Nibe F1345 Series Installer Manual

Category
Heat pumps
Type
Installer Manual
Installer manual
LEK
NIBE™ F1345
Ground source heat pump
IHB GB 1251-2
231282
Table of Contents
1 Important information 2
Safety information 2
2 Delivery and handling 6
Transport 6
Assembly 7
Supplied components 7
Removing the covers 7
3 The heat pump design 8
General 8
Electrical cabinets 10
Cooling section 11
4 Pipe connections 13
General 13
Dimensions and pipe connections 14
Brine side 15
Heating medium side 17
Hot water heater 17
Docking alternatives 18
5 Electrical connections 21
General 21
Connections 22
Optional connections 24
Connecting accessories 29
6 Commissioning and adjusting 30
Preparations 30
Filling and venting 30
Start guide 31
Post adjustment and venting 32
7 Accessories 37
8 Technical data 39
Dimensions and setting-out coordinates 39
Technical specifications 40
Wiring diagram, 3x400V 24 kW 43
Wiring diagram, 3x400V 30 kW 53
Wiring diagram, 3x400V 40 and 60 kW 63
Item register 73
1Table of Contents |NIBE F1345
Safety information
This manual describes installation and service procedures
for implementation by specialists.
This appliance is designed for use in a home environment
and not intended to be used by persons (including chil-
dren) with reduced physical, sensory or mental capabilit-
ies, or lack of experience and knowledge, unless they
have been given supervision or instruction concerning
use of the appliance by a person responsible for their
safety. This in accordance to applicable parts of the low-
voltage directive 2006/95/EC, LVD. The appliance is also
intended for use by experts or trained users in shops,
hotels, light industry, on farms and in similar environ-
ments. This in accordance to applicable parts of the ma-
chinery directive 2006/42/EC.
Children should be supervised to ensure that they do not
play with the appliance.
This is an original instruction manual. Translation is not
allowed without approval from NIBE.
Rights to make any design or technical modifications are
reserved.
©NIBE 2012.
Symbols
NOTE
This symbol indicates danger to machine or
person.
Caution
This symbol indicates important information
about what you should observe when maintain-
ing your installation.
TIP
This symbol indicates tips on how to facilitate
using the product.
Marking
F1345 is CE marked and fulfils IP21.
The CE marking means that NIBE ensures that the product
meets all regulations that are placed on it based on relev-
ant EU directives. The CE mark is obligatory for most
products sold in the EU, regardless where they are made.
IP21 means that the product can be touched by hand,
that objects with a diameter larger than or equivalent to
12.5 mm cannot penetrate and cause damage and that
the product is protected against vertically falling drops.
Safety precautions
Caution
Install the system in full accordance with this installation
manual.
Incorrect installation can cause bursts, personal injury, water leaks,
refrigerant leaks, electric shocks and fire.
Observe the measurement values before working on the
cooling system, especially when installing in small rooms, so
that the limit for the refrigerant's density is not exceeded.
Consult an expert to interpret the measurement values. If the refri-
gerant density exceeds the limit, lack of oxygen can occur in the
event of any leak, which can cause serious accidents.
Use original accessories and the stated components for the
installation.
If parts other than those stated by us are used, water leaks, electric
shocks, fire and personal injury may occur as the unit may not work
properly.
Ventilate the working area well – refrigerant leakage may
occur during service work.
If the refrigerant comes into contact with naked flames, poisonous
gas is created.
Install the unit in a location with good support.
Unsuitable installation locations can cause the unit to fall and cause
material damage and personal injury. Installation without sufficient
support can also cause vibrations and noise.
Ensure that the unit is stable when installed, so that it can
withstand earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause
material damage and personal injury.
The electrical installation must be carried out by a qualified
electrician and the system must be connected as a separate
circuit.
Power supply with insufficient capacity and incorrect function can
cause electric shocks and fire.
Use the stated cables for the electrical connection, tighten
the cables securely in the terminal blocks and relieve the
wiring correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause abnormal heat
production or fire.
Check, after completed installation or service, that no refriger-
ant leaks from the system in gas form.
If refrigerant gas leaks into the house and comes into contact with
an aerotemp, an oven or other hot surface, poisonous gases are
produced.
Use types of pipe and tools stated for this type of refrigerant.
Using existing parts for other refrigerants can cause breakdowns
and serious accidents due to process circuit bursts.
Switch off the compressor before opening/breaching the re-
frigerant circuit.
If the refrigerant circuit is breached /opened whilst the compressor
is running, air can enter the process circuit. This can cause unusually
high pressure in the process circuit, which can cause bursts and
personal injury.
Switch off the power supply in the event of a service or in-
spection.
If the power supply is not shut off, there is a risk of electric shocks
and damage due to the rotating fan.
Do not run the unit with removed panels or protection.
Touching rotating equipment, hot surfaces or high voltage parts
can cause personal injury due to entrapment, burns or electric
shocks.
Cut the power before starting electrical work.
Failure to cut the power can cause electric shocks, damage and in-
correct function of the equipment.
Care
Carry out the electrical installation with care.
Do not connect the ground lead to the gas line, water line, lightning
conductor or telephone line's ground lead. Incorrect grounding can
cause unit faults such as electric shocks due to short-circuiting.
NIBE™ F1345Chapter 1 | Important information2
1 Important information
Use main switch with sufficient breaking capacity.
If the switch does not have sufficient breaking capacity, malfunctions
and fire can occur.
Always use a fuse with the correct rating in the locations
where fuses are to be used.
Connecting the unit with copper wire or other metal thread can
cause unit breakdown and fire.
Cables must be routed so that they are not damaged by
metal edges or trapped by panels.
Incorrect installation can cause electric shocks, heat generation and
fire.
Do not install the unit in close proximity to locations where
leakage of combustible gases can occur.
If leaking gases collect around the unit, fire may occur.
Do not install the unit where corrosive gas (for example ni-
trous fumes) or combustible gas or steam (for example thinner
and petroleum gases) can build up or collect, or where
volatile combustible substances are handled.
Corrosive gas can cause corrosion to the heat exchanger, breaks in
plastic parts etc. and combustible gas or steam can cause fire.
Do not use the unit for specialist purposes such as for storing
food, cooling precision instruments, freeze-conservation of
animals, plants or art.
This can damage the items.
Do not install and use the system close to equipment that
generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby sets, medical high frequency
equipment and telecommunications equipment can affect the unit
and cause malfunctions and breakdowns. The unit can also affect
medical equipment and telecommunications equipment, so that it
functions incorrectly or not at all.
Take care when carrying the unit by hand.
If the unit weights more than 20 kg, it must be carried by two
people. Use gloves to minimize the risk of cuts.
Dispose of any packaging material correctly.
Any remaining packaging material can cause personal injury as it
may contain nails and wood.
Do not touch any buttons with wet hands.
This can cause electric shocks.
Do not touch any refrigerant pipes with your hands when
the system is in operation.
During operation the pipes become extremely hot or extremely cold,
depending on the method of operation. This can cause burn injuries
or frost injuries.
Do not shut off the power supply immediately after operation
has start.
Wait at least 5 minutes, otherwise there is a risk of water leakage
or breakdown.
Do not control the system with the main switch.
This can cause fire or water leakage. In addition, the fan can start
unexpectedly, which can cause personal injury.
Especially for units intended for R410A
- Only use R410A refrigerant. R410A means that the pressure is
about 1.6 times as high as conventional refrigerants.
- The filling connections on units with R410A are different sizes, to
prevent the system being filled with the incorrect refrigerant by
mistake.
- Do not use charging bottles. These types of bottles change the
composition of the refrigerant, which makes the performance of
the system worse.
- When filling refrigerant, the refrigerant must always leave the
bottle in liquid form.
Serial number
The serial number can be found at the bottom right of
the front cover and in the info menu (menu 3.1).
6HULDO QXPEHU
Caution
Always give the product's serial number (14 di-
gits) when reporting a fault.
Country specific information
Installer manual
This installer manual must be left with the customer.
3Chapter 1 | Important informationNIBE™ F1345
Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be
carried out by a suitably qualified person. Fill in the page for information about installation data in the Operating manual.
DateSignatureNotesDescription
Brine (page 15)
Non-return valves
System flushed
System vented
Antifreeze
Level/Expansion vessel
Particle filter
Safety valve
Shut off valves
Circulation pumps set
Heating medium (page 17)
Non-return valves
System flushed
System vented
Expansion vessel
Particle filter
Safety valve
Shut off valves
Circulation pumps set
Electricity (page 21)
Fuses heat pump
Fuses property
Outside sensor
Room sensor
Current sensor
Safety breaker
Earth circuit-breaker
Relay output for emergency mode
NIBE™ F1345Chapter 1 | Important information4
Contact information
KNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT
Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44
NIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 FlurlingenCH
Tel: (52) 647 00 30 Fax: (52) 647 00 31
Druzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ
Tel: +420 326 373 801 Fax: +420 326 373 803
NIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE
Tel: 05141/7546-0 Fax: 05141/7546-99
Vølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK
Tel: 97 17 20 33 Fax: 97 17 29 33
NIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI
Puh: 09-274 697 0 Fax: 09-274 697 40
AIT France, 10 rue des Moines, 67000 HaguenauFR
Tel : 03 88 06 24 10 Fax : 03 88 06 90 15
NIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB
Tel: 0845 095 1200 Fax: 0845 095 1201
NIBE Energietechniek B.V., Postbus 2, NL-4797 ZG WILLEMSTAD (NB)NL
Tel: 0168 477722 Fax: 0168 476998
ABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO
Tel. sentralbord: +47 23 17 05 20
NIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL
Tel: 085 662 84 90 Fax: 085 662 84 14
© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU
Tel./fax +7 831 419 57 06
NIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE
Tel: +46-(0)433-73 000 Fax: +46-(0)433-73 190
For countries not mention in this list, please contact Nibe Sweden or check for more information.
5Chapter 1 | Important informationNIBE™ F1345
Transport
F1345 should be transported and stored vertically in a
dry place. When being moved into a building, the heat
pump may be tilted back 45 °. NOTE! The heat pump is
top heavy.
If the cooling modules are pulled out and transported
upright, F1345 can be transported on its back.
NOTE
Ensure that the heat pump cannot fall over
during transport.
TIP
The side panels can be removed for easier install-
ation in the building.
R
0
R
0
Lift from the street to the set up location
If the base allows, the simplest thing is to use a pallet
truck to move the F1345 to the set up location.
NOTE
The centre of gravity is offset to one side (see
print on the packaging).
LEK
1
2
If F1345 needs to be transported across soft ground, such
as a lawn, we recommend that a crane is used that can
lift the unit to the installation location. When F1345 is
raised using a crane, distribute the load according to the
instructions on the packaging.
If a crane cannot be used F1345 can be transported on
a sack truck. F1345 must be taken from its heaviest side
(see printed material on packaging for where the centre
of gravity is) and two people are required to lift F1345.
Lift from the pallet to final positioning
Before lifting, remove the packaging and the load anchor
to the pallet as well as front and side panels.
Before lifting, the heat pump must be separated by
pulling the cooling modules out from the cabinet. See
the service chapter in the operating manual for instruc-
tions about the separation.
Carry the heat pump by the upper cooling module's slide
rails, use gloves.
NOTE
The heat pump must not be moved when only
the lower cooling module has been pulled out.
If the heat pump is not secured in position the
upper cooling module must always be removed
before the lower one can be pulled out.
Scrapping
For scrapping, remove the product in reverse order.
NIBE™ F1345Chapter 2 | Delivery and handling6
2 Delivery and handling
Assembly
Position F1345 on a firm base that can take the weight,
preferably on a concrete floor or foundation. Use the
product's adjustable feet to obtain a horizontal and
stable set-up.
30 - 50 mm
The area where F1345 is located must be equipped
with floor drainage.
Install with its back to an outside wall, ideally in a room
where noise does not matter, in order to eliminate
noise problems. If this is not possible, avoid placing it
against a wall behind a bedroom or other room where
noise may be a problem.
Wherever the unit is located, walls to sound sensitive
rooms should be fitted with sound insulation.
Route pipes so they are not fixed to an internal wall
that backs on to a bedroom or living room.
Installation area
Leave a space of 800 mm in front of the product. Approx
50 mm free space is required in order to open the side
hatches. The hatches do not need to be opened during
service, all service on F1345 can be carried out from the
front. Leave space between the heat pump and wall be-
hind (and any routing of supply cables and pipes) to re-
duce the risk reproduction of any vibration.
(50) (50)

* A normal installation needs 300 - 400 mm (any side) for connec-
tion equipment, i.e. level vessel, valves and electrical equipment.
Supplied components
See separate list of supplied components.
Location
The kit of supplied items is placed in packaging on top
of the heat pump.
Removing the covers
Front cover
1
2
LEK
LEK
1. Remove the screws from the lower edge of the front
cover.
2. Lift the cover out at the bottom edge and up.
Side covers
LEK
LEK
LEK
The side covers can be removed to facilitate the installa-
tion.
1. Remove the screws from the upper and lower edges.
2. Twist the cover slightly outward.
3. Move the cover backwards and slightly to the side.
4. Pull the cover to one side.
5. Pull the cover forwards.
7Chapter 2 | Delivery and handlingNIBE™ F1345
General
LEK
)& ; ; ; ; ;
;
$$
6)
$$;-
$$;-
;-
;-
;-
;-
;-
;-
;-
;-
;-
;-
(3
(3
8%
8%
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
8% 8% 8%
(33)
(33)
3)
3)
LEK
; 8% .
$$
$$
$$
;
.
$$
;-
;-
)&
. ..
NIBE™ F1345Chapter 3 | The heat pump design8
3 The heat pump design
Pipe connections
Connection, heating medium flowXL 1
Connection, heating medium returnXL 2
Connection, brine inXL 6
Connection, brine outXL 7
HVAC components
Cooling moduleEP 14
Cooling moduleEP 15
Sensors etc.
Outside sensorBT 1
Electrical components
Base cardAA 2
Input circuit boardAA 3
Display unitAA 4
AA4-XJ3 USB outlet (no function)
AA4-XJ4 Service outlet (No function)
Extra relay circuit boardAA 7
Base card 2AA 26
Miniature circuit-breakerFC 1
Emergency mode relayK1
Relay, external circulation pump (only 40 and
60 kW)
K2
Relay, external circulation pump (only 40 and
60 kW)
K3
Relay, external circulation pump (only 40 and
60 kW)
K4
Relay (only 24 and 30 kW)K5
Terminal block, incoming electrical supplyX1
Terminal block, non-return valve, external brine
pump (only 40 and 60 kW) and external operating
voltage (at tariff control)
X2
Terminal block, step controlled additional heatX3
Terminal block, emergency mode relayX4
Terminal block, common alarmX5
Terminal block, communication, sensors and soft-
ware controlled inputs
X6
Terminal block, control signal external brine pump
(only 40 and 60 kW)
X7
Terminal blockX8
Connector, electrical supply to compressor, cooling
module EP14
XJ 1
Connector, electrical supply to compressor, cooling
module EP15
XJ 2
Connector, cooling module EP14XJ 3
Connector, brine pump, cooling module EP14 (only
24 and 30 kW)
XJ 4
Connector, heating medium pump, cooling module
EP14
XJ 5
Connector, cooling module EP15XJ 6
Connector, brine pump, cooling module EP15 (only
24 and 30 kW)
XJ 7
Connector, heating medium pump, cooling module
EP15
XJ 8
Connector, cooling module EP15XJ 9
Connector, cooling module EP14XJ 10
SwitchSF 1
Miscellaneous
Rating platePF 1
Type plate, cooling sectionPF 2
Serial number platePF 3
Cable gland, incoming electricityUB 1
Cable gland, powerUB 2
Cable gland, signalUB 3
Designations in component locations according to
standard IEC 81346-1 and 81346-2.
9Chapter 3 | The heat pump designNIBE™ F1345
Electrical cabinets
F1345 24 kW, 3x400 V
LEK
)& $$
F1345 30 kW, 3x400 V
LEK
4$ 4$
)& $$
F1345 40 and 60 kW, 3x400 V
LEK
4$ 4$
)& $$
Electrical components
Soft-start cardAA 10
Motor cut-outFC 2
Contactor, compressorQA 10
Contactor, compressorQA 11
Designations in component locations according to
standard IEC 81346-1 and 81346-2.
NIBE™ F1345Chapter 3 | The heat pump design10
Cooling section
F1345 24 and 30 kW, 3x400 V
LEK
$$
%7
%7
40
%7
*3
*3
%7
40
;
F1345 40 and 60 kW, 3x400 V
LEK
$$
%7
%7
%7
*3
%7
40
;
40
LEK
)  N: [9
(3
%7
%7
(3
%3
%7
%3
*4
+6
;/
41
(% ;/
%3
LEK
)  N: [9
(3
%7
%3
(3
%3
%7
%3
*4
+6
;/
41
(% ;/
%7
%7
LEK
)  N: [9
(3
%7
+6
(3
%7
*4
;/
%3
%3
;/
41
(%
%7
%3
%7
LEK
)  N: [9
(3
%7
%3
(3
%7
*4
;/
%3
+6
;/
41
(%
%7
%3
%7
11Chapter 3 | The heat pump designNIBE™ F1345
Pipe connections
Service connection, high pressureXL 20
Service connection, low pressureXL 21
HVAC components
Circulation pumpGP 1
Brine pumpGP 2
Drainage, climate systemQM 1
Draining, brine sideQM 2
Sensors etc.
High pressure pressostatBP 1
Low pressure pressostatBP 2
Sensor, low pressureBP 8
Temperature sensors, heating medium returnBT 3
Temperature sensor, brine inBT 10
Temperature sensor, brine outBT 11
Temperature sensor, condenser supply lineBT 12
Temperature sensor, hot gasBT 14
Temperature sensor, fluid pipeBT 15
Temperature sensor, suction gasBT 17
Temperature sensor, compressorBT 29
Electrical components
Joint cardAA 100
Compressor heaterEB 10
Joint connector, compressor and motor moduleX 401
Cooling components
EvaporatorEP 1
CondenserEP 2
CompressorGQ 10
Drying filterHS 1
Expansion valveQN 1
Designations in component locations according to
standard IEC 81346-1 and 81346-2.
NIBE™ F1345Chapter 3 | The heat pump design12
General
Pipe installation must be carried out in accordance with
current norms and directives. F1345 can operate with a
return temperature of up to 58 °C and an outgoing
temperature from the heat pump of 65 °C.
F1345 is not equipped with internal shut off valves; these
must be installed to facilitate any future servicing.
NOTE
The pipe system needs to be flushed out before
the heat pump is connected so that debris can-
not damage component parts.
NOTE
Do not solder directly on the heat pump pipes,
because of internal sensors.
Compression ring coupling alternatively pressure
connection should be used.
Symbol key
MeaningSymbol
Venting valve
Shut-off valve
Non-return valve
Shunt / shuttle valve
Safety valve
Temperature sensor
Expansion vessel
Pressure gauge
P
Circulation pump
Particle filter
Auxiliary relay
Compressor
Heat exchanger
System diagram
F1345 consists of two heat pump modules, circulation
pumps and control system with possibility of additional
heat. F1345 is connected to the brine and heating medi-
um circuits.
In the heat pump evaporator, the brine (water mixed with
anti-freeze, glycol or ethanol) releases its energy to the
refrigerant, which is vaporised in order to be compressed
in the compressor. The refrigerant, of which the temper-
ature has now been raised, is passed to the condenser
where it gives off its energy to the heating medium circuit
and, if necessary, to any docked water heater. If there is
a greater need for heating/hot water than the com-
pressors can provide it is possible is to connect an external
immersion heater.
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3
(3
Cooling moduleEP 14
Cooling moduleEP 15
Connection, heating medium flowXL 1
Connection, heating medium returnXL 2
Connection, brine inXL 6
Connection, brine outXL 7
13Chapter 4 | Pipe connectionsNIBE™ F1345
4 Pipe connections
Dimensions and pipe connec-
tions
1775
600
560
25-50
735
1555
1715
80 145 145 145
450
820
Pipe dimensions
Connection
G2"
(XL1) Heating medium supply, external
thread
G2"(XL2) Heating medium return, external
thread
G2"(XL6) Brine in, external thread
G2"(XL7) Brine out, external thread
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
(3;/
NIBE™ F1345Chapter 4 | Pipe connections14
Brine side
Collector
Rock heat, recom-
mended active
drilling depth (m)
Surface soil heat,
recommended col-
lector length (m)
Type
2x180-3x1803x350-4x40024 kW
3x150-5x1503x450-4x45030 kW
4x170-5x2004x500-6x50040 kW
6x150-8x1806x450-8x45060 kW
Applies to PEM hose 40x2.4 PN 6.3.
These are rough example values. At installation the correct
calculations must be made according to local conditions.
Caution
The length of the collector hose varies depend-
ing on the rock/soil conditions, climate zone and
on the climate system (radiators or underfloor
heating).
Max length per coil for the collector should not exceed
500 m.
The collectors must always be connected in parallel with
the possibility of adjusting the flow for the relevant coil.
For surface soil heat, the hose should be buried at a depth
determined by local conditions and the distance between
the hoses should be at least 1 metre.
For several bore holes, the distance between the holes
must be determined according to local conditions.
Ensure the collector hose rises constantly towards the
heat pump to avoid air pockets. If this is not possible,
airvents should be used.
As the temperature of brine system can fall below 0 °C
it must be protected against freezing down to -15 °C. 1
litre of ready mixed brine per meter of collector hose
(applies when using PEM-hose 40x 2.4 PN 6.3) is used as
a guide value when making the volume calculation.
Caution
Because the temperature of the brine system
varies depending on the heat source, the menu
5.1.7 "br pmp al set." must be set to the suit-
able value.
Connecting the brine side
The pipe connections are on the rear of the heat pump.
Insulate all indoor brine pipes against condensation.
NOTE
Condensation may drip from the expansion
vessel. Position the vessel so that this does not
harm other equipment.
Caution
When necessary you should install venting valves
in the brine system.
Mark the brine system with the antifreeze that is used.
Install the supplied safety valve at the expansion vessel
as illustrated in the outline diagram. The entire length
of the overflow water pipe from the safety valves must
be inclined to prevent water pockets and must also be
frost-free.
Install shut off valves as close to the heat pump as
possible so that the flow to individual cooling modules
can be shut off. Extra safety valves between the particle
filter and shut off valves (according the outline diagram)
are required.
Fit the supplied particle filter on the incoming pipe.
Fit the supplied non-return valves on the outgoing pipe.
In the case of connection to an open groundwater system,
an intermediate frost-protected circuit must be provided,
because of the risk of dirt and freezing in the evaporator.
This requires an extra heat exchanger.
P
15Chapter 4 | Pipe connectionsNIBE™ F1345
Connecting external brine pump (40 and
60kW only)
Install the brine pump (GP16) according to the circulation
pump manual for connection of incoming brine (EP14-
XL6) and (EP15-XL6) between the heat pump and shut
off valve (see image).
In some countries the brine pump is not supplied, see list
of supplied items.
(3
(3
*3
NOTE
Insulate the brine pump against condensation
(do not cover the drainage hole).
Expansion vessel
The brine circuit must be supplied with a pressure expan-
sion vessel.
The brine side must be pressurised to at least 0.05 MPa
(0.5 bar).
The pressure expansion vessel should be dimensioned as
set out in the following diagram, to prevent operating
disturbances. The diagrams cover the temperature range
from 10 °C to +20 °C at a pre-pressure of 0.05 MPa (0.5
bar) and the safety valve's opening pressure of 0.3 MPa
(3.0 bar).
Ethanol 28% (volume percent)
In installations with ethanol (28% volume percent) as the
brine the pressure expansion vessel must be dimensioned
according to the following diagram.
30
0
40
50
60
0
10
20
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
9ROXPH SUHVVXUH H[SDQVLRQ YHVVHO O
7RWDO YROXPH UHIULJHUDQW LQ V\VWHP O
Ethylene glycol 40% (volume percent)
In installations with ethylene glycol (40% volume percent)
as the brine the pressure expansion vessel must be dimen-
sioned according to the following diagram.
0 200 400 600 800 1000 1200 1400 1600 1800 2000
0
10
20
30
40
50
60
70
80
90
100
9ROXPH SUHVVXUH H[SDQVLRQ YHVVHO O
7RWDO YROXPH UHIULJHUDQW LQ V\VWHP O
NIBE™ F1345Chapter 4 | Pipe connections16
Heating medium side
Connecting the climate system
A climate system is a system that regulates indoor comfort
with the help of the control system in F1345 and for ex-
ample radiators, underfloor heating/cooling, fan con-
vectors etc.
The pipe connections are on the rear of the heat pump.
Install the necessary safety equipment and shut off
valves (installed as close to the heat pump as possible
so that the flow to individual cooling modules can be
shut off).
Fit the supplied particle filter on the incoming pipe.
The safety valve must have a maximum 0.6 MPa (6.0
bar) opening pressure and be installed on the heating
medium return. The entire length of the overflow water
pipe from the safety valves must be inclined to prevent
water pockets and must also be frost-free.
When connecting to a system with thermostats on all
radiators, a relief valve must be fitted, or some of the
thermostats must be removed to ensure sufficient flow.
Fit the supplied non-return valves on the outgoing pipe.
Caution
When necessary you should install venting valves
in the climate system.
Caution
The heat pump is designed so that heating pro-
duction can occur with one or two cooling
modules. This however entails different pipe or
electrical installations.
Hot water heater
Connecting the hot water heater
Any docked hot water heater must be fitted with ne-
cessary set of valves.
The mixing valve must be installed if the setting is
changed so that the temperature can exceed 60 °C.
The setting for hot water is made in menu 5.1.1.
The safety valve must have a maximum opening pres-
sure in accordance with the water heater manual and
be installed on the incoming domestic water line. The
entire length of the overflow water pipe from the safety
valves must be inclined to prevent water pockets and
must also be frost-free.
Caution
Hot water production is activated in menu 5.2
or in the start guide.
Caution
The heat pump/system is designed so that hot
water production can occur with one or several
cooling modules. This however entails different
pipe or electrical installations.
Fixed condensing
If F1345 is to work with fixed condensing you must con-
nect an external flow sensor (BT25) according to the de-
scription on page 23. In addition, you must do the follow-
ing menu settings.
Menu setting (local vari-
ations may be required)
Menu
Desired temperature in the
tank.
1.9.3 - min. flow line temp.
Desired temperature in the
tank.
5.1.2 - max flow line temper-
ature
intermittent5.1.10 - op. mod heat med
pump
manual4.2 - op. mode
17Chapter 4 | Pipe connectionsNIBE™ F1345
Docking alternatives
F1345 can be connected in several different ways, some
of which are shown below.
Further option information is available at
and in the respective assembly instructions for the ac-
cessories used. See page 37 for a list of the accessories
that can be used with F1345.
Explanation
Pool systemCL11
Accessory cardAA5
Temperature sensor, poolBT51
Exchanger, poolEP5
Circulation pump, poolGP9
Particle filter, poolHQ41
Three way valve, poolQN19
Trim valveRN42
External additional heatEB1
Expansion vessel, closedCM5
External electrical additional heatEB1
Safety valve, heating medium sideFL10
Shut-off valve, heating medium sideQM42 - QM43
Trim valveRN11
Heat pump system (Master)EB100
Temperature sensor, outdoorBT1
Temperature sensor, hot water chargingBT6
Temperature sensor, heating medium flow,
External
BT25
Temperature sensor, heating medium return,
External
BT71
Heat pump, F1345EB100
Cooling module AEP14
Cooling module BEP15
Safety valve, collector sideFL11 - FL12
Safety valve, heating medium sideFL13 - FL14
Particle filterHQ12 - HQ15
Shut-off valve, brine sideQM50 - QM53
Shut-off valve, heating medium sideQM54 - QM57
Reversing valve, heating/hot waterQN10
Non-return valveRM10 - RM13
Heat pump system (Slave 1)EB101
Heat pump, F1345EB101
Cooling module AEP14
Cooling module BEP15
Safety valve, collector sideFL11 - FL12
Safety valve, heating medium sideFL13 - FL14
Particle filterHQ12 - HQ15
Shut-off valve, brine sideQM50 - QM53
Shut-off valve, heating medium sideQM54 - QM57
Non-return valveRM10 - RM13
External additional heatEM1
Accessory cardAA5
Temperature sensor, boilerBT52
Expansion vessel, closedCM5
Gas boilerEM1
Safety valve, heating medium sideFL10
Auxiliary relay, external additional heatKA1
Mixing valve, additionQN11
Climate system 2EP21
Accessory cardAA5
Temperature sensors, heating medium flow
BT2
Temperature sensors, heating medium returnBT3
Circulation pumpGP20
Shunt valveQN25
Miscel-
laneous
Accessory cardAA5
Manometer, brine sideBP6
Temperature sensor, hot water flowBT70
Accumulator tank with hot water coilCP10, CP11
Expansion vessel, closed, heating medium
side
CM1
Expansion vessel, closed, brine sideCM3
Immersion heaterEB2
Hot water heaterEB10
Collector, brine sideEP12
Safety valve, heating medium sideFL2
Safety valve, brineFL3
Mixer valve, hot waterFQ1
Circulation pump, heating medium externalGP10
Circulation pump, domestic hot water circu-
lation
GP11
Auxiliary relay, immersion heaterKA1
Filler valve, heating medium sideQM11
Venting valve, heating medium sideQM20
Venting valve, brine sideQM21
Shut off valve, brine flowQM33
Shut off valve, brine returnQM34
Non-return valveRM42 - RM43
Trim valveRN41, RN60 -
RN63
Connection boxXD1
Connection, filling brineXL27 - XL28
Designations according to standards 81346-1 and 81346-
2.
NIBE™ F1345Chapter 4 | Pipe connections18
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80