101442
9wayfemale
Dtype
RJ11
PC
ConnectiontotheIQ4xxcanbemadedirectlyviatheRS232LocalSupervisorPort,USBLocalEngineeringPort,orEthernet
Port.Connectioncanalsobemadeoveranetwork(Ethernet).
Connection use
Notes
IPTool
SET
ü
WebBrowser
Supervisor
Connection use
Notes
IPTool
SET
ü
WebBrowser
Supervisor
ü
IQView8viaLocalSupervisorPort(RS232)
IQView8requiresitsownpowersupply.
Note: If local supervisor port address is 0’ (default)
communication is limited to the IQ4xx. If non-zero,
communicationispossibleovertheentirenetwork.
RJ11
RJ11
RD/SDU-IQ2COMMSCABLE3M
USBcable
MicroBUSBconnector
3 CONNECT TO IQ4XX
IQView8
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018 11
InstallationInstructions-Conguring IQ422, IQ4NC/00, IQ4NC/12
3
Make Connection (continued)
3 CONNECT TO IQ4XX (continued)
RJ11
RJ11
24Vdc
Supply
XW/R/IQ
Mustuseexternal24Vsupply
Connect Directly to Controller
RD-IQ, SDU-xcite, IQView4 via Local Supervisor Port
(RS232)
Connect via Ethernet Network
EnsuretheIQ4xxisconnectedtotheEthernetnetwork.
Connecttheotherdevice(e.g.networkdisplayorPC)to
sameEthernetnetwork and ensure an IP connection is
availablebetweenitandtheIQ4xx.
TomakeaconnectionwithSET,asupervisorordisplay
ensureavCNCisavailableinaTrenddeviceonthesame
Ethernet Trend network and connect to the vCNC as
describedinthesupplieddocumentation.
Note:IfconnectingwithIPTool,thePCshouldbeonthe
same Ethernet segment as the IQ4xx.
To make a connection with a web browser run a web
browseronthePCandaccesstheIQ4xxIPaddressor
hostname.
XW/R/IQwirelesssensorreceiver via LocalSupervisorPort
(RS232)
PC Connection use
Notes
IPTool
ü
SET
ü
RequiresvCNC
WebBrowser
ü
Supervisor
ü
RequiresvCNC
Note: Set local supervisor port address to 0’ (default) as
communicationislimitedtotheIQ422,IQ4NC/00,IQ4NC/12.
IQView4 requires its own power
supply.
RJ11
RJ11
RD/SDU-
IQ2COMMSCABLE3M
RJ11
RJ11
IQView4
RD-IQ
SDU-xcite
StandardEthernetcable
(Cat5etwistedpair)
max100m(109yds)
Hub/Switch
Router
RJ45
RD-WMBviaWallbusPort
RD-WMB
TwistedPairCable
maximumlength60m(200ft)
IQView8
PC
12 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12 InstallationInstructions-Conguring
Please send any comments about this or any other Trend technical
publicationto[email protected]
© 2018 HoneywellProductsandSolutionsSARL,ConnectedBuildingDivision.Allrightsreserved.ManufacturedforandonbehalfoftheConnected
BuildingDivisionofHoneywellProductsandSolutionsSARL,Z.A.LaPièce,16,1180Rolle,SwitzerlandbyitsAuthorizedRepresentative,TrendControl
SystemsLimited.
TrendControlSystemsLimitedreservestherighttorevisethispublicationfromtimetotimeandmakechangestothecontenthereofwithoutobligation
tonotifyanypersonofsuchrevisionsorchanges.
TrendControlSystemsLimited
St.Mark’sCourt,NorthStreet,Horsham,WestSussex,RH121BW,UK.Tel:+44(0)1403211888,www.trendcontrols.com
2
Reset Controller
1
Isolate Power and Disconnect All I/O
3
Re-congureController
The factory reset will erase the strategy and reboot the
controllerinto its original conguration.While the controller
iserasingthestrategy,theWatchdogandLANOKindicators
will ash alternately. During the reboot all indicators will be
ON. Once this process has completed the Watchdog and
LAN OKindicatorswill go OFF, leaving thePowerindicator
ON.This processmaytakeup to 10minutes depending on
controllertype.
Do not switch off the controller until the process has
completed.
4 RESETTODEFAULTS
Gotostep1onpage1.
Unplug the Ethernet cable and press and hold down the
service button. While continuing to hold down the button,
switchonthecontroller. Ensurethebuttonremainspressed
for2to5safterpowerisswitchedon.
WARNING FOR /230 versions: Hazardous
voltages exist in this area when the unit is
powered.Thisoperationshouldonlybeperformed
aftertakingsuitableprecautions
Thestrategy,usermodules(passwords,PINsetc),alarmlogs,
andplotsarecleareddownandthefollowingparametersset
todefaults:
LANnumber
outstation address
IPaddressingmode
IP address
subnetmask
UDPport
identier
Router 1
remoteTrenddevices
VirtualvCNCs.
Timeanddateareleftattheircurrentsettings.
O
I
2to5s
22 23 24 25
RX+
28 29
WMB
RX- TX+
TX-
RX OK
456 789101112
13
14 15 16 17 18
123
230V
19
4 5
10
24V
0V
0V
0V 0V 0V
0V
986 7
1 2 3
Press
22 23 24 25
RX+
28 29
WMB
RX- TX+
TX-
RX OK
456 789101112
13
14 15 16 17 18
123
230V
19
4 5
10
24V
0V
0V
0V 0V 0V
0V
986 7
1 2 3
Release
Followsteps1,2,4,5and8(onpages1to3)to:
IsolatePower,
OpenPanel,
OpenRotatingCovers,
DisconnectAllI/O,
CloseRotatingCovers.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Trend IQ4NC/12 Installation Instructions Manual

Type
Installation Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI