  • Hello! I've reviewed the provided installation instructions for the BARRON QXS Series exit sign. This document covers important safety guidelines, mounting options such as ceiling, end, and wall mounting, and electrical connections for standard and remote-capable models. It also explains how to adjust the color output making it suitable for diverse environments. I'm ready to answer any questions you may have.
  • What should I do before servicing?
    Who should perform installation and service?
    What is the maximum mounting height?
    How do you change the color of the exit sign?
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
When using electrical equipment, basic safety precautions should always be followed including the following:
DISCONNECT AC POWER SUPPLY BEFORE SERVICING.
• Installation and servicing of this equipment should be performed by qualified service personnel only.
• Ensure that the electrical wiring conforms to the National Electrical Code NEC® and local regulations
if applicable.
• Do not mount near gas or electrical heaters.
• Do not use outdoors.
• Equipment should be mounted in locations and at heights (MAX: 8ft) where it will not be readily subjected to
tampering by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Any modification or use of non-original components will void the warranty and product liability.
• Do not use this equipment for other than intended use.
Allow battery to charge for 24 hours before first use.
SAVE THESE INSTRUCTIONS!
Technical Support ■ (623) 580-8943 ■ [email protected]
QXS Series
Installation Instructions
10070237 REV 1 - 01/21 800-533-3948 www.barronltg.com
1
Ceiling or End Mount (Fig. 1 & 2)
1. Make electrical connections; see Electrical Connections section.
2. Fasten canopy to J-box mounting plate.
3. Snap enclosure to canopy.
4. Secure faceplate to enclosure and remove chevrons, as desired.
Wall Mount
1. Make electrical connections; see Electrical Connections section.
2. Fasten backplate to J-box.
3. Snap enclosure to backplate.
4. Secure faceplate to enclosure and remove chevrons, as desired. Fig. 2 - End Mount
Fig. 1 - Ceiling Mount
Faceplate
J-Box Mounting
Plate
Canopy
Enclosure
Faceplate
J-Box
Mounting
Plate
Canopy
Enclosure
QXS Series
Installation Instructions
10070237 REV 1 - 01/21 800-533-3948 www.barronltg.com
2
Operation
1. The unit is shipped from the factory with the color selector jumper set to “RED” (see Fig. 3 - jumper is placed across
pins 2 & 3) and use the red diffuser.
2. To change the color to “GREEN,” move the color selector jumper to “GREEN” (see Fig. 4 - jumper is placed across
pins 1 & 2) and use the green diffuser.
Electrical Connections (Fig. 5 & 6)
All electrical connections should be made inside the junction box. Make electrical connections as follows:
Note: Cap unused leads to prevent shorting.
120VAC 277VAC
White - Common White - Common
Black - 120VAC Red - 277VAC
Fig. 5 - Standard Models Fig. 6 - Remote Capable Models
Fig. 3 - Red Color Selection Fig. 4 - Green Color Selection