EU Air Handling Unit INSTALLATION
EURV liquid coupled heat exchangers
Condition on delivery
The heat exchanger is filled at the factory with the heat
transfer medium and is provided with plugged connec-
tions for venting, filling and drainage. The heat transfer
medium consists of water with 30% ethylene glycol addi-
tive to serve as an anti-freeze agent.
Description
The pipework of pressure vessel-rated design is connected
across flat gaskets directly to the heat exchangers. The
pipework package is insulated with 10 mm thick
ARMAFLEX insulation to prevent frosting.
The three-way valve with actuator provides max. effici-
ency and prevents frost from forming on the heat
exchanger for exhaust air.
A flow adjustment valve with measurement connec-
tions is installed for adjusting the duty point of the pump
to the correct flow setting depending on the flow range
selected.
The anti-freeze controller is incorporated in the anti-
freeze sensor. The controller emits a 0–10 V input signal
to the valve actuator. 24 V ac power must be supplied to
the actuator and the anti-freeze controller. The trans-
former is not included. Two shut-off valves are fitted, one
before the suction side and the other after the delivery
side of the pump.
The temperature of the heat transfer medium must be
regulated by an external controller (0...10 V), not in-
cluded in the supply.
Fig. 1 EUAZ-08 siphon (not
included in the EURV)
Technical particulars
Max. operating pressre 0,6 MPa
Test pressure 0,8 MPa
Max. operating temp.
Ambient temp., air 40°C
Brine 90°C
Max. mixture of glycol 40%
Pump motor 3-fas 400 V, 50 Hz
Degree of protection
pump motor IP 54
Pipe, size, flow
DN25 0,42...0,92 l/s
DN32 0,92...1,61 l/s
DN50 1,61...2,45 l/s
Size EURV Power supply, V Rating, W Rated current A 1)
20–21 550 1,6
22–30 3 x 400 550 1,6
31–40 750 1,8
41–42 740 1,8
Pump specification
RC2 Frosting monitor
S1 Actuator
Y Control signal from the
temperature controller
G, Go G: 24 V system potential
Go: system neutral
YGG0
RC2
G
R
M
G
R
M
Z8
Y1
Y
S1
G0
G0
Fig. 2
Connections diagram
1) The rated current may vary slightly between different batches of pumps. The
correct data are indicated on the pump rating plate.
EURV liquid coupled heat exchangers
Fläkt Woods 3197 GB 03.01 2 Specifications are subject to alteration without notice
EU Air Handling Unit INSTALLATION
Arrangement of liquid system
9
86
11
7
10
13
1
13
12
5
4
2
3
10
RC
1. Circulation pump
2. Control box
3. Temperature controller
4. Valve actuator
5. 3-way valve
6. Expansion vessel
7. Safety valve
8. Draining/topping-up valve
9. Manometer
10. Contact thermometer
11. 1/2 hose connection
12. Adjustment valve
13. Shut-off valve
Charging the system
If the pressure is below 0.01 MPa, the system requires
charging with heat transfer medium. This is done by
pumping pre-mixed heat transfer medium (30% ethyle-
ne glycol) into the charging valve (8 in Fig. 3) until the
manometer reads 0.1 MPa.
Fig. 3
  • Page 1 1