Nibe FIGHTER 2010 Series Installation And Maintenance Instructions Manual

Category
Heat pumps
Type
Installation And Maintenance Instructions Manual
R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGHTER 2010
MOS GB 0609-5 611864
FIGHTER 2010
LEK
For the Installer
Contents 1
FIGHTER 2010
For Home Owners
Miscellaneous
General information for the installer
Transport and storage ............................................ 5
Inspection of the installation .................................. 5
Erecting the heat pump .......................................... 5
Control .................................................................... 5
Pipe connections
General .................................................................. 6
Pipe connection (heating medium) ........................ 6
Water volumes ...................................................... 6
Sensor placement .................................................. 6
Pressure drop, heating medium side .................... 7
Docking
General .................................................................. 8
FIGHTER 2010 docked with SMO 10 ......................8
Several FIGHTER 2010s docked with SMO 10 ......9
FIGHTER 2010 docked with VVM 240 ..................10
FIGHTER 2010 docked with EVC 13 ....................11
FIGHTER 2010 docked to an electric/oil boiler......12
Electrical connections
Electrical installation ..............................................13
Connection .......................................................... 13
Circulation pump .................................................. 14
Thermostat hot water .......................................... 14
Single step thermostat heating (auto mode) ........ 15
Double step thermostat heating ............................15
Additional heating/downtime ................................ 16
Example of additional heating connection ............ 16
External indication of common alarms ................ 16
Outside sensor .................................................... 16
Commissioning and adjusting
Preparations ..........................................................17
Filling and venting the heating medium system .. 17
Balance temperature ............................................ 17
Stop temperature ................................................ 17
Soft-start relay ...................................................... 17
Compressor heater .............................................. 17
Starting and checking .......................................... 18
Adjustment, charge flow ...................................... 18
Readjustment, heating medium side .................... 18
Control
Explanation .......................................................... 19
Channel description ............................................ 20
Sensors
Sensor placement ................................................ 22
Temperature sensor data .................................... 22
Data for hot gas sensor ........................................ 22
Electrical circuit diagram
Electrical circuit diagram ...................................... 23
Component positions
Component positions .......................................... 24
List of components
List of components .............................................. 25
Sound pressure levels
Sound pressure levels .......................................... 26
Dimensions
Dimensions and setting-out coordinates .............. 27
Technical specifications
Technical specifications ...................................... 28
Enclosed kit
Enclosed kit .......................................................... 29
General
Concise product description ................................ 2
Setting table ........................................................ 2
System description
Principle of operation .......................................... 3
Maintenance routines
Maintenance of FIGHTER 2010 .......................... 4
Accessories
Accessories .......................................................... 30
Dealing with malfunctions
FIGHTER 2010 not in operation ........................ 31
Draining, heat medium side ................................ 31
Channel Factory setting
06 Start defrosting ............. -3 °C
07 Stop defrosting ............. +10 °C
09 Max. defrosting ............. 7 min
10 Min. interval
between defrosting ............. 50 min
13 Select thermostat ............. 0 (auto mode)
14 Power step, heating ............. +7 °C
15 Power step, HW ............. +7 °C
16 Start drip tray heater ............. +2 °C
17 Balance temperature ............. +5 °C
18 Stop temperature ............. -7 °C
19 Start interval compressor ............. 20 min
28
Time delay supplement relay
............. 120 min
30 Max return temperature ............. 45 °C
31
Connection diff. return temp.
............. 2 °C
General
FIGHTER 2010
For Home Owners
2
In order to get the ultimate benefit from your heat pump FIGHTER 2010 you should read through
the For Home Owners section in this Installation and Maintenance Instruction.
FIGHTER 2010 is a base heat pump for heating small houses, apartment blocks and small industrial
premises. Outdoor air is used as a heat source.
FIGHTER 2010 is a Swedish made quality product offering a long life span and safe operation.
Installation date
Type designation
FIGHTER 2010- __ kW
Installation engineers
Settings
Date __________ Signed __________________________________
The serial number (103) should always be stated in all
correspondence with NIBE.
089
___________
To be filled in when the heat pump has been
installed.
FIGHTER 2010 is an outdoor air heat pump, specially
designed for the Nordic climate. FIGHTER 2010 utilis-
es the outside air so there is no need for bore holes or
collectors in the ground. FIGHTER 2010 has an auto-
matic 2-step capacity regulator for the fan and com-
pressor.
