Nibe FLM 30 Installation And Maintenance Instructions Manual

Type
Installation And Maintenance Instructions Manual

Nibe FLM 30 is an exhaust air module that can utilize the energy in the ventilation air and use it to raise the temperature of the ingoing brine to the heat pump and thereby increase its heating factor. FLM 30 is designed to connect to the FIGHTER 1110/1210 type of ground heat pump. It is positioned directly on FIGHTER 1210, but can also be mounted using brackets (accessory) on the wall.

Nibe FLM 30 is an exhaust air module that can utilize the energy in the ventilation air and use it to raise the temperature of the ingoing brine to the heat pump and thereby increase its heating factor. FLM 30 is designed to connect to the FIGHTER 1110/1210 type of ground heat pump. It is positioned directly on FIGHTER 1210, but can also be mounted using brackets (accessory) on the wall.

INSTALLATION AND MAINTENANCE INSTRUCTIONS
FLM 30
MOS GB 0325-1 611867
FLM 30
R
LEK
Contents
1
For Home Owners
FLM 30
General points for the installation
engineer
Transport and storage .......................................... 6
Handling .............................................................. 6
Frost protection .................................................... 6
Installation ............................................................ 6
Pipe installation
Condensation water hose ...................................... 7
Filling and venting the system ................................ 7
Pressure expansion vessel .................................... 7
Pipe connections (brine) ...................................... 7
Effect transfer to brine .......................................... 7
Ventilation connection
Ventilation flow ...................................................... 8
Exhaust air duct .................................................... 8
Duct installation ...................................................... 8
Adjustment ............................................................ 8
Fan diagram .......................................................... 8
Electrical installation
Electrical connections ............................................ 9
Setting the fan capacity ........................................ 9
Commissioning and adjustment
Preparations ........................................................ 10
Starting ................................................................ 10
Setting the ventilation .......................................... 10
Commissioning .................................................... 10
Readjustment........................................................ 10
Electrical circuit diagram
Electrical circuit diagram ...................................... 11
Component locations
Component locations .......................................... 12
List of components
List of components .............................................. 13
Dimensions
Dimensions and setting-out coordinates .............. 14
Technical data
Technical data ...................................................... 15
Accessories .......................................................... 15
Enclosed kit .......................................................... 15
Dealing with malfunctions
Low or a lack of ventilation ................................ 16
Helping the circulation pump to start .................. 16
General
Concise product description ................................ 2
Installation data .................................................... 2
System description
Principle of operation .......................................... 3
System diagram .................................................. 3
Maintenance routines
Cleaning the air filter ............................................ 4
Cleaning the fan .................................................... 4
Cleaning the ventilation devices .......................... 5
Checking the condensation water seal ................ 5
For the Installation engineer
For Home Owners
General2
For Home Owners
FLM 30
In order to get the ultimate benefit from your FLM 30
you should read through the For Home Owners sec-
tion in this Installation and Maintenance Instruction.
FLM 30 is an exhaust air module. This means it can
utilise the energy in the ventilation air. The energy is
used to raise the temperature of the ingoing brine to
the heat pump.
FLM 30 is intended to be installed with FIGHTER
1110/1210 in houses or the like.
Installation date
Installation engineers
The serial number (95), should always be stated with all
correspondence with NIBE.
089
___________
Trim valve
Selected fan curve
Date______________ Signed__________________________________
Installation data
To be filled in when the exhaust air module has
been installed.
System description
3
For Home Owners
FLM 30
System diagram
C
When the room air has
passed through the exhaust
air module it is discharged.
The temperature has then
dropped as FLM 30 has
utilised the energy in the
room air.
G
The air from the kitchen
fan goes directly out
into a separate duct.
B
The warm room
air is led to FLM
30.
D
FLM 30 increases the
temperature of the brine to the
heat pump.
E
Outdoor air is
drawn into the house.
A
The warm room air is
drawn into the air duct
system.
F
Air is transported
from rooms with
outdoor air devices to
rooms with exhaust
air devices.
