20 Technical Manual
Euro Matic DOL 95 Broiler
2.2.2.17 Terminal connections
DOL 95
Terminal Type House Function Activation Note
1
(2=earth)
contact input 1 + 2 water meter not activated:
activated:
open, high, +15V
short-circuited, low
shortest pulse length: 0.5 sec.
(i.e. approx. 1500 litres/hour
with DOL 90)
3
(2=earth)
contact input 1 + 2 sensor in cross auger
container in the house
feed demand:
no feed demand:
short-circuited, low
open, high, +15V
DOL 41R: wires 1 and 3
(dism. DOL 41R does not
result in feed demand)
4
(6=earth)
analog input (0-10V) 1 + 2 input for light sensor can be adjusted RIN ≅ 2.2MΩ
5
(6=earth)
analog input (0-10V) 1 + 2 control of light dimmer can be adjusted RIN ≅ 1MΩ
7
(9=earth)
analog input (0-10V) 1 + 2 input for poultry
weigher 1
can be adjusted RIN ≅ 2.2MΩ
8
(9=earth)
analog input (0-10V) 1 + 2 input for poultry
weigher 2
can be adjusted RIN ≅ 2.2MΩ
10
(13=earth)
+18 V DC supply 1 + 2 supply to environment
sensors
max. current: 50 mA
(corresponds to 2 DOL 14
units and 2 DOL 15 units)
11
(13=earth)
analog input (0-10V) 1 + 2 input for environment
sensor 1
can be adjusted RIN ≅ 2.2MΩ
12
(13=earth)
analog input (0-10V) 1 + 2 input for environment
sensor 2
can be adjusted RIN ≅ 2.2MΩ
14, 15, 16 relay: NO: 14,16
(NC: 14,15)
1 + 2 alarm relay alarm:
no alarm:
relay not operated
relay operated
power failure in DOL 95: alarm
17
(18=earth)
+24 V DC supply common supply to: DOL 99B
DA 74V
4 x DOL 98B
DOL 99B load cells: 100 mA
DA 74V winch motor: 100 mA
DOL 98B poultry
weigher (4 weighers): 200 mA
max. total current: 400 mA
19
(21=earth)
+10 V DC supply common supply to pot. in DA
74V motor for
distribution shutter
potentiometer: 1kΩ - 100kΩ
20
(21=earth)
analog input (0-10V) common distribution shutter
position (potentiometer
in DA 74V)
house 1:
house 2:
0 V
10 V
RIN ≅ 2.2MΩ
22
(24=earth)
analog input (0-10V) common weight signal from
DOL 99B
0 kg:
20 kg:
30 kg:
approx. 1.0 V
approx. 6.8 V
approx. 9.7 V
RIN ≅ 2.2MΩ
23
(24=earth)
analog input (0-10V) common reference signal from
DOL 99B
approx. 9.6 V RIN ≅ 2.2MΩ
25
(26=earth)
contact input 1 feed demand sensor in
DOL 99B house 1
feed demand:
no feed demand:
short-circuited, low
open, high, +15V
DOL 41R: wires 1 and 3
(dismounted DOL 41R does
not result in feed demand)
27
(26=earth)
contact input 2 feed demand sensor in
DOL 99B house 2
feed demand:
no feed demand:
short-circuited, low
open, high, +15V
DOL 41R: wires 1 and 3
(dismounted DOL 41R does
not result in feed demand)
28,29
(30=earth)
contact input
28: +15V
common inductive sensor in
DOL 99B
sensor activated:
sensor not
activated:
high, > 5V
low, < 3V
Note: Terminals 28 and 29
must be short-circuited
31,32,33 relay: NO: 31,33
(NC: 32,33)
common drum motor in DOL
99B
relay operated:
relay not
operated:
the drum is turning
the drum is
standing still
34,35,36 relay: NO: 34,36
NC: 35,36
common feed inlet, silo 4 relay operated: auger 4 running
37,38 relay: NO: 37,38 common feed inlet, silo 1 relay operated: auger 1 running
39,40 relay: NO: 39,40 common feed inlet, silo 2 relay operated: auger 2 running
41,42 relay: NO: 41,42 common feed inlet, silo 3 relay operated: auger 3 running
43,44,45 relay: NO: 43,45
(NC: 44,45)
common control of DA 74V
winch motor
relay operated:
relay not
operated:
house 2
house 1
47,48 mains supply
common
common
49,50 relay: NO: 49,50 1 cross auger, house 1 relay operated:
relay not
operated:
cross auger 1
running
cross auger 1 not
running
motor must be connected via
auxiliary contactor