The unique two-step control provides a very high ener-
gy coverage and great savings.
FIGHTER 2010 is designed for water based heating
systems and can be used together with most electric
boilers, oil-fired boilers or equivalent. The heat pump
includes an advanced control system for optimal con-
trol. FIGHTER 2010 is started by a start signal from
another controller or thermostat.
FIGHTER 2010 can also be controlled by a specially
designed controller, SMO 10*. This connects addition-
al heat and controls switching between room heating
and hot water heating.
In addition, FIGHTER 2010 can be docked to a
specially adapted hot water module, VVM 240*. This
contains a similar controller as SMO 10 and consists
of a water heater and additional heat in the form of an
electric boiler. FIGHTER 2010 and VVM 240 together
make up a complete heating plant.
With help of its unique 2-stage compressor, FIGHTER
2010 can heat hot water effectively at high outdoor
temperatures and provide a high output to the heating
system at low outdoor temperatures. This results in
much higher annual heat factors/savings for the heat
pump plant compared to traditional compressor tech-
nology.
If the outdoor temperature drops to a level under the
stop temperature all heating must then occur with
external additional heat.
FIGHTER 2010 is manufactured in two sizes 6 and 8.
Materials have been chosen to provide a long life and
to fully withstand the outdoor conditions that prevail in
the Nordic countries.
System description 3
For Home Owners
FIGHTER 2010
Principle of operation
The heating medium side and the hot water side must
be fitted with the necessary safety equipment in accor-
dance with the applicable regulations.
* accessories for FIGHTER 2010-6 and -8
95
FIGHTER 2010
VVM 240
AV
AV
SÄK
SF
RC
TV
FG
RG
UG
Maintenance routines
For Home Owners
4
FIGHTER 2010
FIGHTER 2010 is equipped with control and monitor-
ing equipment, however some exterior maintenance is
still necessary.
Make regular checks throughout the year that the inlet
grille is not clogged by leaves, snow or anything else.
In addition, you should ensure during the colder parts
of the year that too much frost or ice does not form
under FIGHTER 2010. Strong wind in connection with
extensive snowfall can cause the inlet and exhaust air
grilles to become clogged. Make sure that there is no
snow on the grilles.
If necessary the outer casing can be cleaned using a
damp cloth. Care must be exercised so that the plastic
cover is not scratched when cleaning. Avoid spraying
water into the grilles or on the sides so that water can
penetrate into FIGHTER 2010.
Maintenance of FIGHTER 2010
WARNING!
Rotating fan blades
General information for the installer 5
FIGHTER 2010
Current regulations require the heating installation to
be inspected before it is commissioned. The inspec-
tion must be carried out by a suitably qualified person
and should be documented. The above applies to
closed heating systems. If the heat pump is replaced,
the installation must be inspected again.
FIGHTER 2010 is placed outdoors on a firm base,
preferably a concrete foundation. FIGHTER 2010
should not be positioned next to sensitive walls, for
example, next to a bedroom. Also ensure that the
placement does not inconvenience the neighbours.
Large amounts of condensation water as well as melt
water from defrosting can be produced. Provide good
drainage at the installation area and make sure water
cannot run out onto paths or the like during periods
when ice can form. Ideally condensation water is led
off to a street inlet or the like.
The distance between FIGHTER 2010 and the house
wall should be at least 350 mm. Clearance in front of
FIGHTER 2010 should be at least one metre.
FIGHTER 2010 should not be placed so that recircula-
tion of outdoor air can occur, since this causes lower
output and efficiency.
FIGHTER 2010 should be transported and stored ver-
tically.
Transport and storage
Installation
Inspection of the installation
FIGHTER 2010 is equipped with an internal electronic
controller that handles all functions necessary for heat
pump operations.
Accordingly, defrosting, stop at max/min temperature,
connection of the compressor heater as well as
enabling the heater for the drip pan, monitoring of
motor protection and pressure switches are controlled.
In addition, the number of starts for respective capaci-
ties and the running time for respective capacities can
be read off.
The integrated controller is set during installation and
can be used during a service.
Under normal operation conditions the home owner
does not need to have access to the controller.
FIGHTER 2010 has an integrated electronic return
sensor that limits the return temperature. The flow and
return sensors are fitted during installation.
FIGHTER 2010 can also be switched on/off via sig-
nals from other control equipment or a thermostat. If
FIGHTER 2010 is to be controlled using the acces-
sories SMO 10 or VVM 240 then relevant procedures
are described in respective instructions.
SMO 10 and VVM 240 communicate with FIGHTER
2010, which means that the settings and measure-
ment values from FIGHTER 2010 can be adjusted
and read on SMO 10 and VVM 240.
Control
For the Installer
350 mm
400 mm
1000 mm
Fritt utrymme bakom
Fritt utrymme framför
Fritt utrymme
Min. avstånd
vid användning
av flera F 2010
Free distance behind
Free distance in front
Free distance
Min. distance
when using
several F2010
Pipe connections
FIGHTER 2010
For the Installer
6
Pipe installation must be carried out in accordance
with current norms and directives. FIGHTER 2005
works up to an outgoing temperature from the heat
pump of approximately 55 °C. See section “Commis-
sioning and adjusting” – “Adjustment, charge flow” for
the right flow setting. Since FIGHTER 2010 is not
equipped with shutoff valves on the water side these
must be fitted to facilitate future service. The return
temperature is limited by the return sensor and is
adjustable on channel 30.
General
FIGHTER 2010 is supplied with flow and return sen-
sors, sensors and cables are packed in the distribution
box. The edge board connector is fitted at the factory.
Flow sensor (89), yellow cable.
Return sensor (93), blue cable.
The flow and return sensors are routed through the
cable gland (102) to the measurement points.
The flow and return sensors are fitted on the
straight section of the copper pipe using cable ties
together with heating pipe paste and aluminium
tape.
NOTE! It is important that the contact between the
sensor and measurement point is good and that
the sensors are insulated.
Sensor placement
FIGHTER 2010 can be connected to the heating sys-
tem see the section “Docking” or according to one of
the system solutions that can be downloaded from the
website www.nibe.se/vvs .
The heat pump must be vented by the upper connec-
tion (70, WW-out) using the venting nipple on the
enclosed flexible hose. The supplied particle filter is
installed before the inlet, that is to say, the lower con-
nection (71, WW-in) on FIGHTER 2010. All outdoor
pipes are to be thermally insulated with at least
19 mm thick pipe insulation.
The circulation pump should be operational, even
if FIGHTER 2010 is not running, to prevent dam-
age due to freezing. The circulation pump can also
be controlled directly from FIGHTER 2010, terminal
(11), which takes the outdoor temperature into consid-
eration. Alternatively, the heat pump is connected to
an intermediate circuit with a heat exchanger, pump
and water with anti-freeze. Shutoff and drain valves
are fitted so that FIGHTER 2010 can be emptied in
the event of prolonged power failures.
The supplied flexible hoses act as vibration dampers.
The flexible hoses are fitted so a slight bend is creat-
ed, thus acting as vibration damping.
Pipe connections
(heating medium)
AV
AV
SÄK
SF
TV
FG
RG
LEK
E
NOTE!
The pipe work must be flushed before
the heat pump is connected, so that
any contaminants do not damage the
component parts.
When docking with FIGHTER 2010, a total water vol-
ume, incl. boiler, radiators, pipes, etc. of at least 15 –
20 litres boiler water per kW output on the heat pump
is recommended.
Water volumes
Pipe connections 7
For the Installer
FIGHTER 2010
Pressure drop, heating medium side
FIGHTER 2010-6
FIGHTER 2005-8, 10
FIGHTER 2010-8
Flöde
kPa
Tryckfall
kPa
Tryckfall
l/s
Flöde
l/s
0
0,5
1
1,5
2
2,5
3
3,5
4
0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45
0
0,5
1
1,5
2
2,5
3
3,5
4
0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45
Pressure drop
Pressure drop
Flow
Flow
FIGHTER 2010-6
FIGHTER 2010-8
Docking
FIGHTER 2010
For the Installer
8
FIGHTER 2010 can be installed in several different
ways. The safety equipment must be installed in
accordance with current regulations for all docking
options. See www.nibe.se/vvs for more docking
options.
When docking with FIGHTER 2010, a total water vol-
ume, incl. boiler, radiators, pipes, etc. of at least 15–20
litres boiler water per kW output on the heat pump is
recommended.
