Fläkt Woods 3164 GB 2008.01 1 Specifications are subject to alteration without notice
EU Air Handling Unit MAINTENANCE
Adjustment
The air handling unit must be adjusted before being
taken into service to ensure its satisfactory function.
Since the unit must function reliable year after year,
it must receive proper maintenance and the correct
spare parts.
Adjustment includes the following operations:
Filter – check pressure sensor
Heater – check shunt
Cooler – check shunt, or check valves and compressor
Humidifier – check water quaklity
Fan – check belt tension
Rotary heat exchanger – setting of forced air cleaning
sector and direction of rota-
tion at constant speed
Plate heat exchanger – check damper function
Water trap – check that the water trap is full
This check is not required if water trap EUAZ-08 is
used.
Maintenance
Regular maintenance of this air handling unit can be
provided by signing a contract with an Fläkt Woods
company, or maintenance can be carried out by the
company normally responsible for maintaining the
property.
Inspection intervals
A number of service charts to be completed by the
person who maintains the unit can be found at the rear
of this book.
The service chart includes the service and inspec-
tion operations to be performed on functional compo-
nents that may be part of an air handling unit. The unit
contains one or more of these functional components.
Any components that are not relevant may be deleted
from the service chart.
The chart shall be dated and signed each time serv-
icing is carried out.
The length of the service interval is estimated at 2000
operating hours over a 12-month period and for an
installation providing a normal comfort level.
In environments with a high level of dust in the
supply air or exhaust air, inspection of the air
handling unit shall be performed at more frequent
intervals.
Replacement of door seal
The door seal is available as a spare part and must be
replaced, if necessary, to ensure that the unit is
airtight.
Spare parts
Spare parts and accessories for this unit can be ordered
from our nearest sales office.
The order should also state the product code.
The code can be found on a separate data panel
located on the functional component concerned.
Removal of fixed panels
General maintenance instructions
Fig. 1
1/4” bit (magnetic)
Max. ø 12
Self-tapping screw, 4.2 x 13