Rheem RGEDZR090ACB20BAAAA0 Installation guide

Category
Split-system air conditioners
Type
Installation guide
92-106166-01-04
SUPERSEDES 92-106166-01-03
ST-A1273-32-00
INSTALLATION INSTRUCTIONS
FOR PACKAGE GAS ELECTRIC UNITS
RGED SERIES 7.5, 8.5, 10.0 & 12.5 TON [26.4, 29.9, 35.2 & 44.0 KW]
60 HZ MODELS
Featuring New Industry
Standard R-410A
ISO 9001:2015
I. SPECIFICATIONS
A. GENERAL
The Combination Gas Heating/Electric
Cooling Rooftop is available in 150,000,
205,000 and 225,000 BTUH heating input.
Cooling capacity is 7.5, 8.5, 10, 12.5
nominal tons. Units are convertible from
bottom supply and return to side supply and
return by relocation of supply and return air
c
over panels. See cover installation detail.
The units are weatherized for mounting
outside of the building.
UNITS ARE NOT DESIGN CERTIFIED TO
BE INSTALLED INSIDE THE
STRUCTURE. DOING SO CAN CAUSE
INADEQUATE UNIT PERFORMANCE AS
WELL AS PROPERTY DAMAGE AND
CARBON MONOXIDE POISONING
RESULTING IN PERSONAL INJURY OR
DEATH.
The information on the rating plate is in
compliance with the FTC and DOE rating
for single phase units. The following
information is for three phase units which
are not covered under the DOE
certification program.
1. The energy consumption of the ignition
system used with this unit is 175 watts.
2. The efficiency rating of this unit is a
product thermal efficiency rating
determined under continuous operating
conditions independent of any installed
system.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed
refrigerating system consisting of a scroll
compressor, condenser coil, evaporator coil
with TXV, a circulation air blower, a
condenser fan, a heat exchanger assembly,
gas burner and control assembly,
combustion air motor and fan, and all
necessary internal electrical wiring. The
cooling system of these units is factory-
evacuated, charged and performance
tested. Refrigerant amount and type are
indicated on rating plate.
C. R-410A REFRIGERANT
All units are factory charged with R-410A
refrigerant.
1. Specifications of R-410A:
Application: R-410A is not a drop-in
replacement for R-22; equipment designs
must accommodate its higher pressures. It
cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is
approximately 60% (1.6 times) greater
than R-22. Recovery and recycle
equipment, pumps, hoses, and the like need
to have design pressure ratings appropriate
for R-410A. Manifold sets need to range up
INTRODUCTION
TABLE OF CONTENTS
!
WARNING
!
WARNING
Page No.
INTRODUCTION 2
Checking Product Received 2
I. SPECIFICATIONS 2
General 2
Major Components 2
R-410A Refrigerant 2
Safety Information 3
Unit Dimensions 4-6
General Data 7-9
Heating Performance 10
Electrical Data 11-21
II. INSTALLATION 22
General 22
Location Considerations 22
Outside Installation 22
Exhaust & Combustion
Air Inlet Hoods 23
Cover Panel Installation 23
Filter Replacement 23
Rooftop Installation 24
Ducting 24
Return Air 25
III. GAS SUPPLY & PIPING 26
Gas Connection 26
LP Conversion 27
Adjusting or Checking
Furnace Input 27
Condensate Drain 28
THE MANUFACTURER’S WARRANTY
DOES NOT COVER ANY DAMAGE OR
DEFECT TO THE AIR CONDITIONER
CAUSED BY THE ATTACHMENT OR
USE OF ANY COMPONENTS,
ACCESSORIES OR DEVICES (OTHER
2
!
NOTICE
BREAK-IN PERIOD
PRIOR TO AGENCY TESTING, RUN THE
COMPRESSOR FOR 16 HOURS AT 115ºF
OUTDOOR AMBIENT TEMPERATURE
AND 80º DRY BULB/75º WET BULB
I
NDOOR AMBIENT TEMPERATURE.
!
NOTICE
EFFICIENCY TESTING NOTICE
FOR PURPOSES OF VERIFYING OR
TESTING EFFICIENCY RATINGS, THE
TEST PROCEDURE IN TITLE 10 PART
431 APPENDIX A TO SUBPART F
(UNIFORM TEST METHOD FOR
MEASURING THE ENERGY
CONSUMPTION OF SMALL, LARGE,
AND VERY LARGE COMMERCIAL
PACKAGE AIR CONDITIONING AND
HEATING EQUIPMENT), AND THE
CLARIFYING PROVISIONS PROVIDED
IN THE AHRI OPERATIONS FOR
UNITARY LARGE EQUIPMENT 340/360,
365 THAT WERE APPLICABLE AT THE
DATE OF MANUFACTURE SHOULD BE
USED FOR TEST SET UP AND
PERFORMANCE.
THAN THOSE AUTHORIZED BY THE
MANUFACTURER) INTO, ONTO OR IN
CONJUNCTION WITH THE AIR
CONDITIONER. YOU SHOULD BE AWARE
THAT THE USE OF UNAUTHORIZED
COMPONENTS, ACCESSORIES OR
DEVICES MAY ADVERSELY AFFECT THE
OPERATION OF THE AIR
CONDITIONER AND MAY ALSO
ENDANGER LIFE AND PROPERTY. THE
MANUFACTURER DISCLAIMS ANY
RESPONSIBILITY FOR SUCH LOSS OR
I
NJURY RESULTING FROM THE USE OF
SUCH UNAUTHORIZED COMPONENTS,
ACCESSORIES OR DEVICES.
This booklet contains the installation and
operating instructions for your combination
gas heating/electric cooling unit. There are
some precautions that should be taken to
derive maximum satisfaction from it.
Improper installation can result in
unsatisfactory operation or dangerous
conditions.
Read this booklet and any instructions
packaged with separate equipment required
to make up the system prior to installation.
Give this booklet to the owner and explain its
provisions. The owner should retain this
booklet for future reference.
CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any
damage from shipment. Claims for damage,
either shipping or concealed, should be filed
immediately with the shipping company.
IMPORTANT: Check the unit model number,
heating size, electrical characteristics, and
accessories to determine if they are correct.
IV. WIRING 29
Power Supply 29
Hook-up 30
Internal Wiring 30
Thermostat 30
V. FURNACE CONTROLS 31
Operating Sequence 31
Operating Instructions 31
Burners 32
Manual Reset 32
Pressure Switch 32
Limit Control 32
VI. COOLING SECTION 32
Cooling Mode 32
Continuous Fan Mode 32
Blower VFD 32
VII. OPERATION INFORMATION 33
Advise Customer 33
Furnace Maintenance 33
Lubrication 33
Cooling Maintenance 33
Replacement Parts 34
Troubleshooting 34
Wiring Diagrams 34
Charging 34
VII. AIRFLOW PERFORMANCE 35-42
VIII. TROUBLESHOOTING 43-45
Alarm Codes 46
IX. CHARGE CHARTS 47-53
X. WIRING DIAGRAMS 54-85
to 800 psig high-side and 250 psig low-
side with a 550 psig low-side retard. Hoses
need to have a service pressure rating of
800 psig. Recovery cylinders need to have
a 400 psig service pressure rating. DOT
4BA400 or DOT BW400.
Combustibility: At pressures above 1
atmosphere, mixture of R-410A and air
can become combustible. R-410A and air
should never be mixed in tanks or
supply lines, or be allowed to
accumulate in storage tanks. Leak
checking should never be done with a
mixture of R-410A and air. Leak checking
can be performed safely with nitrogen or a
mixture of R-410A and nitrogen.
2. Quick Reference Guide For R-410A
R-410A refrigerant operates at
approximately 60% higher pressure (1.6
times) than R-22. Ensure that servicing
equipment is designed to operate with
R-410A.
R-410A refrigerant cylinders are pink.
3
existing evaporator must be replaced
with the factory specified TXV evaporator
specifically designed for R-410A.
4. Tools Required For Installing &
S
ervicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High Side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or
BW400
R-410A SYSTEMS OPERATE AT HIGHER
PRESSURE THAN R-22 SYSTEMS. DO
NOT USE R-22 SERVICE EQUIPMENT OR
COMPONENTS ON R-410A EQUIPMENT.
!
CAUTION
R-410A, as with other HFC’s is only
compatible with POE oils.
Vacuum pumps will not remove moisture
from POE oil.
R-410A systems are to be charged with
liquid refrigerants. Prior to March 1999,
R-410A refrigerant cylinders had a dip
tube. These cylinders should be kept
upright for equipment charging. Post
March 1999 cylinders do not have a dip
tube and should be inverted to ensure
liquid charging of the equipment.
Do not install a suction line filter drier in
the liquid line.
A liquid line filter drier is standard on
every unit.
Desiccant (drying agent) must be
compatible for POE oils and R-410A.
3. Evaporator Coil/ TXV
The thermostatic expansion valve is
specifically designed to operate with R-
410A. DO NOT use an R-22 TXV. The
USE ONLY WITH TYPE OF GAS
APPROVED FOR THIS UNIT.
REFER TO THE UNIT RATING
PLATE.
INSTALL THIS UNIT ONLY IN A
LOCATION AND POSITION AS
SPECIFIED IN THE LOCATION
REQUIREMENTS AND
CONSIDERATIONS SECTION OF
THESE INSTRUCTIONS. PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR TO THE UNIT
SPACE AS SPECIFIED IN THE
VENTING SECTION OF THESE
INSTRUCTIONS.
PROVIDE ADEQUATE
COMBUSTION AND VENTILATION
AIR TO THE UNIT SPACE AS
SPECIFIED IN THE COMBUSTION
AND VENTILATION AIR SECTION
OF THESE INSTRUCTIONS.
COMBUSTION PRODUCTS MUST
BE DISCHARGED OUTDOORS.
CONNECT THE FACTORY
SUPPLIED EXHAUST AND
COMBUSTION AIR INLET HOODS
ONLY, AS SPECIFIED IN THE
EXHAUST AND COMBUSTION AIR
INLET HOODS INSTALLATION
SECTION OF THESE
INSTRUCTIONS.
NEVER TEST FOR GAS LEAKS
WITH AN OPEN FLAME. USE A
COMMERCIALLY AVAILABLE
SOAP SOLUTION MADE
SPECIFICALLY FOR THE
DETECTION OF LEAKS TO CHECK
ALL CONNECTIONS, AS
SPECIFIED IN GAS SUPPLY AND
PIPING SECTION OF THESE
INSTRUCTIONS.
ALWAYS INSTALL UNIT TO
OPERATE WITHIN THE UNIT'S
INTENDED TEMPERATURE-RISE
RANGE WITH A DUCT SYSTEM
WHICH HAS AN EXTERNAL
STATIC PRESSURE WITHIN THE
ALLOWABLE RANGE, AS
SPECIFIED IN DUCTING SECTION
OF THESE INSTRUCTIONS. SEE
ALSO UNIT RATING PLATE.
WHEN A UNIT IS INSTALLED SO
THAT SUPPLY DUCTS CARRY AIR
CIRCULATED BY THE UNIT TO
AREAS OUTSIDE THE SPACE
CONTAINING THE UNIT, THE
RETURN AIR SHALL ALSO BE
HANDLED BY DUCT(S) SEALED
TO THE UNIT CASING AND
TERMINATING OUTSIDE THE
SPACE CONTAINING THE UNIT.
THIS UNIT MAY BE USED TO HEAT
THE BUILDING OR STRUCTURE
DURING CONSTRUCTION IF THE
FOLLOWING INSTALLATION
REQUIREMENTS ARE MET.
INSTALLATION MUST COMPLY
WITH ALL INSTALLATION
INSTRUCTIONS INCLUDING:
PROPER VENT INSTALLATION;
FURNACE OPERATING UNDER
THERMOSTATIC CONTROL;
RETURN AIR DUCT SEALED TO
THE FURNACE;
AIR FILTERS IN PLACE;
SET FURNACE INPUT RATE AND
TEMPERATURE RISE PER
RATING PLATE MARKING;
RETURN AIR TEMPERATURE
MAINTAINED BETWEEN 55°F
(13°C) AND 80°F (27°C); AND
INSTALLATION OF EXHAUST
AND COMBUSTION AIR INLET
HOODS COMPLETED;
CLEAN FURNACE, DUCT WORK
AND COMPONENTS UPON
SUBSTANTIAL COMPLETION OF
THE CONSTRUCTION
PROCESS, AND VERIFY
FURNACE OPERATING
CONDITIONS INCLUDING
IGNITION INPUT RATE,
TEMPERATURE RISE AND
VENTING, ACCORDING TO THE
INSTRUCTIONS.
!
WARNING
!
WARNING
!
WARNING
!
WARNING
!
WARNING
!
WARNING
!
WARNING
!
WARNING
SAFETY INFORMATION
ST-A1273-01_D-00
SERVICE
PORT
DOOR
POWER
ENTRY
RECEPTACLE
29 1/4”
[743 mm]
32 3/4”
[832 mm]
90 1/8”
[2289 mm]
59 1/2”
[1511 mm]
3 3/4”
[97 mm]
FILTER
ACCESS PANEL
INDOOR COIL
ACCESS PANEL
4 1/4”
[110 mm]
FIGURE 2
REAR VIEW
Unit
Dimensions
IMPORTANT: THIS
UNIT MUST BE
MOUNTED LEVEL IN
B
OTH DIRECTIONS
TO ALLOW WATER
TO DRAIN FROM THE
CONDENSER
S
ECTION AND
CONDENSATE PAN.
4
ST-A1273-01_B-00
89”
[2261 mm]
57 7/8”
[1470 mm]
ACCESS PANEL
HEAT EXCHANGER
ACCESS PANEL
BLOWER
ACCESS PANEL COMPRESSOR
CONTROL ACCESS
150 MODEL
60”
[1524 mm]
090 THRU 120
MODELS
50”
[1270 mm]
RETURN COVER
SUPPLY COVER
DRAIN PAN
FLUE
OUTLET
GAS ENTRY
(SIDE SUPPLY)
SERVICE DISCONNECT
KNOCKOUT
7 5/8”
[196 mm]
38 1/8”
[967 mm]
FIGURE 1
FRONT VIEW
5
5 3/8”
[1407 mm]
5
9 1/2”
[
1511 mm]
1
4”
[356 mm]
2
6 3/4”
[
679 mm]
5
9 1/8”
[1507 mm]
6 1/2”
[165 mm]
6
5/8”
[321 mm]
5 1/2”
[140 mm]
2
8 1/2”
[
724 mm]
6
3/8”
[
162 mm]
36 3/8”
[
924 mm]
86 3/4”
[2203 mm]
9
0 1/8”
[2289 mm]
14 3/8”
[
366 mm]
37 1/2”
[
954 mm]
ST-A1273-01_A-00
R
ETURN AIR
S
UPPLY
A
IR
2
[51 mm]
T
YP. (3) SIDES
1 3/8”
[
35 mm]
(VIEW FROM BOTTOM LOOKING UP)
1 3/8”
[
35 mm]
F
IGURE 3
SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS
31 1/4”
[794 mm]
19 7/8”
[505 mm]
21 3/4”
[555 mm]
59 3/8”
[1510 mm]
28 3/8”
[721 mm]
13 7/8”
[353 mm]
1
2 5/8”
[
321 mm]
ST-A1273-17-00
7
1/4”
[184 mm]
6 5/8”
[170 mm]
3 7/8”
[99 mm]
SUPPLY AIR
RETURN
AIR
5 7/8”
[149 mm]
5
1/4”
[
57 mm]
FIGURE 4
SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS
5
ST-A1279-01-00
F
IGURE 5
ROOFCURB INSTALLATION
6
7
GENERAL DATA - GEDZR MODELS
7.5-12.5 TON [26.4 - 44.0 kW]
Model RGEDZR Series ZR090A******A ZR102A******A ZR120A******A
ZR series ZR series ZR series
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
8
8,000 [25.78]
9
9,000 [29.01]
1
18,000 [34.57]
EER/SEER
2
11/NA 11/NA 11/NA
Nominal CFM/AHRI Rated CFM [L/s] 3000/3175 [1416/1498] 3400/3200 [1604/1510] 4000/3480 [1888/1642]
AHRI Net Cooling Capacity Btu [kW] 85,000 [24.9] 96,000 [28.13] 114,000 [33.4]
Net Sensible Capacity Btu [kW] 62,700 [18.37] 68,300 [20.01] 80,600 [23.62]
Net Latent Capacity Btu [kW] 22,300 [6.53] 27,700 [8.12] 33,400 [9.79]
IEER
3
12.7 12.7 12.7
Net System Power kW 7.53 8.51 9.86
Compressor
No./Type
1
/Scroll
1
/Scroll
1
/Scroll
No. Stages 1 1 1
Outdoor Sound Rating (dB)
5
8
8
8
8
8
8
Outdoor Coil - Fin Type Louvered Louvered Louvered
Tube Type MicroChannel MicroChannel MicroChannel
MicroChannel Depth in. [mm] 0.71 [18] 0.81 [20.6] 1 [25.4]
Face Area sq. ft. [sq. m] 25.4 [2.36] 25.6 [2.38] 25.6 [2.38]
Rows / FPI [FPcm] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9]
Indoor Coil - Fin Type Louvered Louvered Louvered
Tube Type MicroChannel MicroChannel MicroChannel
MicroChannel Depth in. [mm] 1 [25.4] 1.26 [32] 1.26 [32]
Face Area sq. ft. [sq. m] 11 [1.02] 10.9 [1.01] 10.9 [1.01]
Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8]
Refrigerant Control TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05]
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8500 [4011]
No. Motors/HP 2 at 1/5 HP 2 at 1/5 HP 2 at 1/3 HP
Motor RPM 820 820 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type Belt (Adjustable) Belt (Adjustable) Belt (Adjustable)
No. Speeds Single Single Single
No. Motors 1 1 1
Motor RPM 1725 1725 1725
Motor Frame Size 56 56 56
Filter - Type Disposable Disposable Disposable
Furnished Yes Yes Yes
(NO.) Size Recommended in. [mm x mm x mm] (4)2x20x20 [51x508x508] (4)2x20x20 [51x508x508] (4)2x20x20 [51x508x508]
Refrigerant Charge Oz. [g] 100 [2835] 117 [3317] 136 [3856]
Weights
Net Weight lbs. [kg] 839 [381] 868 [394] 896 [406]
Ship Weight lbs. [kg] 878 [398] 907 [411] 935 [424]
GENERAL DATA - GEDZS MODELS
7.5-12.5 TON [26.4 - 44.0 kW]
8
1
3
5
GENERAL DATA - GEDZT MODELS
7.5-12.5 TON [26.4 - 44.0 kW]
9
1
3
5
HEATING PERFORMANCE - GED MODELS
7.5-12.5 TON [26.4 - 44.0 kW]
10
-
1
5-45 [8.3-25]
5-35 [2.8-19.4] /
35-65 [19.4-36.1]
15-45 [8.3-25] /
35-65 [19.4-36.1]
1
5-45 [8.3-25] /
15-45 [8.3-25]
5-35 [2.8-19.4] /
20-50 [11.1-27.8]
1
0-40 [5.6-22.2] /
2
5-55 [13.9-30.6]
10-40 [5.6-22.2] /
1
43,500 / 205,000
[42.06/60.08]
157,500 / 225,000
[46.16/64.94]
157,500 / 225,000
[46.16/64.94]
157,500 / 225,000
[46.16/64.94]
1
16,200 / 166,000
[34.07/48.66]
127,500 / 182,250
[
37.39/53.41]
127,500 / 182,250
[37.39/53.41]
127,500 / 182,250
[37.39/53.41]
85,050 / 121,500
[24.92/35.6]
Unit Operating Voltage Range
187-253 187-253 414-506 414-506 517-633 517-633
Volts
208/230 208/230 460 460 575 575
Phase
3 3 3 3 3 3
Hz
60 60 60 60 60 60
M
inimum Circuit Ampacity
4
1
4
3
2
1
2
3
1
6
1
7
Minimum Overcurrent Protection Device
S
ize
50 50 25 30 20 20
Maximum Overcurrent Protection Device
Size
60 60 30 35 25 25
No. 1 1 1 1 1 1
Volts 208/230 208/230 460 460 575 575
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
HP, Compressor 1 7 7 7 7 7 7
Amps (RLA), Comp. 1 25 25 12.8 12.8 9.6 9.6
Amps (LRA), Comp. 1 164 164 164 164 78 78
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 460 460 575 575
Phase 1 1 1 1 1 1
HP 1/5 1/5 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 0.8 0.8 0.6 0.6
Amps (LRA, each) 2.3 2.3 1.4 1.4 1.1 1.1
No. 1 1 1 1 1 1
Volts 208/230 208/230 460 460 575 575
Phase 3 3 3 3 3 3
HP 2 3 2 3 2 2
Amps (FLA, each) 6.6 9.1 3.3 4.6 2.5 3.5
Amps (LRA, each) 47 74.5 22.5 38.1 19 20
Evaporator Fan
Unit Information
Compressor Motor
Condenser Motor
E
LECTRICAL DATA - -GEDZR SERIES
090ACB15
090ACC15
0
90ACC20
090ACB20
090ACA15
0
90ACA20
090ADA15
0
90ADA20
090ADB15
090ADB20
0
90ADC15
090ADC20
090AYA15
0
90AYA20
090AYB15
090AYB20
0
90AYC15
090AYC20
ELECTRICAL DATA - GEDZR MODELS
11
ELECTRICAL DATA - GEDZR MODELS
12
U
nit Operating Voltage Range
1
87-253
1
87-253
4
14-506
4
14-506
4
14-506
5
17-633
5
17-633
Volts
208/230 208/230 460 460 460 575 575
P
hase
3 3 3 3 3 3 3
Hz
60 60 60 60 60 60 60
M
inimum Circuit Ampacity
4
4
4
6
2
2
2
3
2
4
1
6
1
7
M
inimum Overcurrent Protection Device
Size
60 60 25 30 30 20 20
M
aximum Overcurrent Protection Device
S
ize
7
0
7
0
3
0
3
5
3
5
2
5
2
5
No. 1 1 1 1 1 1 1
V
olts
2
08/230
2
08/230
4
60
4
60
4
60
5
75
5
75
Phase 3 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
3
450
HP, Compressor 1 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2 7 1/2
Amps (RLA), Comp. 1 27.6 27.6 12.8 12.8 12.8 9.6 9.6
Amps (LRA), Comp. 1 191 191 100 100 100 78 78
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2 2
Volts 208/230 208/230 460 460 460 575 575
Phase 1 1 1 1 1 1 1
HP 1/5 1/5 1/5 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 0.8 0.8 0.8 0.6 0.6
Amps (LRA, each) 2.3 2.3 1.4 1.4 1.4 1.1 1.1
No. 1 1 1 1 1 1 1
Volts 208/230 208/230 460 460 460 575 575
Phase 3 3 3 3 3 3 3
HP 2 3 2 3 3 2 3
Amps (FLA, each) 7.1 9.1 3.5 4.6 6 2.5 3.5
Amps (LRA, each) 45 74.5 22.5 38.1 38.1 19 20
102ADA15
102ADA22
102ADB15
102ADB22
102ADC15
102ADC22
Condenser Motor
Evaporator Fan
Unit Information
1
02AYB15
102AYB22
102AYC15
1
02AYC22
102AYA15
102AYA22
Compressor Motor
ELECTRICAL DATA - -GEDZR SERIES
102ACA15
102ACA22
1
02ACB15
102ACB22
102ACC15
1
02ACC22
ELECTRICAL DATA - GEDZR MODELS
13
Unit Operating Voltage Range
187-253 187-253 187-253 414-506 414-506 414-506 517-633 517-633
V
olts
2
08/230
2
08/230
2
08/230
4
60
4
60
4
60
5
75
5
75
Phase
3 3 3 3 3 3 3 3
H
z
6
0
6
0
6
0
6
0
6
0
6
0
6
0
6
0
Minimum Circuit Ampacity
48 51 53 26 27 28 19 20
Minimum Overcurrent Protection Device
S
ize
6
0
6
0
6
0
3
0
3
0
3
5
2
5
2
5
Maximum Overcurrent Protection Device
Size
70 70 80 35 40 40 25 30
N
o.
1 1 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460 575 575
Phase 3 3 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
3
450
3
450
H
P, Compressor 1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Amps (RLA), Comp. 1 28.2 28.2 28.2 14.7 14.7 14.7 11.3 11.3
Amps (LRA), Comp. 1 239 239 239 130 130 130 93.7 93.7
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460 575 575
Phase 1 1 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA, each) 2.4 2.4 2.4 1.4 1.4 1.4 1 1
Amps (LRA, each) 4.7 4.7 4.7 2.4 2.4 2.4 1.6 1.6
No. 1 1 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460 575 575
Phase 3 3 3 3 3 3 3 3
HP 2 2 2 2 3 3 2 3
Amps (FLA, each) 7.9 10.1 12 3.9 5 6 2.5 3.5
Amps (LRA, each) 45 74.5 74.5 22.5 38.1 38.1 19 20
Unit Information
Compressor Motor
1
20ACA15
1
20ACA22
1
20ACB15
1
20ACB22
120AYB15
1
20AYB22
1
20AYC15
120AYC22
ELECTRICAL DATA - -GEDZR SERIES
1
20ACC15
1
20ACC22
1
20ADA15
1
20ADA22
1
20ADB15
1
20ADB22
1
20ADC15
1
20ADC22
1
20AYA15
1
20AYA22
Condenser Motor
Evaporator Fan
Unit Operating Voltage Range
187-253 187-253 187-253 187-253 414-506 414-506
Volts
208/230 208/230 208/230 208/230 460 460
P
hase
3 3 3 3 3 3
H
z
6
0
6
0
6
0
6
0
6
0
6
0
Minimum Circuit Ampacity
41 44 41 44 17 19
M
inimum Overcurrent Protection Device
Size
50 50 50 50 20 25
M
aximum Overcurrent Protection Device
Size
6
0
6
0
6
0
6
0
2
5
2
5
No. 1 1 1 1 1 1
V
olts
2
08/230
2
08/230
2
08/230
2
08/230
4
60
4
60
Phase 3 3 3 3 3 3
RPM 3450 3450 3450 3450 3450 3450
HP, Compressor 1 7 7 7 7 7 7
Amps (RLA), Comp. 1 25.3 25.3 25.3 25.3 9.6 9.6
Amps (LRA), Comp. 1 184 184 184 184 84 84
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 208/230 208/230 460 460
Phase 1 1 1 1 1 1
HP 1/5 1/5 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 1.2 1.2 0.8 0.8
Amps (LRA, each) 2.3 2.3 2.3 2.3 1.4 1.4
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 208/230 460 460
Phase 3 3 3 3 3 3
HP 2 3 2 3 2 3
Amps (FLA, each) 6.6 9.1 6.6 9.1 3.2 4.6
Unit Information
Compressor Motor
Condenser Motor
Evaporator Fan
0
90ACA15
0
90ACA20
090ACB15
0
90ACB20
0
90ACC15
0
90ACC20
0
90ACF15
0
90ACF20
090ACG15
0
90ACG20
0
90ACH15
0
90ACH20
090ADA15
0
90ADF15
0
90ADF20
0
90ADA20
0
90ADB15
090ADB20
0
90ADC15
090ADC20
090ADG15
0
90ADG20
0
90ADH15
E
LECTRICAL DATA - -GEDZS SERIES
ELECTRICAL DATA - GEDZS MODELS
14
Amps (LRA, each) 47 74.5 22.5 74.5 22.5 38.1
0
90ADB15
0
90ADB20
090ADC15
0
90ADC20
090ADG15
090ADG20
0
90ADH15
Unit Operating Voltage Range
187-253 187-253 187-253 414-506 414-506 414-506
V
olts
2
08/230
2
08/230
2
08/230
4
60
4
60
4
60
Phase
3 3 3 3 3 3
H
z
6
0
6
0
6
0
6
0
6
0
6
0
Minimum Circuit Ampacity
46 48 51 21 22 24
Minimum Overcurrent Protection Device
S
ize
6
0
6
0
6
0
2
5
2
5
3
0
Maximum Overcurrent Protection Device
Size
70 70 70 30 30 35
N
o.
1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
H
P, Compressor 1
7
1/2
7
1/2
7
1/2
7
1/2
7
1/2
7
1/2
Amps (RLA), Comp. 1 28.8 28.8 28.8 12.5 12.5 12.5
Amps (LRA), Comp. 1 191 191 191 100 100 100
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460
Phase 1 1 1 1 1 1
HP 1/5 1/5 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 1.2 0.8 0.8 0.8
Amps (LRA, each) 2.3 2.3 2.3 1.4 1.4 1.4
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
HP 2 3 3 2 3 3
Amps (FLA, each) 7 9.1 12 3.5 4.6 6
Amps (LRA, each) 45 74.5 74.5 22.5 38.1 38.1
102ACB15
1
02ACB22
1
02ACG15
102ACG22
102ACC15
1
02ACC22
1
02ACH15
102ACH22
Unit Information
Compressor Motor
Condenser Motor
Evaporator Fan
ELECTRICAL DATA - -GEDZS SERIES
102ADC15
1
02ADC22
1
02ADH15
1
02ADH22
102ADH22
102ACA15
1
02ACF15
1
02ACF22
102ACA22
102ADA15
1
02ADA22
1
02ADF15
102ADF22
102ADB15
1
02ADB22
1
02ADG15
102ADG22
ELECTRICAL DATA - GEDZS MODELS
15
U
nit Operating Voltage Range
1
87-253
1
87-253
1
87-253
4
14-506
4
14-506
4
14-506
Volts
208/230 208/230 208/230 460 460 460
P
hase
3 3 3 3 3 3
Hz
60 60 60 60 60 60
M
inimum Circuit Ampacity
5
4
5
6
5
8
2
6
3
2
3
4
M
inimum Overcurrent Protection Device
Size
70 70 70 30 40 40
M
aximum Overcurrent Protection Device
S
ize
8
0
8
0
9
0
4
0
4
5
4
5
No. 1 1 1 1 1 1
V
olts
2
08/230
2
08/230
2
08/230
4
60
4
60
4
60
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
HP, Compressor 1 10 10 10 10 10 10
Amps (RLA), Comp. 1 32.6 32.6 32.6 14.8 14.8 14.8
Amps (LRA), Comp. 1 240 240 240 130 130 130
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460
Phase 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA, each) 2.4 2.4 2.4 1.4 1.4 1.4
Amps (LRA, each) 4.7 4.7 4.7 2.4 2.4 2.4
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
HP 2 2 2 2 3 3
Amps (FLA, each) 7.9 10.1 12 3.9 5.1 6
Amps (LRA, each) 45 74.5 74.5 22.5 38.1 38.1
ELECTRICAL DATA - -GEDZS SERIES
1
20ADA15
120ADA22
120ADF15
1
20ADF22
1
20ADB15
120ADB22
120ADG15
1
20ADG22
1
20ADC15
120ADC22
120ADH15
1
20ADH22
1
20ACA15
120ACA22
120ACF15
1
20ACF22
1
20ACB15
120ACB22
120ACG15
1
20ACG22
1
20ACC15
120ACC22
120ACH15
1
20ACH22
Condenser Motor
Evaporator Fan
Unit Information
Compressor Motor
ELECTRICAL DATA - GEDZS MODELS
16
ELECTRICAL DATA - GEDZS MODELS
Unit Operating Voltage Range
187-253 187-253 414-506 414-506 517-633 517-633
V
olts
2
08/230
2
08/230
4
60
4
60
5
75
5
75
Phase
3 3 3 3 3 3
H
z
6
0
6
0
6
0
6
0
6
0
6
0
Minimum Circuit Ampacity
70 75 34 37 25 27
Minimum Overcurrent Protection Device
S
ize
8
0
9
0
4
0
4
0
3
0
3
0
Maximum Overcurrent Protection Device
Size
90 90 40 45 30 30
N
o.
2 2 2 2 2 2
Volts 208/230 208/230 460 460 575 575
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
H
P, Compressor 1
6 6 6 6 6 6
Amps (RLA), Comp. 1 25 25 12.8 12.8 9.6 9.6
Amps (LRA), Comp. 1 164 164 100 100 78 78
HP, Compressor 2 6 6 6 6 6 6
Amps (RLA), Comp. 2 25 25 12.8 12.8 9.6 9.6
Amps (LRA), Comp. 2 164 164 100 100 78 78
No. 2 2 2 2 2 2
Volts 208/230 208/230 460 460 575 575
Phase 1 1 1 1 1 1
HP 3/4 3/4 3/4 3/4 3/4 3/4
Amps (FLA, each) 4.2 4.2 2.3 2.3 1.2 1.2
Amps (LRA, each)
No. 1 1 1 1 1 1
Volts 208/230 208/230 460 460 575 575
Phase 3 3 3 3 3 3
HP 3 5 3 5 3 5
Amps (FLA, each) 10.4 16 5.2 8 4.4 5.9
Amps (LRA, each) 74.5 82 38.1 41 20 38
Evaporator Fan
Unit Information
Compressor Motor
150ACA15
1
50ACA22
1
50ACF15
150ACF22
150ACB15
1
50ACB22
1
50ACG15
150ACG22
150ADA15
1
50ADA22
1
50ADF15
150ADF22
150ADB15
1
50ADB22
1
50ADG15
150ADG22
Condenser Motor
ELECTRICAL DATA - -GEDZS SERIES
1
50AYA15
1
50AYA22
1
50AYB15
1
50AYB22
17
U
nit Operating Voltage Range
1
87-253
1
87-253
4
14-506
4
14-506
Volts
208/230 208/230 460 460
P
hase
3 3 3 3
Hz
60 60 60 60
M
inimum Circuit Ampacity
4
1
4
4
1
7
1
9
M
inimum Overcurrent Protection Device
Size
50 50 20 25
M
aximum Overcurrent Protection Device
S
ize
6
0
6
0
2
5
2
5
No. 1 1 1 1
V
olts
2
08/230
2
08/230
4
60
4
60
Phase 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
HP, Compressor 1 7 7 7 7
Amps (RLA), Comp. 1 25.3 25.3 9.6 9.6
Amps (LRA), Comp. 1 184 184 84 84
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2
Volts 208/230 208/230 460 460
Phase 1 1 1 1
HP 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 0.8 0.8
Amps (LRA, each) 2.3 2.3 1.4 1.4
No. 1 1 1 1
Volts 208/230 208/230 460 460
Phase 3 3 3 3
HP 2 3 2 3
Amps (FLA, each) 6.6 9.1 3.2 4.6
Amps (LRA, each) 22.5 74.5 22.5 38.1
090ACF15
090ACF20
0
90ACG15
090ACG20
090ACH15
0
90ACH20
090ADF15
090ADF20
Unit Information
Compressor Motor
Condenser Motor
Evaporator Fan
0
90ADG15
090ADG20
090ADH15
0
90ADH20
ELECTRICAL DATA - -GEDZT SERIES
ELECTRICAL DATA - GEDZT MODELS
18
Unit Operating Voltage Range
187-253 187-253 187-253 414-506 414-506 414-506
V
olts
2
08/230
2
08/230
2
08/230
4
60
4
60
4
60
Phase
3 3 3 3 3 3
H
z
6
0
6
0
6
0
6
0
6
0
6
0
Minimum Circuit Ampacity
46 48 51 21 22 24
Minimum Overcurrent Protection Device
S
ize
6
0
6
0
6
0
2
5
2
5
3
0
Maximum Overcurrent Protection Device
Size
70 70 70 30 30 35
N
o.
1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
H
P, Compressor 1
7
1/2
7
1/2
7
1/2
7
1/2
7
1/2
7
1/2
Amps (RLA), Comp. 1 28.8 28.8 28.8 12.5 12.5 12.5
Amps (LRA), Comp. 1 191 191 191 100 100 100
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460
Phase 1 1 1 1 1 1
HP 1/5 1/5 1/5 1/5 1/5 1/5
Amps (FLA, each) 1.2 1.2 1.2 0.8 0.8 0.8
Amps (LRA, each) 2.3 2.3 2.3 1.4 1.4 1.4
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
HP 2 3 3 2 3 3
Amps (FLA, each) 7 9.1 12 3.5 4.6 6
Amps (LRA, each) 45 74.5 74.5 22.5 38.1 38.1
ELECTRICAL DATA - -GEDZT SERIES
1
02ADG15
1
02ADG22
1
02ADH15
1
02ADH22
1
02ACH15
1
02ACH22
1
02ADF15
1
02ADF22
Unit Information
Compressor Motor
Condenser Motor
Evaporator Fan
1
02ACF15
1
02ACF22
1
02ACG15
1
02ACG22
ELECTRICAL DATA - GEDZT MODELS
19
U
nit Operating Voltage Range
1
87-253
1
87-253
1
87-253
4
14-506
4
14-506
4
14-506
Volts
208/230 208/230 208/230 460 460 460
P
hase
3 3 3 3 3 3
Hz
60 60 60 60 60 60
M
inimum Circuit Ampacity
5
4
5
6
5
8
2
6
3
2
3
4
M
inimum Overcurrent Protection Device
Size
70 70 70 30 40 40
M
aximum Overcurrent Protection Device
S
ize
8
0
8
0
9
0
4
0
4
5
4
5
No. 1 1 1 1 1 1
V
olts
2
08/230
2
08/230
2
08/230
4
60
4
60
4
60
Phase 3 3 3 3 3 3
R
PM
3
450
3
450
3
450
3
450
3
450
3
450
HP, Compressor 1 10 10 10 10 10 10
Amps (RLA), Comp. 1 32.6 32.6 32.6 14.8 14.8 14.8
Amps (LRA), Comp. 1 240 240 240 130 130 130
HP, Compressor 2
Amps (RLA), Comp. 2
Amps (LRA), Comp. 2
No. 2 2 2 2 2 2
Volts 208/230 208/230 208/230 460 460 460
Phase 1 1 1 1 1 1
HP 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA, each) 2.4 2.4 2.4 1.4 1.4 1.4
Amps (LRA, each) 4.7 4.7 4.7 2.4 2.4 2.4
No. 1 1 1 1 1 1
Volts 208/230 208/230 208/230 460 460 460
Phase 3 3 3 3 3 3
HP 2 2 2 2 3 3
Amps (FLA, each) 7.9 10.1 12 3.9 5.1 6
Amps (LRA, each) 45 74.5 74.5 22.5 38.1 38.1
120ACF15
120ACF22
120ACG15
120ACG22
120ACH15
120ACH22
120ADF15
120ADF22
120ADG15
120ADG22
120ADH15
120ADH22
ELECTRICAL DATA - -GEDZT SERIES
Compressor Motor
Condenser Motor
Evaporator Fan
Unit Information
ELECTRICAL DATA - GEDZT MODELS
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88