Nibe FIGHTER1310 HPAC Installation And Maintenance Instructions Manual

Category
Heat pumps
Type
Installation And Maintenance Instructions Manual
R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGHTER1310 HPAC
MOS GB 0322-1 611682
FIGHTER1310 HPAC
LEK
LEK
Contents 1
FIGHTER 1310 HPAC
General points for the installation engineer
Transport and storage .......................................... 11
Installation ............................................................ 11
Floating regulation ................................................ 11
Collectors ............................................................ 11
Inspection of the installation ................................ 11
Control (also with accessories)
General ................................................................ 12
Degree minutes .................................................... 12
Settings on the display ........................................ 13
Pipe connections
General ................................................................ 16
Pipe connection, the building’s
distribution system .......................................... 16
Pipe connection, collector side ............................ 16
Condensation insulation ...................................... 16
Outline Diagram .................................................. 17
Pump capacity diagram, the building’s
distribution system
............................................ 18
Pump capacity diagram, collector side ................ 18
Electrical connections
Electrical installation FIGHTER 1310 .................. 19
Connecting the supply FIGHTER 1310 ................ 19
Connecting the outside sensor FIGHTER 1310 .. 20
Connecting temperature sensors supplied with
the unit FIGHTER 1310 .................................. 20
Connecting the supply and control HPAC ............ 21
Valve settings HPAC ............................................ 22
Terminal blocks for external units FIGHTER 1310
..24
Reversing valve (RV) .......................................... 24
Connecting FIGHTER 1310 HPAC ...................... 24
Commissioning and adjusting
Filling and venting the pipe system ...................... 25
Start-up and inspection ........................................ 25
Readjustment, the building’s distribution system 26
Readjustment, collector side ................................ 26
Internal control panel ............................................ 26
Setting of heating/cooling automatic system
Setting of heating/cooling .................................... 27
Heating curve offset -2 ........................................ 27
Heating curve offset 0 .......................................... 27
Heating curve offset +2 ........................................ 27
Component placement
Component placement FIGHTER 1310................ 28
List of components
List of components .............................................. 29
Component placement
Component placement HPAC .............................. 30
Circuit diagram
Circuit diagram .................................................... 31
Dimensions
Dimensions and setting-out coordinates
FIGHTER 1310 ................................................ 32
Dimensions
Dimensions and setting-out coordinates HPAC .. 33
Accessories
Accessories .......................................................... 34
Enclosed kit .......................................................... 34
Technical specifications
FIGHTER 1310 .................................................... 35
HPAC .................................................................. 35
Actions with operating disturbances
Low room temperature ........................................ 36
High room temperature ........................................ 36
Low hot water temperature or no
hot water .......................................................... 36
Indications ............................................................ 37
Draining, the building’s distribution system .......... 38
Draining, collector side ........................................ 38
Helping the circulation pump to start .................... 38
Cleaning the circulation pump .............................. 39
General
Concise product description ................................ 2
Setting table ........................................................ 2
System description
Principle of operation .......................................... 3
Front panel
Front panel .......................................................... 4
Functions .............................................................. 5
Setting different operating modes (even with
accessories) ...................................................... 5
Control
General ................................................................ 6
Setting heat/cooling .............................................. 6
Changing the room temperature .......................... 6
Heating production .............................................. 7
Domestic hot water .............................................. 7
Heat transfer pump .............................................. 7
Cooling ................................................................ 7
Passive cooling .................................................... 7
Active cooling ...................................................... 7
Available information and
on-display settings ............................................ 8
For the Installation engineer
For the System manager
General
FIGHTER 1310 HPAC
For the System manager
2
In order to get the best results from the climate system FIGHTER 1310 HPAC you should read
through the section For the System manager in these Installation and Maintenance instructions.
FIGHTER 1310 HPAC is a
climate system
for heating and cooling large houses and apartment build-
ings as well as industrial properties. Ground, rock or lakes can be used as the heat exchange source.