General
FIGHTER 2010 docked to the oil-fired/pellet boiler together with
SMO 10 and water heater (floating condensing)
VXV1
PG
SMO 10
HR
HR
HR
HR
P
VP
FG1 CP1
RG1 RG2
SV1
SV2
CP2 FG2
VVC
VVG
LP1
UG
RG
FG AV
SÄV
TV RV SF
SÄV
SMO 10 controls FIGHTER 2010, oil-fired boiler, circu-
lation pumps, shunts, etc. FIGHTER 2010 works with
floating condensing against the heating system and
prioritizes hot water charging via the reversing valve
(VXV1). FIGHTER 2010 works in stage 1 or stage 2
depending on the outdoor air temperature and the
heating requirement.
If FIGHTER 2010 cannot meet the heating require-
ment, the oil-fired boiler is started and additional heat-
ing is shunted in.
The above diagram is equipped with accessories.
Docking 9
For the Installer
FIGHTER 2010
Several FIGHTER 2010s together with
SMO 10 and water heater (floating condensing)
SMO 10 controls up to nine FIGHTER 2010s (of which
max one for hot water), electric element, circulation
pump, shunt, etc. FIGHTER 2010 works with floating
condensing against the heating system and prioritizes
hot water charging via the reversing valve VXV1.
FIGHTER 2010 works in stage 1 or stage 2 depending
on the outdoor air temperature and the heating
requirement.
FIGHTER 2010 HP1 heats the hot water. If FIGHTER
2010 cannot meet the heating requirement, additional
heating is shunted in from the oil-fired boiler. When
additional heat is engaged, hot water is heated using
the immersion heater in the hot water heater.
FIGHTER 2010 HP1 is connected in at position (44a)
using the enclosed modular cable (15m) from SMO
10. HP2 is connected in to HP1 using the shielded
3-core cable on the screw terminal (44b).
The above diagram is equipped with accessories.
HP 2
HP 1
Docking
FIGHTER 2010
For the Installer
10
FIGHTER 2010 docked with VVM 240 (floating condensing)
95
FIGHTER 2010
VVM 240
AV
AV
SÄK
SF
RC
TV
FG
RG
UG
FIGHTER 2010 6 and 8 can be connected to VVM
240. FIGHTER 2010 is controlled by VVM 240.
FIGHTER 2010 works with floating condensing aga-
inst the heating system and prioritizes hot water
charging in VVM 240. FIGHTER 2010 works in stage
1 or stage 2 depending on the outdoor air temperature
and the heating requirement.
If FIGHTER 2010 cannot meet the heating require-
ment, additional heating is shunted in from VVM 240.
When the outside temperature drops below the set
stop temperature, VVM 240 engages and takes over
the heating.
Docking 11
For the Installer
FIGHTER 2010
FIGHTER 2010
EVC 13
AV
RV SF
SÄV
TV
FG
RG
RT 10
FIGHTER 2010 docked with EVC 13 (floating condensing)
FIGHTER 2010 is controlled by a room thermostat and
works with floating condensing against the return from the
heating system. FIGHTER 2010 works in stage 1 or stage
2 depending on the outdoor air temperature. If FIGHTER
2010 can not provide the heating requirement additional
heat is connected using the existing control equipment
from EVC 13.
Additional heat can be blocked above the set outdoor tem-
perature by means of the automatic control system in
FIGHTER 2010. The heating medium also circulates
through FIGHTER 2010 during the set stop temperature.
Hot water production only takes place using the existing
hot water heater.
The right curve is chosen on EVC 13 so that FIGHTER
2010 is not disturbed.
The accessory RT 10 is required for this option.
Docking
FIGHTER 2010
For the Installer
12
Abbreviations
AV Shutoff valve
CP Circulation pump
FG Temperature sensor, supply line Included with FIGHTER 2010
HR Auxiliary relay
LP Charge pump
RG Return temperature sensor Included with FIGHTER 2010
RV Control valve
RT 10 Room thermostat
SF Particle filter Included with FIGHTER 2010
SV Shunt valve
SÄV Safety valve
TV Drain valve
UG Outside sensor
VVG Hot water sensor
FIGHTER 2010 docked to an electric/oil boiler
(floating condensing)
FIGHTER 2010 is controlled by a room thermostat and
works with floating condensing on the return from the heat-
ing system. FIGHTER 2010 works in stage 1 or stage 2
depending on the outdoor air temperature.