Brine in
Brine out
FIGHTER 1210
FLM 30
Exhaust air
Ø 160
Extract air
Ø 160
C
i
r
k
.
p
u
m
p
V
ä
r
m
e
p
u
m
p
V
a
r
m
v
a
t
t
e
n
T
i
l
l
s
a
t
s
v
ä
r
m
e
L
a
r
m
K
o
n
t
r
o
l
l
e
r
a
a
t
t
v
a
t
t
e
n
f
i
n
n
s
i
p
a
n
-
n
a
n
i
n
n
a
n
d
e
n
i
n
-
k
o
p
p
l
a
s
.
1
R
0
FLM 30 is an exhaust air module specially designed to
combine recovery of mechanical exhaust air with an
energy collector in the ground or in rock.
FLM 30 is designed to connect to the FIGHTER
1110/1210 type of ground heat pump.
The integrated fan in FLM 30 extracts the air from the
wet areas of the house to the recovery unit. Here the
energy is transferred to the heat pump's brine, where-
by the temperature increases and raises the heat
pump's heating factor. Energy is stored in the ground
or rock collector even if the heat pump is not in opera-
tion, which fully utilises the exhaust air
energy.
The heat pump capacity is not bound by the amount of
air, but the output can be optimally adapted to suit the
size of the house.
FLM 30 is positioned directly on FIGHTER 1210, but
can also be mounted using brackets (accessory) on
the wall.
Principle of operation
The exhaust air module’s air filter should be cleaned
regularly (about 4-5 times a year) by taking it out and
shaking off any dirt. If the filter is very dirty, turn it up-
side-down and wash it carefully with water.
Open the front cover by pulling it out by the lower
edge, then lifting it up.
Set the switch (8) to “0”.
Release the filter holder by turning the two black
knobs a quarter of a turn anticlockwise.
Pull out the holder, take out the filter (63) and
shake off any dirt. Check that the filter is not dam-
aged. New original filters can be ordered from
NIBE.
Assembly takes place in the reverse order.
The interval between cleaning operations varies and
depends on the amount of dust in the exhaust air.
Maintenance routines4
For Home Owners
FLM 30
LEK
63
LEK
1
TRYCK
1
TRYCK
2
DRAG
2
1
34
93
FLM 30 and its ventilation ducting require some regu-
lar maintenance where the following points should be
checked:
The numbers in brackets refer to the section List of
components.
Clean the fan once a year by taking it out of the ex-
haust air module and carefully brushing the vanes
clean.
Open the front cover by pulling it out by the lower
edge, then lifting it up.
Set the switch (8) to 0.
Dismantle the inner cover by loosening the 6 cover
screws.
The fan is removed by disconnecting the fan cable
connector and the two screws as illustrated.
Once the inner cover has been removed also
check the drip-pan under the heat exchanger. Also
check the outlet from the drip-pan (98) to ensure it
is not blocked.
Assembly takes place in the reverse order.
NOTE!
Avoid distorting the fan blades as
this causes imbalance.
Do not use water or detergents.
Switch (8)
PRESS
PRESS
PULL
Cleaning the air filter
Cleaning the fan
Maintenance routines
5
For Home Owners
FLM 30
Check that there is water in the water seal (92) to the
drip-pan (93). If the water seal is empty or has a very
low water level so that it gurgles water can be filled,
for example, using a watering can through the drip-
pan water hose which then forms a water seal or di-
rectly in the drip-pan (the inner cover plate must then
be dismantled). The water seal is maintained during
filling.
After using for a period of time dust and other particles
can clog the water seal, consequently, you should
check this regularly and clean when necessary.
The ventilation devices in the house should be
cleaned regularly to maintain the correct ventilation.
The device settings must not be changed.
NOTE! If you take down more than one ventilation de-
vice for cleaning, do not mix them up.
