14 IQ23x Series Controllers Installation Instructions TG200539 Issue 2 , 23-Feb-2012
IQ23x Installation Instructions
10 REPLACING AN IQ111 WITH AN IQ231
Fixing Are xing bars used? If NO must drill new xing holes
Is panel depth greater than 93 mm?
If not, can this be modied?
I/O Are current outputs used? If YES replace SRMI with SRMV (or
2SRM for 2 channels), use 2VID on
other channels
SRMV (one for each SRMI,
or 2SRM for 2 channels)
2VID (one for two
External 2DP Is an external 2 line display panel
If YES must t IQ231 with KIT/2xx/RDS KIT/2xx/RDS
Internal 2DP Is internal 2 line display panel tted? If YES must use IQ231/DP/ IQ231/DP/..option
Extenal NDP Is external NDP connected? If YES use cable CABLE/EJ104029 for
signal and power
CABLE/EJ104029
Local
Supervisor
Is local supervisor connected either
permanently or from time to time?
If YES replace complete cable with new
cable CABLE/EJ101442
CABLE/EJ101422
Auxiliary
Supply
Are the auxiliary supply terminals
used?
If YES connect to IQ231 auxiliary supply
terminals by 2 way extension cable.
Rewire connector to swop polarity
2 way extension cable in
KIT/IQ23x/UPGRADE
Link Headers Are Link headers used? If YES identify link headers below
LK/B? Use LKE/15V LKE/15V
LK/E? not supported
LK/0? Link for externally powered current
Internal Node Is an internal node tted? If YES and node is CNC used to
connect local supervisor or NDP to
network, discard board, else if YES,
Is the node based on the TMN board
(CNC2, PNC2, INC2, TMN, since
1999)?
Use TMN type board plate TMN type board plate in
KIT/NODE/IQ23x
Is the node an older board (CNC,
PNC, INC,before 1999, and ANC,
AND, ENC, XN28, XNC+, MNC,
LINC)?
Use pre-TMN type board plate pre-TMN type board plate
in KIT/NODE/23x
Is node CNC, CNC2, PNC, PNC2?
Use EJ100179A001 10 pin in line socket
(Molex) to 25 way female D cable to
connect to printer or device
EJ100179A001 in KIT/
NODE/IQ23x
Is node TMNE? Use EJ103817 10 pin in line socket
(Molex) to 25 way male D cable to
connect to modem
EJ103817 in KIT/NODE/
IQ23x
Is node ANC, AND, XN28? Use 78-0903/1 10 pin in line socket
(Stocko) to 25 way male D cable to
78/0903/1 in KIT/NODE/
IQ23x
Baud Rates Is supervisor baud rate 1k2? Change supervisor baud rate to 9k6
Internal Sensor
Is internal sensor used in internal
digital mode?
If YES set bit 506,1
Note that KIT/IQ23x/UPGRADE also contains the 2 off 4 wide network extension cables (see step 15 below).
1
Survey Unit