EUBA-20/53, EUBB-60/84 – General instruc-
tions, outdoor version
Fläkt Woods 4067 GB 05.08 4 Specifications are subject to alteration without notice
EU Air Handling Unit INSTALLATION
Jointing of blocks, sizes 20–53
Internal bolted joints at the bolt lugs fitted along the
frame are used for jointing the blocks to one another.
Access to the inside of the casing can be gained either
by opening an inspection door or by removing a wall
panel. If nesessary, withdraw any unit sections that
are in the way.
1. Fit the sealing strips supplied to the frame of one of
the blocks.
2. Push the blocks towards one another, making sure
that they are well lined up with one another.
3. Fit the joint bolts into the corner brackets on the
inside of the frame and make sure that they are
firmly in position.
4. Use a 14 mm spanner for the joint bolts to pull the
blocks together.
5. Tighten all four bolts alternately, compressing the
seal to 1–2 mm.
N.B! Make sure that the joint bolt is located in the
bottom of the screw pocket throughout the
tightening process. The cone of the joint bolt
will then fit into the cone of the screw pocket
(see Fig. 10).
Connection to next EU block
Fit the self-tapping screws in the existing holes in the
frame profiles, and tighten the connector with a size
14 spanner.
Connection to Regoterm (EURA) and
Jointing frame (EUVH c = 3, 4)
The connector is attached to the strut with self-tapp-
ping screws and is tightened with a size 14 spanner.
Connection to Angle section
(EUTA b = 1–4)
The connector is attached to the top/bottom with self-
tapping screws and is tightened with a size 14 spanner.
Fig. 10 a
Fig. 10 b
Fig. 10 c