Cleaning the ventilation devices
Checking the condensation
water seal
LEK
93
92
98
General points for the installation engineer6
For the Installation engineer
FLM 30
FLM 30 is installed on FIGHTER 1210 or using brack-
ets when connected to FIGHTER 1110. Noise from
the circulation pump or fan can be transferred to the
brackets. Consequently, mount on an outside wall if
possible. If it is not possible to mount FLM 30 on an
outside wall avoid a wall connecting to a bedroom or
living-room.
NOTE! Ensure that that there is sufficient space (15
mm) above the exhaust air module to open the front
cover, see the section Dimensions.
Route pipework so it is not fixed to an internal wall that
backs on to a bedroom or living room.
The exhaust air module can contain in-
flammable anti-freeze in the brine circuit
(for example ethanol). Special care
should be exercised during handling, in-
stallation, service, cleaning and scrap-
ping to avoid the risk of leakage.
The exhaust air module should be transported and
stored in the dry.
Alt. 1
Alt. 2
FLM 30 features integrated frost protection (65) that
automatically defrosts the heat exchanger (62) if nec-
essary. This is achieved by the brine flow through the
heat exchanger being slowed sufficiently so that the
warm room air can thaw the ice.
Normally the temperature of the incoming brine to
FLM 30 is shown on the display on the frost protec-
tion. The frost protection is set at the factory and
should not need adjusting. Changes to the parameters
can result in the heat exchanger becoming blocked by
frost. The buttons are locked with a code.
In the event of a fault indication the frost protection
stops the FLM 30 (however, not the ventilation flow).
Fault indications on the display
Er Memory fault
-- Short circuit temperature sensor (66)
00 Defective temperature sensor (66)
VL-Temp
4
7
(
5
2
)
°
C
WW-Temp
4
8
°
C
L
E
K
Installation
Frost protection
Handling
Transport and storage
Pipe installation
7
FLM 30
For the Installation engineer
The condensation water hose is routed directly to the
floor drain or other water seal. Ensure that the end of
the hose runs out above the water level in the floor
drain. The pipe installation must be carried out in ac-
cordance with current norms.
Output transfer to
brine
FLM 30 is filled from the heat pump's brine, see the
Installation and Maintenance instructions in question.
Vent using the venting screw (5). The switch (38)
should be set to 0. when venting
SF
Brine in
Brine out
C
i
r
k
.
p
u
m
p
V
ä
r
m
e
p
u
m
p
V
a
r
m
v
a
t
t
e
n
T
i
l
l
s
a
t
s
v
ä
r
m
e
L
a
r
m
K
o
n
t
r
o
l
l
e
r
a
a
t
t
v
a
t
t
e
n
f
i
n
n
s
i
p
a
n
-
n
a
n
i
n
n
a
n
d
e
n
i
n
-
k
o
p
p
l
a
s
.
1
R
0
SÄV
FLM 30
Exhaust air
Ø 160
Extract air
Ø 160
EXP
BV
RV
P
EXP
Pressure expansion vessel
According to the
recommendations
SÄV Safety valve
BV Check valve Included in FLM 30
SF Particle filter
RV Trim valve Included in FLM 30
P Pressure gauge
The brine circuit should be fitted with a pressure ex-
pansion
vessel. If there is a level vessel this should
be replaced. The brine
side should be pressurised to
at least 0.5 bar.
The pressure expansion vessel should be dimen-
sioned as set out in the diagram, to prevent operating
disturbances. The pressure expansion vessel covers
the temperature range from -10 °C to +20 °C at a pre-
pressure of 0.5 (bar) and the safety valves opening
pressure 3 bar.
0
0
l
100
200
l
300
10
20
30
Pressure expansion vessel
Brine
volume
40
50
400
500
600
700
800
900
1000
The lowest permitted incoming brine temperature is -
5 °C.
When installing on FIGHTER 1210 the space under
FLM 30 is limited to 90 mm. This may mean that the
pipe connections on FIGHTER 1210 must be short-
ened.
The brine is connected to FLM 30 as set out on the
outline diagram.