FIGHTER 1310 HPAC is a Swedish made quality product offering a long life span and safe opera-
tion.
Installation date
Accessories: ..............................
Hot water control ..............
Temperature signal distributor .. Room sensor ................
Other ............................
Type designation / serial number
HPAC 089 _ _ _ _ _ _ _ _ _ _ _
Installation engineers
Type designation / serial number
FIGHTER 1310 - _ _ kW / 089 _ _ _ _ _ _ _ _ _ _ _
Completed by the installation engineer when the heat pump is installed
The type of heat transfer fluid Mixing proportion/freezing point
Active drilling depth/collector length
Commissioning checks
Heat transfer fluid temperature(supply/return) _____ / _____
(Nominal temperature diff 2 5 °C)
Heating medium temperature (in/out) _____ / _____
(Nominal temperature diff 5 10 °C)
Settings
* The immersion heater, hot water
Menu Basic
setting
2 Room .............. 20
2b Room comp .............. 3
3 Start C .............. 25
3 Start H .............. 18
4 WW-in .............. 45
4 HW start .............. 44
4b HW stop .............. A
5 Brine Out .............. -12
6 Curve H .............. 9
6 Curve C .............. 2
6b WW out min .............. 5
Menu Basic
setting
6b WW out max .............. 55
10b HP-min A .............. 60
10b HP-min B .............. 200
10c HP-stop B .............. 150
11 WW diff HP .............. 13
11 Diff AC .............. 4
12 HP-int .............. 20
17 HP-no. .............. 0
17 Hw-choice .............. 1
18 Cooling .............. On
Date __________ Signature __________________
FIGHTER 1310 HPAC is a system with the main com-
ponents: heat pump FIGHTER 1310 and exchange
module HPAC. FIGHTER 1310 has an integrated con-
trol computer with a display for control of the
heating/cooling, integrated circulation pumps and is
connected via the HPAC module to the external col-
lector and the building’s distribution system for heating
and cooling.
The heat exchange from the heat source (rock ,
ground or lake) takes place via a closed cooling medi-
um system where water mixed with antifreeze circu-
lates to the heat pump.
Ground water can also be used as a heat source how-
ever, this requires an intermediate heat exchanger
between the HPAC and the ground water.
System description 3
For the System manager
FIGHTER 1310 HPAC
Principle of operation
A
Cirk.pump
Värmepump
Varmvatten
Tillsatsvärme
Larm
Kontrollera
att vatten
finns i pan-
nan innan
1
R
0
P
BP
FIGHTER 1310
HPAC
AB
B
A
VXV
FG RG
VPA
+2
0
-2
1
R
0
WW-out
49 (50) °C
Hot-water
51 °C
Front panel
FIGHTER 1310 HPAC
For the System manager
4
Indicator lamps
Function keys
Display
Front panel
B
Switch
A
D
Increase/reduce heat
C
E
PLEASE NOTE!
Make sure there is water in the heat pump
before putting switch (A) into position 1 or R.
Power switch
Three-position switch (1 0 R)
0Heat pump off.
1Normal mode. All control functions connect-
ed.
RStandby. Not connected at the factory.
Function keys
Channel
To choose window menu.
Increase
To increase the current value.
Reduce
To reduce the value currently displayed.
Operating mode
Room heating/cooling on/off.
Extra Hot Water
No function
Display
In normal operation the display shows:
WW out: The actual system temperature, that is
to say, the supply temperature
of the water out of
HPAC. The figure in brackets shows the calculat-
ed flow temperature.
Hot water: Actual hot water temperature
(accessory).
Indicator lamps
Room heating/cooling
A steady light indicates that room
heating is allowed.
Compressor
A flashing light shows that a compres-
sor is running.
A steady light shows that both com-
pressors are running.
Hot water (accessory)
A steady light shows that hot water
charging is in progress.
Supplementary heating (external)
No function.
Alarms
Flashes rapidly when a fault has
occurred.
Increase/reduce heating/cool-
ing
The Increase/reduce heat knob raises or lowers
the room temperature (changes the tempera-
ture of
WW-out
).
Front panel 5
For the System manager
B
A
CE
Functions
D
Normal mode (basic setting):
Hot water charging cuts in if necessary.
LEDs:
Room heating/cooling: Lit
Hot water: Steady light during hot water
charging
LEDs:
Room heating/cooling: Lit
Hot water: Lit during hot water charging
Supplementary heat Not lit (no function)
No room heating position: Press the Operating
mode button again.
LEDs:
Room heating/cooling: Not lit
Hot water: Lit during hot water charging
Supplementary heat Not lit (no function)
The system returns to normal mode the next time the
Operating mode button is pressed.
Setting different operating modes
(also applies with accessories)
FIGHTER1310 HPAC
Control
For the System manager
6
FIGHTER 1310 HPAC
Setting takes place by programming the Curve slope,
see the section Available information and settings on
the display, and by setting the Heating curve offset
using the Increase/reduce heat knob on the panel.
If the required room temperature is not obtained, read-
justment may be necessary.
PLEASE NOTE! Wait one day between settings so
that the temperatures have time to stabilise.
Readjusting the setting
Cold weather conditions
If the room temperature is too low, increase the
value for the heating curve by one step.
If the room temperature is too high, reduce the
value for the heating curve by one step.
Warm weather conditions
If the room temperature is too low, turn the
Increase/reduce heat knob one step clockwise.
If the room temperature is too high, turn the
Increase/reduce heat knob one step anticlockwise.
The indoor temperature depends on several factors.
Sunlight and heat emissions from people and house-
hold machines are normally sufficient to keep the
house warm during the warmer parts of the year.
When it gets colder outside, the heating system must
be started. The colder it is outside the warmer the out-
going temperature supply fan coil units must be. To
ensure sufficient cooling is obtained the outgoing tem-
perature to the fan coil units is lowered with a cooling
requirement. In FIGHTER 1310 HPAC this adaptation
is handled automatically by a control computer, which
must however be set with the right basic settings.
The heat pump is controlled by built-in sensors for
flow and return heat transfer fluid temperatures (col-
lector). Heat transfer fluid return temperatures can, if
so required, be limited to a minimum (e.g. for ground
water systems).
Control of the heating/cooling production is performed
based on the floating condensing principle, i.e. the
temperature level needed for heating at a specific out-
door temperature is produced guided by collected val-
ues from the outside and flow sensors. As an option,
room sensors can also be used to compensate for
deviations in room temperature.
General
Changing the room temperature manually
If you want to temporarily or permanently increase or
lower the indoor temperature in relation to the previ-
ous heat setting turn the Increase/reduce heat knob
clockwise or anticlockwise. One line approximately
represents a 1 degree change in the room tempera-
ture in the heating mode.
NOTE! An increase in the room temperature may be
inhibited by the radiator or floor heating thermostats, if
so these must be turned up.
Changing the room temperature
Setting heat/cooling
Control 7
For the System manager
The heat transfer pump is in operation when one of
the compressors is in operation.
When fitted with the Hot water control accessory and,
for instance, our hot water accumulator VPA, the
FIGHTER 1310 HPAC can be used for hot water pro-
duction.
The supply of heat to the building is controlled by the
control computer settings (curve slope and offset).
After adjustment the correct amount of heat for the
current outdoor temperature is supplied. The flow tem-
perature (
WW out
) from HPAC will vary around the
theoretical required value (value in brackets on the
control computer display). For subnormal tempera-
tures the computer calculates a deficit in the form of
degree minutes, which results in the acceleration of
heat production. The larger the subnormal tempera-
ture, the greater the heat production.
Heat production
Hot water production
Heat transfer fluid pump
With active cooling the compressor starts and the pro-
duced cooling circulates to the buildings distribution
system and the heat circulates out to the ground/rock
collector.
Active cooling.
Using the circulation pumps in FIGHTER 1310 fluid
from the ground/rock collector circulates through the
buildings distribution system and cools the building.
Cooling comes from the ground/rock collector.
Passive cooling
The cooling supply to the building is controlled by the
computer settings (curve gradient and offset). After
adjustment the correct amount of cooling for the cur-
rent outdoor temperature is supplied. The flow tem-
perature (
WW out
) from HPAC will vary around the
theoretical required value (value in brackets on the
control computer display). In the event of excess tem-
perature the control computer calculates a surplus in
the form of degrees-minutes, which means that the
greater the excess temperature that temporarily pre-
vails the more the connection of cooling production is
accelerated.
FIGHTER 1310 HPAC automatically switches to cool-
ing mode when the outdoor temperature exceeds the
set value in menu 3.
When the cooling requirement is large and passive
cooling is not sufficient active cooling is engaged at
the set limit value.
Cooling
FIGHTER 1310 HPAC
PLEASE NOTE!
This system solution means that the
heat transfer fluid will also circulate
through the heating system. Check
that all component parts are designed
for the heat transfer fluid in question.
Control
FIGHTER 1310 HPAC
For the System manager
8
FIGHTER 1310 is equipped with a 2-row background
lit LCD-display. The heat pump can be set via this dis-
play and its associated buttons.
Channel selection
The Channel button lets you browse through the fol-
lowing display modes to find the information you
require.
Values within brackets are also described within
brackets.
If a value is programmable, this is denoted by a [P]
(Programmable) in front of the value.
If the next value cannot be changed, you can access
the next menu by pressing Channel.
Setting up
The first step when changing a value is to press
the Increase button once. A cursor (line) then
appears under the value. Now you can either
increase or reduce the value with the Increase
or Reduce buttons.
Available information and on-display settings
WW-out 47 (52) °C
Hot water 49 °C
Outdoor -14 °C
Room 23,0(18) °C
Outdoor -14 °C
Room- comp 4
StartC 25 °C
StartH 18 °C
In normal mode, the above information appears on the
LCD-display of the heat pump.
WW out
Current flow temperature
(Calculated flow temperature.)
() if there is no heating or cooling demand
Hot water *
Actual hot water temp.
With hot water charging hot water (WW) is stated on
the top row.
1
Outdoor
Actual outside temperature.
Room **
Actual room temperature.
[P](Target value set on room sensor.)
Setting range: 5 30 °C.
Default setting is 20 °C.
2
Outdoor
Actual outside temperature.
Room-comp **
[P]When the room temperature deviates by 1
degree C, the WW out set point is changed by
the value indicated.
A higher value gives a quicker reaction if the
temperature in the premises is too high or too
low.
Normal value is 4.
Setting range: 0 6 °C)
Default setting is 3 °C.
Setting room-comp
(Only applies if a room sensor is connected).
After setting the curve slope, press the Channel
button. The cursor moves under the figure for
Room-comp. Change the figure using the Increase
or Reduce buttons. A higher value gives a quicker
reaction to excess or low indoor temperatures. The
normal value for a radiator system is 4.
2b
Start C
Start temperature for cooling function.
Setting range: 24 - 30 °C (outdoor temperature).
With connected the room sensor: If the room tem-
perature exceeds the set value by more than 3 and
the cooling function in menu 18 is On, cooling
mode starts automatically, independent of start C.
Default setting is 25 °C.
Start H
Start temperature for heating function.
Setting range: 10 -22 °C (outdoor temperature).
Default setting is 18 °C.
3
*Only displayed if the hot water control accessory
has been installed.
** Only displayed if a room sensor is connected.
Control 9
For the System manager
FIGHTER 1310 HPAC
WW-in 37(45) °C
HWstart 49(44) °C
WW-in 37(45) °C
HW-stop 49( A) °C
BrineIn
BrineO +2 °C
0(-12) °C
CurveH 9
CurveC 2
WW-out min 5 °C
WW-out max 55 °C
WW in
Actual temperature of incoming heating medium.