If FIGHTER 2010 cannot meet the heating requirement the
additional heating is shunted in using the existing control
equipment.
Additional heat can be blocked above the set balance tem-
perature by means of the automatic control system in
FIGHTER 2010. Hot water production only takes place using
the existing electric/oil boiler.
The accessory RT 10 is required for this option.
P
FIGHTER 2010
AV
RV SF
SÄV
TV
FG
RG
RT 10
RC
Extern alt
befintlig regler-
utrustning.
Accessory or
existing control
equipment
Electrical connection 13
For the Installer
FIGHTER 2010
R
LEK
9
30
NOTE!
Electrical installation and service must
be carried out under the supervision of
a qualified electrician in accordance
with the stipulations in force.
NOTE!
The live external control must be taken
into consideration when connecting.
The routing of cables for heavy current and signals
should be made out through the cable glands on the
heat pump's left-hand side, seen from the front.
The terminal block (9) for the incoming supply is
accessed by removing the 6 screws on the plastic cover
and the 3 screws (TORX 20) on the electrical
box.
A heat pump must not be connected without the per-
mission of the electricity supplier and must be con-
nected under the supervision of a qualified electri-
cian.
If a miniature circuit breaker is used this should have
a motor characteristic “D” (compressor operation).
For MCB size see Technical Specifications.
The FIGHTER 2010 does not include an isolator
switch on the incoming electrical supply. The instal-
lation must be preceded by a circuit-breaker with at
least a 3 mm breaking gap.
If an insulation test is to be carried out in the buil-
ding, disconnect the heat pump.
Connect the heat pump to the terminal strip (9), 400
V 3-phase, neutral + earth via a distribution board
with fuses.
The signal cable for the thermostats is connected to
terminal (30) on the relay card (29). Cable type:
unscreened LiYY, screened LiYCY. Cable area, at
least 0.22 mm2with cable lengths less than 50 m.
Alternatively the relevant signal cable is connected
from terminal (44) on the control card (34) to SMO10
or VVM 240.
The circulation pump for FIGHTER 2010 is connec-
ted to a separate supply or on terminal block (11).
NOTE! There is a risk of freezing when the circu-
lation pump is connected to the terminal block
(11) and
FIGHTER 2010 is deenergized.
A common alarm can be connected to terminal
(11).
Connection
Electrical installation
9
kommande matning 3x 400 V
L2 L3 N L1
11
Re1
X29
4
X29
5
N
X29
6
29
3 4 1 2 5 6
LEK
29
30
34
11
44
13
9
Circulation pump (accessory)
Common alarm
Incoming electrical supply
Electrical connection
FIGHTER 2010
For the Installer
14
You can use a basic contactor or a thermostat to
switch the compressor on and off for heating hot
water. This function is given priority ahead of the heat-
ing function, which means that irrespective of the sta-
tus of the heating thermostat the compressor will work
according to the settings for hot water production.
This contactor should be of the breaking type (NC)
when the set temperature is reached. The contactor
should be potential free.
Set the preferred outdoor air temperature level on
channel 15 for shifting between compressor stage 1
and compressor stage 2.
Compressor stage 1 is used at high outdoor air tem-
peratures. Compressor stage 2 is used at low outdoor
air temperatures.
Connection of the switch for the hot water function is
made as set out in the picture below.
Hot water thermostat
29
30
1
2
3
4
5
6
7
8
29
30
NOTE!
The following pages about
thermostats, additional heat, common
alarms and downtime, do not apply
when FIGHTER 2010 is controlled by
VVM 240 or SMO 10.
NOTE!
When a thermostat with a bulb is
used, the bulb must be insulated
carefully.
LEK
29
30
34
14
16
11
When the circulation pump is connected to terminal
block (11) the pump is controlled by FIGHTER
2010. Pump activity is dependent on the status of
FIGHTER 2010, heating/hot water requirement and
the outdoor temperature. Pump exercising is hand-
led by FIGHTER 2010.
NOTE! There is a risk of freezing when the cir-
culation pump is connected to the terminal
block (11) and FIGHTER 2010 is deenergized.