0
100
(m
3
/h)
300
0,5
1
1,5
Överförd effekt (kW)
Luftflöde
2
2,5
500
200
400
Köldbärare in vid 0 °C
Köldbärare in vid 5 °C
The diagram shows the effect transferred from the
ventilation air to the brine and applies for an air tem-
perature of +20 °C and 50% relative air humidity.
Transferred effect (kW)
Air flow (m
3
/h)
Brine in at 0 °C
Brine in at 5 °C
Pipe connections (brine)
Condensation water hose
Pressure expansion vessel
Filling and venting the system
Ventilation connection8
For the Installation engineer
FLM 30
FLM 30 is connected so that all ventilation air, except
for the kitchen fan, passes the heat exchanger (62) in
the exhaust air module. Minimum flow should conform
to the demands as set out in applicable norms. The
ventilation flow should conform to applicable norms.
Switching the ventilation capacity is described in the
section Electrical installation Setting the fan capaci-
ty. The numbering of the curves refers to the terminal
block on the fan transformer (22).
To prevent fan noise being transferred to the exhaust
air devices, it may be a good idea to install a silencer
in the duct. This is especially important if there are ex-
haust air devices in bedrooms.
Connections can be made using flexible hoses, which
should be stretched well and routed to allow easy re-
placement. The extract air duct must be provided with
diffusion-tight insulation over its entire length.
Provision must be made for inspection of the duct.
Make sure that there are no reductions of cross-sec-
tional area in the form of creases, tight bends etc,
since this will reduce the ventilation capacity. All joins
in the ducting must be sealed and pop-riveted to pre-
vent leakage. The duct system must be carried out in
accordance with current norms. A minimum of air
tightness class B is recommended.
To obtain the necessary air exchange in every room of
the house, the exhaust air devices must be correctly
positioned and adjusted. A defective ventilation instal-
lation may lead to reduced exhaust air module effi-
ciency and thus poorer operating economy, and may
result in damage to the house.
The diagram below shows the available ventilation ca-
pacity.
Ventilation flow
Fan diagram
Duct installation
Adjustment
NOTE!
A duct in a masonry chimney stack
must not be used for extract air.
Luftflöde
Tillgängligt statiskt tryck
Pa
mmvp
40
30
10
20
1
2
3
4
5
6
7
8
9
10
0
100
200
300 400
m
3
/h
400
300
200
100
0
500
500
50
0
25
50
75
100
l/s
The kitchen flue must not be connected to FLM 30
Air flow
mmwp Pa
Available static pressure
Exhaust air duct
Electrical installation
9
For the Installation engineer
FLM 30
22
8
Selection of the fan capacity is done by connecting
the black cable to a suitable outlet on the
terminal block (22). See the section Ventilation con-
nection - Fan diagram.
Connection
1
2
3
4
5
6
7
8
9
10
Voltage (V)
100
110
125
140
155
170
185
200
215
230
22
56789103412
Svart
When FLM 30 is placed directly above the heat pump
the power supply can be connected to the heat
pumps terminal block. The connection plug must
however be cut off.
If FLM 30 is installed independently (together with a
FIGHTER 1110 or if the ceiling level is not high
enough to allow placement above 1210) it can be con-
nected either to an earthed 1-phase wall socket or
through permanent installation. When a permanent in-
stallation is used, FLM 30 must be preceded by a cir-
cuit-breaker.
If an insulation test is to be carried out in the building,
disconnect the exhaust air module.
Open the front cover by pulling it out by the lower
edge, then lifting it up.
Switch off the voltage by turning the switch (8)
to 0.
Remove the securing screw on the electrical box
and pull out the electrical box as illustrated.
Select a suitable fan capacity, see below.
Assembly takes place in the reverse order.
NOTE!
Electrical installation and service
must be carried out under the
supervision of a qualified electrician.
Electrical installation and wiring must
be carried out in accordance with the
stipulations in force. Work behind
screwed covers may only be carried
out under the supervision of a
qualified electrician.
Black
Setting the fan capacity
Electrical connections
Commissioning and adjusting10
For the Installation engineer
FLM 30
Start the heat transfer pump on the heat pump, see
the Installation and Maintenance instructions in ques-
tion.
