  • Hello, I'm your chat assistant. I've reviewed the installation instructions for the QCSS Series Exit Sign from BARRON. This document details how to safely install, connect, and test the device. It also specifies key features, such as the emergency lighting duration and battery life. I'm here to help with any questions about this product.
  • How long should the battery charge before first use?
    How long will the LED lamps stay on during a power failure?
    How often should I test the battery?
    What is the life expectancy of the battery?
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
When using electrical equipment, basic safety precautions should always be followed including the following:
DISCONNECT AC POWER SUPPLY BEFORE SERVICING.
• Installation and servicing of this equipment should be performed by qualified service personnel only.
• Ensure that the electrical wiring conforms to the National Electrical Code NEC® and local regulations
if applicable.
• Do not mount near gas or electrical heaters.
• Do not use outdoors.
• Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering
by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Any modification or use of non-original components will void the warranty and product liability.
• Do not use this equipment for other than intended use.
Allow battery to charge for 24 hours before first use.
SAVE THESE INSTRUCTIONS!
Technical Support ■ (623) 580-8943 ■ [email protected]
QCSS Series
Installation Instructions
10070234 REV 1 - 01/21 800-533-3948 www.barronltg.com
1
Wall Mount
1. Remove faceplate from sign and set aside.
2. Position fixture over the junction box and mark the appropriate holes to be drilled / knocked out to align the enclosure
correctly over the junction box.
3. Route wires through center hole of backplate.
4. Make electrical connections; see Electrical Connections section.
5. Secure backplate to junction box (hardware not included).
6. Remove proper chevron(s) as required. When removing chevrons, it may be helpful to remove the color diffuser panel
to allow easier access to the chevrons. If removing color diffuser panel, it is important to remember to reinstall the
diffuser panel once chevron(s) have been removed.
7. Connect battery to circuit board (battery backup models only).
8. Secure faceplate(s) to the enclosure.
Ceiling Mount
1. Attach mounting plate to junction box.
2. Feed transformer leads through the top hole of the enclosure, making sure to secure wire into wire guides found at the
edge of the sign.
3. Attach sign to canopy by snapping canopy into place.
4. Make electrical connections; see Electrical Connections section.
5. Push excess wire into junction box. Align holes in canopy with those in mounting plate. Use supplied screws to secure
canopy to mounting plate, tightening until canopy is pulled firmly to ceiling.
6. Remove proper chevron(s) as required. When removing chevrons, it may be helpful to remove the color diffuser panel
to allow easier access to the chevrons. If removing color diffuser panel, it is important to remember to reinstall the
diffuser panel once chevron(s) have been removed.
7. Connect battery to circuit board (battery backup models only).
8. Secure faceplate(s) to the enclosure.
Operation
1. During and electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2. To test, depress the “TEST” switch. The emergency LED lamps will illuminate. When the switch is released, the lamps
will go off.
Testing
The battery supplied with this unit requires no maintenance. However, it should be tested periodically and replaced when
it no longer operates the lamp heads for the duration of 30 seconds. The battery in this unit has a life expectancy of 4
years when used in a normal ambient temperature of 72°F.
QCSS Series
Installation Instructions
10070234 REV 1 - 01/21 800-533-3948 www.barronltg.com
2
Fig. 2 - StandardFig. 1 - Remote Capable
Electrical Connections (Fig. 1 & 2)
All electrical connections should be made inside the junction box. Make electrical connections as follows:
Note: Cap unused leads to prevent shorting.
120VAC 277VAC
White - Common White - Common
Black - 120VAC Orange - 277VAC
Green - Ground Green - Ground
Blue (-)
Yellow (+) To Remote Head
Blue (-)
Yellow (+)
Test
“READY” Light
+ -
BATTERY
Blue (-)
Yellow (+)
Red (277V)
Black (120V)
White (Com)
TRANSFORMER
LAMP
LAMP
TRANSFORMER
Red (277V)
Black (120V)
White (Com)
LAMP
LAMP
Blue (-)
Yellow (+) BATTERY
+ -
Blue (-)
Yellow (+)
“READY” Light
Test
QCSS Series
Installation Instructions
10070234 REV 1 - 01/21 800-533-3948 www.barronltg.com
3
/