Circulation pump
Electrical connection 15
For the Installer
FIGHTER 2010
Double step thermostat
heating
A double step thermostat can also be used to switch
the compressor on and off. This thermostat should be
of the breaking type (NC) when the set temperature
has been reached. The contactor should be potential
free. The thermostat should have an adjustable differ-
ence.
If you choose to use a double step thermostat then
option “1” on channel 13 should be selected, see sec-
tion “Control Channel description”.
In this position channel 14 has no function.
The function for compressor operation will be as fol-
lows:
When the thermostat’s step 1 and step 2 are broken
both the compressor’s stages will be inactive.
When the thermostat’s step 1 is closed and the
thermostat's step 2 is broken the compressor’s
stage 1 will be active.
When the thermostat’s step 1 and step 2 are closed
the compressor’s stage 2 will be active.
Connection of the double step thermostat is made as
set out in the picture below.
29
30
steg 2
steg 1
1
2
3
4
5
6
7
8
29
30
Single step thermostat heating
(auto mode)
You can use a basic thermostat to switch the com-
pressor on and off. This thermostat should be of the
breaking type (NC) when the set temperature has
been reached. The contactor should be potential free.
Single step thermostat VT 10 or room thermostat RT
10 are available as accessories. When an external
thermostat is not used, terminal block 30, pos 6
and 7 should be strapped.
If you choose to use a single step thermostat then
option “0” on channel 13 should be selected, see sec-
tion “Control Channel description”.
Set the preferred outdoor air temperature level on
channel 14 for shifting between compressor stage 1
and compressor stage 2.
Compressor stage 1 is used at high outdoor air tem-
peratures. Compressor stage 2 is used at low outdoor
air temperatures.
Connection of the single step thermostat is made as
set out in the picture below.
30
29
1
2
3
4
5
6
7
8
29
30
Step 2
Step 1
Electrical connection
FIGHTER 2010
16
For the Installer
Example of additional heating
connection
Additional heating/downtime
FIGHTER 2010 is equipped with a potential free con-
tactor intended for additional heat: Max 250V, 2A.
The setting of the outdoor air temperature (balance
temperature) when the additional heating relay is acti-
vated is made on channel 17, see the section “Control
Channel description”.
External additional heat: connected via additional
heating relay terminal (14). Conditions for connecting
additional heat:
The outdoor air temperature should be lower than
the set balance temperature (channel 17).
The compressor should have been operational in
stage 2 during at least the period selected in chan-
nel 28. Defrosting is included in this time.
If the outdoor air temperature drops down to a level
under the set value, stop temperature (downtime), in
channel 18 compressor operations are blocked and all
heating must take place using the external additional
heat via the downtime relay terminal (16). This func-
tion is also activated when FIGHTER 2010 is deener-
gized.
The connection to the additional heating relay is made
as set out in the picture below.
34
16
14
NO O/C NO O/C
Tillsats Stillestånd
NC NC
16
14
34
NO O/C
NC
Hjälpkontaktor
(ingår ej vid leverans)
12 – 230V
Max load across the relay contactors is 250V, 2A.
During operations without the need of the additional
heating or downtime the relay contactors are closed
between NO and O/C.
Additional heating and downtime are acquired
between NC and O/C. The contactors are drawn in the
deenergized state.
Additional heating and downtime relays are activated
during normal operating conditions for FIGHTER
2010. Both relays are deactivated in the event of oper-
ating disruptions.
Basic circuit diagram for connection of auxiliary relays
for additional heating and downtime.
11
Re1
X29
4
X29
5
N
X29
6
29
3 4 1 2 5 6
Position 2, 230 V output
signal with a common alarm.
Position 3, 230 V output
signal with no alarm.
FIGHTER 2010 is equipped with a contactor for exter-
nal indication of common alarms. The function be-
comes active with all types of alarms. Max load on the
relay contact is 250V, 2A.
The connection for external indication of common
alarms is made as set out in the picture below:
An outdoor sensor (15) is positioned on the underside
of FIGHTER 2010. If the FIGHTER 2010 faces south
or to the west, where there is a risk of intensive heat-
ing by the sun, the outdoor sensor should be posi-
tioned on a north or north-west facing wall.
External indication of common
alarms
Outside sensor
Additional heating “Downtime”
Auxiliary relay
(not included)
Commissioning and adjusting 17
FIGHTER 2010
For the Installer
The heating medium system is filled with water to the
required pressure. Vent the system using the venting
nipple on the enclosed flexible hose and possibly the
circulation pump.