The brine flow across the FLM 30 is controlled by
means of the circulation pump (16) and trim valve (81)
so that the temperature difference on the brine in and
out through FLM 30 is 3 - 4 degrees. Adjustments are
made when the heat pump is running. The tempera-
ture difference applies at a room temperature of 20
degrees and 0 degrees on the brine.
The brine flow through FLM 30 will be from 0.1 l/s (360
l/h) to 0.15 l/s (540 l/h) at the above temperature dif-
ferences, depending on the ventilation flow.
When the heat pump is at a standstill the internal cir-
culation pump in FLM 30 gives from 0.085 l/s (306 l/h)
to 0.125 l/s (450 l/h) in the return charging flow to the
collector. This applies to a heat pump with an approxi-
mate rated output of 4 kW. For a 15 kW heat pump the
corresponding flow is from 0.09 l/s (324 l/h) to 0.14 l/s
(504 l/h).
Before commissioning check that the brine circuit is
filled and vented.
Check the pipe system for leaks.
Check that the brine circuit is pressurised to at least
0.5 bar.
Set the switch (38) to 1.
Set the switch (8) to 1.
Check that the fan and circulation pump are running.
The ventilation flow and correct outlet on the terminal
block (22) are set out on the ventilation drawing.
Change the fan capacity by moving the black cable
on the terminal block (22) if necessary. Use the
lowest possible output to obtain the lowest noise
levels.
Make sure that all outdoor air devices are fully-
open.
Set correct ventilation flows on the exhaust air de-
vices.
Venting may be necessary after a period of use. Vent
using the venting screw (5). The switch (38) should be
set to 0 when venting.
CommissioningPreparations
Starting
Setting the ventilation
Readjustment
Electrical circuit diagram
11
For the Installation engineer
FLM 30
L
3412
12NPE
756
1089
8
7
9
10
11
BROWN
BLACK
BLUE
N
2
1
3412
7856
9
10
BLACK
54
36
8
9
4B
1A
5B
2A
14
57
16
1
2
PE
A1
A2
L
22
N
66
59
20
65
38
10
PE
Component locations12
For the Installation engineer
FLM 30
90
59
16
36 74 73
20
62
5
91
66
63
93
LEK
22
54
57
38
8
65
9
14
10
List of components
13
For the Installation engineer
FLM 30
3 Connection pipe out from FLM 30
4 Connection pipe in to FLM 30
5 Air screw
8 Switch, positions 0 - 1, main switch
9 Terminal block, incoming supply
10 Cord with connection plug
14 Terminal block, internal
16 Circulation pump
20 Connector, fan
22 Terminal block for fan speed
36 Fan
38 Switch, positions 0 - 1, circulation pump
54 Fan transformer
57 Operating condenser, fan
59 Solenoid valve
62 Heat exchanger
63 Air filter
65 Frost protection
66 Temperature sensor, frost protection
73 Brine out, compression ring Ø 15 mm
74 Brine in, compression ring Ø 15 mm
81 Trim valve, DN 15
82 Check valve, DN 32
90 Ventilation connection exhaust air, Ø 160 mm
91 Ventilation connection extract air, Ø 160 mm
92 Drip-pan water hose
93 Drip-pan
95 Type plate
98 Drip-pan drain
Dimensions14
For the Installation engineer
15
Min avstånd
50 mm från vägg
440
400
365
235
180
Köldbärare in Ø 15
445
100
50
Köldbärare ut Ø 15
Droppskålsavlopp
74
73
98
90
300
70
Erforderligt utrymme för
demontering av frontlucka
Vy sedd underifrån
Fritt installationsutrymme
i FLM 30
445
115
305
Avluft
Ø 160
Frånluft
Ø 160
626
598
95
300
90
510
300
Fritt installationsutrymme
i FLM 30
Clearance in front of FLM 30
should be at least 600 mm for
maintenance and servicing.
The distance to the wall must
be at least 50 mm with the in-
stallation of FLM 30 on FIGHT-
ER 1210.
Dimensions and setting-out coordinates
FLM 30
Space required for removal
of front access panel
Brine in Ø15
View from below
Brine out Ø15
Drip-pan drain
Extract air
Ø 160
Exhaust air
Ø 160
Minimum distance
from wall 10 mm
Clear installationspace
in FLM 30
Clear installationspace
in FLM 30
Technical specifications
15
For the Installation engineer
FLM 30
Width 600 mm
Net weight 60 kg
Rated output fan 225 W
Max air flow approx. 400 m
3
/h
Enclosure class IP 21
Sound level in the boiler house*** 34-44 dB(A)
Height 400 mm
Depth 625 mm
Supply voltage 230 V 50 Hz
Rated output, circulation pump 95 W
Max cooling effect 2,3 kW
Sound power level** 38-48 dB(A)
Technical data
IP 21
Brackets and cover plate
Wall mounting of FLM 30
Part no 089304
Accessories
Enclosed kit
** A-weighted sound power level (L
wA
). The value varies with the selected fan curve.
*** A-weighted sound pressure level (L
pA
). The value varies with the rooms damping capacity.
These values apply with a damping of 4 dB.
L
E
K
Trim valve
Drip-pan water hose
Connecting pipe
Check valve
L
E
K
L
E
K
LEK
3
4
92
81
82
LEK
LEK
Dealing with malfunctions16
For the Installation engineer
FLM 30
If the operating disturbance cannot be rectified by means of the above an installation
engineer should be called.
Cause: Filter (63) clogged.
Action: Clean or replace the filter, see the section
Maintenance procedures - Cleaning the
air filter.
Cause: Closed or too hard throttled exhaust air de-
vice.
Action: Check and measure the air flow.
Cause: Circuit or main MCB tripped.
Action: Reset or replace the MCB.
Cause: Fan clogged.
Action: Check the fan, clean if necessary. See the
section Maintenance routines - Cleaning
the fan.
Cause: The battery blocked by frost.
Action: Switch off the circulation pump using
switch (38). Let it remain switched off for 24
hours.
Low or a lack of ventilation
In the event of malfunction or operating disturbances first
check the points below:
NOTE!
The
product’s serial number
should always be stated with all
correspondence with NIBE.
089
__________
Open the front cover by pulling it out by the lower
edge, then lifting it up.
Set the switch (8) to 0.
Dismantle the inner cover by loosening the 6 cov-
er screws.
Loosen the venting screw with a screwdriver. Hold
a cloth around the screwdriver blade as a certain
amount of fluid may run out.
Insert a screwdriver and turn the pump rotor.
Screw in the venting screw.
Start FLM 30 and check whether the circulation
pump runs.
It is usually easier to start the circulation pump with
FLM 30 running, switch (8) set to 1. If helping the cir-
culation pump to start is performed with FLM 30 run-
ning, be prepared for the screwdriver to jerk when the
pump starts.
Helping the circulation
pump to start
Luftningsskruv
16
LEK
G
R
U
N
D
FO
S
Type UPS
25 - 60
130
P/N:59526447
230V-
H
EJS
AN
PC
;0017NIB
D
K
50Hz
IP 44
TF 110
Class H
M
ax. 10bar
2.5uF
450.20
65
0.30
90
0.40
1m(A) P,(W)
Venting screw
R
NIBE AB
SWEDEN
Box 14
Järnvägsgatan 40
SE-285 21 MARKARYD
Tel: +46 - (0)433 - 73 000
Fax: +46 - (0)433 - 73 190
www.nibe.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Nibe FLM 30 Installation And Maintenance Instructions Manual

Type
Installation And Maintenance Instructions Manual

Nibe FLM 30 is an exhaust air module that can utilize the energy in the ventilation air and use it to raise the temperature of the ingoing brine to the heat pump and thereby increase its heating factor. FLM 30 is designed to connect to the FIGHTER 1110/1210 type of ground heat pump. It is positioned directly on FIGHTER 1210, but can also be mounted using brackets (accessory) on the wall.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI