FläktGroup EU General Installation guide

Type
Installation guide
Fläkt Woods 3164 GB 2008.01 1 Specifications are subject to alteration without notice
EU Air Handling Unit MAINTENANCE
Adjustment
The air handling unit must be adjusted before being
taken into service to ensure its satisfactory function.
Since the unit must function reliable year after year,
it must receive proper maintenance and the correct
spare parts.
Adjustment includes the following operations:
Filter – check pressure sensor
Heater – check shunt
Cooler – check shunt, or check valves and compressor
Humidifier – check water quaklity
Fan – check belt tension
Rotary heat exchanger setting of forced air cleaning
sector and direction of rota-
tion at constant speed
Plate heat exchanger – check damper function
Water trap – check that the water trap is full
This check is not required if water trap EUAZ-08 is
used.
Maintenance
Regular maintenance of this air handling unit can be
provided by signing a contract with an Fläkt Woods
company, or maintenance can be carried out by the
company normally responsible for maintaining the
property.
Inspection intervals
A number of service charts to be completed by the
person who maintains the unit can be found at the rear
of this book.
The service chart includes the service and inspec-
tion operations to be performed on functional compo-
nents that may be part of an air handling unit. The unit
contains one or more of these functional components.
Any components that are not relevant may be deleted
from the service chart.
The chart shall be dated and signed each time serv-
icing is carried out.
The length of the service interval is estimated at 2000
operating hours over a 12-month period and for an
installation providing a normal comfort level.
In environments with a high level of dust in the
supply air or exhaust air, inspection of the air
handling unit shall be performed at more frequent
intervals.
Replacement of door seal
The door seal is available as a spare part and must be
replaced, if necessary, to ensure that the unit is
airtight.
Spare parts
Spare parts and accessories for this unit can be ordered
from our nearest sales office.
The order should also state the product code.
The code can be found on a separate data panel
located on the functional component concerned.
Removal of fixed panels
General maintenance instructions
Fig. 1
1/4” bit (magnetic)
Max. ø 12
Self-tapping screw, 4.2 x 13
General maintenance instructions
Fläkt Woods 3164 GB 2008.01 2 Specifications are subject to alteration without notice
EU Air Handling Unit MAINTENANCE
Fig. 4
Size 60–84
B = max 3 mm
A
A
2
1
Handle for overpressure with/without lock
Lock without handle
To dismantle the handles
Normal handle with/without lock
Nut
Nut
Nut
Plastic washer
Plastic washer
Plastic washer
Screw
Screw
Screw
Sealing washer
Sealing washer
Sealing washer
Handle
Handle
Screw
Screw
Screw
Key
Key
Roller cam
Plastic washer
Distansbricka
Plastic washer
Roller cam
Plastic washer
Cover
Cover
Adjustment of hinge
Slacken items 1 and 2, and adjust the gaps “A” so that
they are equal. The gap “B” shall not exceed 3 mm. Use
spacers of an appropriate size. Push items 1 and 2
together and tighten the screws. Check that the seals
around the cover seal effectively, and that the cover is
easy to open and close. Also check the locking function.
Size 11–53
Fig. 3
2
1
A
A
B = max. 3 mm
2
1
Copy
Service chart
Fläkt Woods 3164 GB 2008.01 3 Specifications are subject to alteration without notice
EU Air Handling Unit MAINTENANCE
Applicable from 20 .. .. .. to 20 .. .. ..
Symbol Operation Mon. Date Operation Date Operation Date
Sign. Sign. Sign.
3-month/9-month service 6-month service 12-month service
Filter
EUP(A,B,C)
Carbon filter
EUPK
Damper
Check pressure drop
and need for filter
replacement.
General inspection.
Check function and
gasket. Replace gasket
if required.
Check function and
gasket. Replace gasket
if required.
Check function and
gasket. Replace gasket
if required.
Check pressure drop
and need for filter
replacement.
Replace cylinders or
carbon as required, or
cassette.
Check pressure drop
and need for filter
replacement.
Replace cylinders or
carbon as required, or
cassette.
Cooling unit
Cooler
Follow instruction 8522
and local regulations.
Follow instruction 8522
and local regulations.
Follow instruction 8522
and local regulations.
Air heater
EUE(E,V,A,S)
Air cooler
EUN(N,P)
Liquid-connected
heat exchanger
EURE, EURV
General inspection. Clean finned body. Clean finned body, drai-
nage box and casing.
Humidifier
EUQA
Check of Casing,
Humidifier inserts,
Droplet separator,
Water filter, Basin,
Sprinkler tube, Water
flow, Constant-flow valve.
Check of Casing,
Humidifier inserts,
Droplet separator,
Water filter, Basin,
Sprinkler tube, Water
flow, Constant-flow valve.
Check of Casing,
Humidifier inserts,
Droplet separator,
Water filter, Basin,
Sprinkler tube, Water
trap, Water quality,
Water flow, Constant-
flow valve.
Fan
EULK
General inspection. General inspection. Clean impeller wheel,
cover and unit casing
Check bearings and
elubrication of bearings,
if required, in plummer
block housing
SKF SNA 5(0) TAV.
Fan
EULR
General inspection. Check belt tension. Check belt tension, clean
impeller wheel, cover
and unit casing Check
bearings and lubrication
of bearings, if required,
in plummer block housing
SKF SNA 5(00) TAV.
Air treatment
unit
Cleaning Cleaning Cleaning
3
9
3
9
3
9
3
9
Rotary heat
exchanger
EUR(A,B)
General inspection.
Check seals.
Clean rotor Clean rotor.
Check equipment for
monitoring and blowing-
through.
3
9
Plate heat
exchanger
EURC
General inspection.
Check damper function.
Clean exchanger cube. Clean exchanger cube,
bypass damper and
casing.
3
9
3
9
3
9
3
9
Sound
attenuator
EUSA
Cleaning as required. Cleaning as required. Cleaning as required.
3
9
3
9
3
9
  • Page 1 1