Before commissioning check that the heating circuit is
filled and well vented. Check the pipe system for
leaks.
Filling and venting the
heating medium system
Preparations
NOTE!
The compressor must not be forced to
start with periods shorter than 1 start
per 15 minutes.
NOTE!
The compressor heater must have
been switched on for 6-8 hours before
the FIRST start, see the section “Start-
up and inspection”
Fighter 2010 is equipped with a soft-starter relay (97)
that limits the inrush current on the compressor to max
24 A.
The compressor must not be forced to start with peri-
ods shorter than 1 start per 15 minutes.
The balance temperature is the outdoor temperature
when the heat pump’s stated output is equal to the
building’s output requirement. This means that the
heat pump covers the whole building’s output require-
ment down to this temperature. Setting of the balance
temperature, additional heating, is made on channel
17.
When using a standard radiator system and with hot
water heating the stop temperature should not fall
below -7 °C. The setting of the stop temperature,
downtime, is done on channel 18.
Venting nipple
Balance temperature
Stop temperature
FIGHTER 2010 is equipped with a compressor heater
that heats the compressor before start-up and when
the compressor is cold. The compressor must have
been switched on for 6-8 hours before the FIRST
start, see the section “Start-up and inspection”
Compressor heater
Soft-start relay
Commissioning and adjusting
FIGHTER 2010
18
For the Installer
Modular cable (44) or thermostat/strap, terminal
(30) is disconnected.
The working switch is turned on.
Check that all incoming phases are energized.
Check that the miniature circuit-breaker (2) is on.
The compressor heater (25) must have been oper-
ational for at least 6 hours before the compressor
start can be initiated. This is done by switching on
the control voltage and disconnecting the modular
cable or thermostat/strap.
The display on the control card (34) shows C0/CC
F0 H1/H3 depending on the outdoor temperature.
When the thermostat or the like calls for
heating/hot water and FIGHTER 2010 is blocked
from starting by e.g. time conditions, C_ will flash
until starting is permitted. This will also be shown
until the modular cable or thermostat/strap is
connected. During this period the compressor is
heated to increase the service life.
After 6-8 hours the modular cable, external
thermostats or strap on the input for hot water
and/or input for single step or double step ther-
mostat are connected. See the section “Electri-
cal connections” (Thermostat hot water, Single
step thermostat heating, Double step thermostat
heating).
Restart SMO 10 or VVM 240.
FIGHTER 2010 now makes two starts of 5 sec-
onds at 1 minute intervals. This is done so that the
control system can measure the compressor cur-
rents.
This procedure means the heat pump corrects itself
for the incoming phase sequence.
After measuring the compressor currents, the com-
pressor starts after approximately 20 minutes.
Adjust the charge flow according to the diagram,
see the section “Adjustment, charge flow”
Fill in the commissioning report on page 2.
Start-up and inspection
NOTE!
The live external control must be
taken into consideration when
connecting.
Adjusting the temperature difference (T) between the
flow temperature and the return temperature.
This is easily done by using the temperatures mea-
sured in Channel 32 (flow temperature) less Channel
29 (return temperature). This temperature difference
(T) is adjusted with the help of the circulation pump
and control valve. Adjustment is performed with stable
operation about 5 minutes after start, or about 5 min-
utes after defrosting with a cold outdoor temperature.
The temperature difference shall be as in the diagram
below (+1- 2K).
Adjustment, charge flow
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
16,0
-10 -5 0 5 10 15 20
°C
T
6
2
1
3
4
5
1 35° heat medium flow stage 2
2 45° heat medium flow stage 2
3 55° heat medium flow stage 2
4 35° heat medium flow stage 1
5 45° heat medium flow stage 1
6 55° heat medium flow stage 1
Air is initially released from the hot water and venting
may be necessary. If bubbling sounds can be heard
from the heat pump, the circulation pump and radia-
tors, the entire system requires further venting. When
the system has stabilised (correct pressure and all the
air removed) the heating controls can be set at the
required value.
Readjustment,
heat medium side
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Nibe FIGHTER 2010 Series Installation And Maintenance Instructions Manual

Category
Heat pumps
Type
Installation And Maintenance Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI