FläktGroup EURV Installation guide

Type
Installation guide
Fläkt Woods 3184 GB 03.01 1 Specifications are subject to alteration without notice
EU Air Handling Unit MAINTENANCE
EURV Liquid-connected heat exchanger
Adjustment
The EURV heat exchanger is adjusted and tested at the
time of delivery. No adjustments are normally required,
therefore.
Design of liquid system
Fig. 1 EUAZ-08 Water trap
(not included in EURV)
9
86
11
7
10
13
1
13
12
5
4
2
3
10
RC
1. Pump
2. Control unit
3. Temp. regulator
4. Adjuster
5. Three-way valve
6. Expansion vessel
7. Safety valve
8. Charging valve
9. Pressure gauge
10. Contact
thermometer
11. 1/2” hose
connection
12. Balancing valve
13. Shut-off valve
Fig. 2
Cleaning
The presence of dust on the heating and cooling surfaces
will result in impaired heat transfer. The finned body
must be kept clean, preferably by vacuum cleaning or
careful blowing with compressed air, moving parallel with
the fins. The use of ULCZ-01 cold degreasing agent is
recommended where the dust is mixed with grease.
After cleaning:
Remove all fallen dust
and/or liquid before
starting the fan
Important!
Clean the water trap,
if fitted
Fig. 3
Charging the system
If the pressure is below 0.01 MPa, the system requires
charging with heat transfer medium. This is done by
pumping pre-mixed heat transfer medium (30% ethyle-
ne glycol) into the charging valve (8 in Fig. 2) until the
manometer reads 0.1 MPa.