[P](Max permitted return temperature.)
Setting range: 40 50 °C.
HW stop
Actual temperature in lower part of water heater
outer jacket.
[P](Chosen stop level for hot water production.)
Setting range: 20 70 °C and A
Default setting is A.
Ameans that the hot water production is stopped
by the pressostat.
4b
WW in
Actual temperature of incoming heating medium.
[P](Max permitted return temperature.)
Setting range: 40 50 °C.
Default setting is 45 °C.
HW start
Actual temperature in lower part of water heater
outer jacket.
[P](Chosen start level for hot water production.)
Setting range: 20 60 °C.
Default setting is 44 °C.
4
Available information and on-display settings
Curve H
Setting range 1 15
Default setting is 9.
Curve C
Setting range 1 3
Default setting is 2.
6
6b
This menu is a submenu to menu 6 and is acti-
vated by placing the cursor under the value for
Curve (or Room comp if a room sensor is con-
nected) and pressing the Channel button.
WW out min Min temp for flow line
[P]Setting for the minimum calculated flow line
temperature.
Setting range: 2 20 °C.
Basic setting: 5 °C
WW out max Heating medium flow, max) Max temp
for flow line
[P]Setting for the maximum calculated flow line
temperature.
Setting range: 30 70 °C.
Default setting is 55 °C.
Brine In
Temperature of incoming heat transfer fluid.
Brine Out
Temperature of outgoing heat transfer fluid.
[P](Min permitted outgoing temperature of heat
transfer fluid from heat pump.)
This setting should only be changed by a special-
ist. It is used for minimum limiting with alarm, for
example as an anti-freezing function in ground-
water systems or exhaust air systems.
A suitable setting with an intermediate heat
exchanger would be 0 °C. When the lowest value
(-12) is set, minimum limiting and the alarm are
disabled.
Setting range: -12 +10 °C.
Default setting is -12 °C.
5
Control
FIGHTER 1310 HPAC
For the System manager
10
Available information and on-display settings
PLEASE NOTE!
Enter the chosen settings in the table
on page 2 of this manual. The details
are important for
service work.
HP start A
Shows the total number of starts of heat pump
module A.
HP start B
Shows the total number of starts of heat pump
module B.
7
HP time A
Shows the total number running hours for heat
pump module A.
HP time B
Shows the total number of running hours for heat
pump module B.
English
[P]Chosen language setting. Press Increase to
change language. When you have chosen the
required language, press the Channel button.
Channel 1 re-appears.
A/B off
Alternately shows the operating status of respec-
tive compressors: A off, B off, A HP on, B HP on,
A start in X min, B start in X min or WW in high
for module A respective B.
8
9
HPstart A 2
HPstart B 2
HP-time A 0h
HP-time B 0h
English
A off
General points for the installation engineer 11
For the Installer
FIGHTER 1310 HPAC
In accordance with current norms, the heating/cooling
installation must undergo an installation check before
being used. The inspection must be carried out by a
suitably qualified person and should be documented.
The above applies to closed heating/cooling installa-
tions. If the heat pump or the cooling module are
replaced the installation must be inspected again.
The FIGHTER 1310 must be installed on a firm sur-
face, preferably a concrete floor or a concrete founda-
tion in a boiler room or a separate equipment room.
HPAC is installed suspended on the wall. Avoid
installing it in or adjacent to a sound-sensitive room.
Wherever the unit is located, any wall that backs on to
a bedroom should be fitted with sound insulation.
The FIGHTER 1310 must be transported and stored
upright and dry. HPAC should be transported and
stored horizontal and dry.
Transport and storage
Setting up the heat pump
Collectors
Inspection of the installation
The length of the collector hose varies depending on
the rock /ground conditions and on the distribution
system.
The maximum length of each loop is 500 metres.
The hose normally used is PEM hose 40 x 2.4 PN 6.3.
Collectors are always connected in parallel, with some
means of adjusting the flow.
Control of the heating/cooling production normal takes
place according to the floating regulation principle, i.e.
the temperature level needed for cooling/heating at a
specific outdoor temperature is produced with the help
of collected values from the outside and flow sensors.
As an option, room sensors can also be used to com-
pensate for deviations in room temperature.
Floating regulation
PLEASE NOTE!
This system solution means that the
heat transfer fluid will also circulate
through the heating system. Check
that all component parts are designed
for the heat transfer fluid in question.
Control (also with accessories)
FIGHTER 1310 HPAC
For the Installer
12
Channel selection
Hold the Channel button down for about 7 seconds to
access the following menus.
By pressing the Channel button again you can browse
through the display settings below to find the informa-
tion you want.
If a value is programmable, this is denoted by a [P]
(Programmable) in front of the value.
If the next value cannot be set, pressing the Channel
button displays the next menu.
Setting/Control
The first step when changing a value is to press the
Increase button once. A cursor (line) then appears
under the value. The value can then be increased or
reduced using the Increase or Reduce buttons.
The electric output is controlled by the control comput-
er for optimum comfort. This calculates the deficit/sur-
plus on the flow temperature in the form of degree
minutes.
If, for example, the flow temperature has been 2
degrees lower than the calculated flow temperature for
10 minutes; 2 x 10 = 20 degree minutes is registered
by the computer. With the standard setting the number
of degree minutes should amount to -60 before the
compressor starts. The degree minutes will continue
to increase until the actual flow temperature is higher
than the set value. After that the accumulated degree
minutes will start to decrease and when zero is
reached the compressor will stop.
General
Degree minutes
30
010 20 30 min
40
31
32
34
Framledningstemperatur
Tid
50 60 70 1009080
33
35
°C
(börvärde)
= ärvärde
-80
min
-60
-40
0
Gradminuter
Tid
-20
+20
-20
-50
-90
-120
-140 -150 -150 -140
-120
-90
= gradminuter
27
28
29
-100
0
110 140130120
-140
-120
-160
-180
-200
-50
-0
-40
-70
10 20 30 40 50 60 70 1009080 110 140130120
Kompressor till
från
+60
+40
+80
37
36
38
Time
On
Off
Actuel value
Degree minutes
Degree minutes
Compressor
Set value
Flow temperature
Time
Control (also with accessories) 13
For the Installer
FIGHTER 1310 HPAC
Gm [P]Actual value for number of degree-minutes.
This value can be changed to speed up the start
of heating production.
Setting range: +100/-350.
10
Settings on the display
HP-°min A
[P]Actual value for number of degree-minutes.
Start value for compressor A.
Setting range: +100/-350.
Default setting is 60.
Deficit before HP module A may start.
HP-°min B
[P]Actual value for number of degree-minutes.
Start value for compressor B.
Setting range 5 - 250
Default setting is 200.
Deficit before HP module B is allowed to start.
10b
HP-°min A
[P]Actual value for number of degree-minutes.
Start value for compressor A.
Setting range: +100/-350.
Deficit before HP module A may start.
HP-stop B
[P]Stop value for compressor B.
Setting range 5 - 250.
Default setting is 150.
Surplus before HP module B may start.
10c
WW diff HP
[P]Greatest temperature deviation from nominal
value for heating medium (WW) before forced
control of the two heat pump modules A and B
starts.
Setting range: 3 25.
Default setting is 13.
Diff AC
Temperature deviation before forced control of
active cooling.
Setting range 1 - 9
Default setting is 4.
11
GM 0
HP-°min A 60
HP-°min B 200
HP-°min A 60
HP-stop B 150
WW diff HP 13°C
Diff AC 4°C
Control (also with accessories)
FIGHTER 1310 HPAC
For the Installer
14
Relay 68: Start contactor, HP.
Relay 69: Operating contac-
tor, A.
Relay K3: Operating contac-
tor, B.
Relay xx: Reversing valve.
Relay VB: Circ. pumps VB
Relay L: Not active
Relay PC:Passive cooling
Relay AC: Active cooling
Relay KB: Circ. pump KB
Man Manual test of outputs.
Change Man 0 to Man 1 orMan 2to test different
functions.
Man 0 must be set before you can exit the menu.
15
Settings on the display
DriftP
Shows status of operating pressure switches.
1= closed
0= a pressure switch contact is open (automatic
return)
HP/MS
Shows status of high-pressure pressure switch-
es/motor protection.
1= closed
0= a pressure switch contact is open (automatic
return)
Gives a permanent alarm.
Manual resetting of the motor protection.
LP Shows the status of the low-pressure pressure
switch
1= closed
0= a pressure switch contact is open (automatic
return)
Gives a permanent alarm.
13
Cal. Out
[P]Calibration of outside sensors.
Room
[P]Calibration of room sensor.
Brine In
[P] Calibration of heat transfer fluid flow.
Brine Out
[P]Calibration of heat transfer fluid return.
Setting values for all quantities: -5 +5.
14
HP int
[P]Min interval in minutes between heat pump
starts.
Setting range: 20 60.
Default setting is 60.
12
HP-int 20m
DriftP 1
HP/MS 1 LP 1
Cal.Out 0Room 0
BrinIn 0BrinO 0
Man: 0
Man: 1 68 0 69 0
K3 0 xx 0
Man: 2 VB 0 L 0
PC 1 AC 0 KB 0
Control (also with accessories) 15
For the Installer
FIGHTER 1310 HPAC
PLEASE NOTE!
Enter the chosen settings in the table
on page 2 of this manual. The details
are important for
service work.
HP-no.
[P]Sequence number of FIGHTER 1310 where
more than one unit is connected together; see
table. HP-no. is set to 0 if only one heat pump is
installed.
Default setting is 0.
HW-choice *
[P]Choice of number of compressors to be run-
ning for hot water production (requires connected
hot water sensor). For one compressor running,
choose 1 (module B). For both compressors run-
ning, choose 2 (modules A+B).
Default setting is 1.
17
Servicetime
Change from 0 to 1 to speed up the time
sequences by a factor of 60 for servicing.
Returns to normal setting eight minutes after the
last button was pressed.
Parallel
Setting of Increase/Reduce heat potentiometer
to displace heating curve (parallel offset).
16
Settings on the display
* Only shown if the accessory hot water control is
installed .
Cooling
[P]Cooling allowed or not allowed.
On or Off can be selected.
Default setting is On.
18
To return to menu 1 9, press the Channel button. You
will then access menu 1, after that the Channels but-
ton should be pressed for approximately 7 seconds to
return to the service position, menu 10 18.
Example: Two FIGHTER 1310 HPAC connected
together.
For the first heat pump (sequence number 1), com-
pressor A starts at -60 degree-minutes and com-
pressor B starts at -200 degree-minutes. For the
second heat pump (sequence number 2), com-
pressor A starts at -120 degree-minutes and com-
pressor B starts at -260 degree-minutes.
HP-no. Degree minutes Degree minutes
compressor A compressor B
1 -60 -200
3 -180 -320
5 -300 -440
7 -420 -560
9 -540 -680
0 -60 -200
2 -120 -260
4 -240 -380
6 -360 -500
8 -480 -620
10 -600 -740
Servicetime 0
Parallel 6
HP-nr 0
HW-val 1
Cooling on
The length of the collector hose varies depending on
the rock /ground conditions and on the distribution
system.
When installing the collector hose ensure it rises con-
stantly towards the heat pump to avoid air pockets. If
this is not possible, install high points to vent the air.
The distribution system should be fitted with two pres-
sure expansion
vessels. The heat transfer fluid
side
should be pressurised to at least 0.5 bar.
All the systems pipes are to be condensation insulated
except the pipes to the hot water heater.
If the temperature of the heat transfer system can fall
below 0 °C this must be protected against freezing
through the mixture of propylene glycol (NOTE! Not
ethanol). The mixing ratio should be approximately 25
% propylene glycol and the remainder water. As a
guideline for the volume calculation, use 1 litre of ready
mixed heat transfer fluid per metre of collector hose,
(for 40 x 2.4 PN 6.3 PEM hose).
The installation should be marked with the antifreeze
used.
Shut-off valves should be installed as close to the heat
pump as possible. Fit a particle filter to the incoming
pipe.
When connecting to an open ground water system,
due to the dirt and risk for freezing in the evaporator,
an intermediate frost protection circuit must be
installed. This requires an additional heat exchanger.
Pipe connections16
Pipe installation must be carried out in accordance
with current norms and directives. FIGHTER 1310
HPAC can only work up to a return temperature of
around 50°C and a flow temperature from the heat
pump of around 60°C. FIGHTER 1310 HPAC is not
equipped with shut-off valves so you have to install
them yourself outside the heat pump to facilitate future
service.
The fluid in the buildings distribution system is the
same as in the ground/rock collector.
FIGHTER 1310 HPAC
For the Installer
General
FIGHTER 1310 is connected to the HPAC and possi-
ble hot water heating
Pipe connections are made at the rear of the FIGHT-
ER 1310. Pipe connections are made at the bottom
and top of HPAC. The necessary safety equipment,
shutoff valves (fitted as close as possible to the heat
pump), and the particle filter and flexible hoses sup-
plied must be fitted.
When connecting to a system with thermostats on all
convectors, a relief valve must be fitted, or a number
of the thermostats must be removed to ensure suffi-
cient flow.
Pipe connection, the buildings
distribution system
Pipe connection, collector side
Condensation insulation
To avoid condensation, all pipes and other cold sur-
faces must be isolated with diffusion-proofed material.
Where the cooling demand is high, fan coil units with a
drip dish and drain connection are needed.
PLEASE NOTE!
This system solution means that the
heat transfer fluid will also circulate
through the heating system. Check
that all component parts are designed
for the heat transfer fluid in question.
Pipe connections 17
FIGHTER 1310 HPAC
For the Installer
Outline diagram
For outline diagrams the necessary safety equipment
must be fitted in accordance with current regulations.
Bathroom radiator Fan coil units
Rock/Ground collector
Pipe connections
FIGHTER 1310 HPAC
For the Installer
18
00
mvpkPa
500 1000 1500
0l/h
2000
2
4
8
20
80
40
Tryck
Flöde
2500 3000 3500 500045004000
60 6
FIGHTER 1310-20
100 10
00
mvpkPa
500 1000 1500
0l/h
2000
2
4
8
20
80
40
Tryck
2500 3000 3500 500045004000
60 6
FIGHTER 1310-25/30
Flöde
100 10
Pump capacity diagram, the buildings distribution system
Heat transfer fluid capacity diagram, collector side
Available pressure setup
A 60 Hz mains supply does not permit the heating medium pump to run at the highest capacity (upper curve in the
diagrams). A frequency
converter is needed to utilise the pumps entire capacity in a 60 Hz mains network.
00
mvpkPa
600 1200 1800
0l/h
2400
5
10
20
50
200
100
Tryck
Flöde
3000 3600 4200 4800
150 15
FIGHTER 1310-20
250 25
01200 1800 2400 l/h
3000
Tryck
3600 4200 4800 720060005400
FIGHTER 1310-25/30
Flöde
0
mvpkPa
0
5
10
20
50
200
100
150 15
250 25
Pressure drop
Flow
Flow
Flow
Flow
Pressure drop
Pressure drop
Pressure drop
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Nibe FIGHTER1310 HPAC Installation And Maintenance Instructions Manual

Category
Heat pumps
Type
Installation And Maintenance Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI