INSTALLATION
INSTRUCTIONS
AIR FLOW AND VELOCITY TRANSMITTERS
DPT-Flow-Batt
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
Thank you for choosing an HK Instruments DPT-Flow-Ba series
airowmeter.TheDPT-Flow-Baseriesisintendedforuseinen-
vironmentsandapplicaonswhereelectricityisnotavailable.The
DPT-Flow-Bameasuresairow,velocityanddierenalpressure.
Itisdesignedtobeusedincombinaonwithcentrifugalfansthat
providedierenalpressureconneconsandK-values.
DPT-FlowseriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•airowmonitoringacrosscentrifugalfansandblowers
•in-ductairowmonitoring
SPECIFICATIONS
Performance
Accuracy (from FS):
±1.5 %
(Accuracyspecicaonsinclude:generalaccuracy,
temperaturedri,linearity,hysteresis,longterm
stability,andrepeonerror)
Thermal eects:
Temperaturecompensatedacrossthefullspectrumof
capability
Overpressure:
Proofpressure:25kPa
Zero point calibraon:
Manualpushbuon
Response me:
1.0−10s,selectableviamenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Pressure units (select via menu):
Pa, kPa, mbar, inWC, mmWC
Flow units (select via menu):
Volume:m3/s,m3/hr,cfm,l/s
Velocity:m/s,/min
Measuring element:
MEMS
Environment:
Operangtemperature:-10...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:102.0x71.5x36.0mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case:ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display
2-linedisplay(12characters/line)
 Line1:Volumeorvelocitymeasurement
 Line2:Pressuremeasurement
Size:46.0x14.5mm
Electrical connecons:
9VDCbaeryconnector
Pressure ngs
Maleø5.0mmand6.3mm
Electrical
Currentconsumpon:
~20mAonacvemode
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
APPLICATIONS
INTRODUCTION WARNING
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 4.0 2017
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
Figure 1a - Surface mounng
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Pushthebuononthetoprightcornerofthehousingtoturnon
thedevice.
3)Thedeviceisnowreadyforconguraon.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
Display connecon
Pressure
sensor
SELECT
UP
DOWN
ZERO
Menu
buons
LED
BATTERY
9 VDC
DPT
Thepressuretubesareconnectedtoaowmeasurementprobe(i.e.FloXact),ortothe
measurementportsspeciedbythefanmanufacturer.PleaseseetheFloXactinstallaon
guideorthefanmanufacturer’stechnicalspecicaonsformoreinformaon.
YES NO NO
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 4.0 2017
CONFIGURATION CONTINUED
1)Startthetransmierbypushingthebuononthehousing.
2)Selectthefunconingmodeoftheowmeter:
-SelectManufacturer whenconnecngDPT-Flowtoafanwith
pressuremeasurementpoints
-SelectCommon probe whenusingDPT-Flowwithacommon
measurmentprobethatfollowstheformula:
 q=k∙√∆P(i.e.FloXact)
3)If
Commonprobe
selected:selectmeasurementunitsusedinthe
formula(akaFormulaunit)(i.e.l/s)
b. If
Commonprobe
selectedinstep1:
Each common probe has a specic K-value. Select the K-value from
commonprobemanufacturer’sspecicaons.
AvailableK-valuerange:0.001...9999.000
6)Selectowunitfordisplayandoutput:
Flowvolume:m3/s,m3/h,cfm,l/s
Velocity:m/s,f/min
MANUFACTURER
Common probe
SELECT
UP
DOWN
Common probe Flakt Woods
SELECT
UP
DOWN
FORMULA UNIT
l/s
SELECT
UP
DOWN
4)SelectK-value
a.Ifmanufacturerselectedinstep1:
EachfanhasaspecicK-value.SelecttheK-valuefromfanmanufac-
turer’sspecicaons.
Manufacturer: K-value:
Fläktwoods k=0,3...99
Rosenberg k=37...800
Nicotra  k=10...1500
Comefri  k=10...2000
Ziehl  k=10...1500
Ebm-papst k=10...1500
Gebhardt k=50...4700
K-VALUE
9000.000
SELECT
UP
DOWN
5)Selectpressureunitfordisplayandoutput:Pa,kPa,mbar,inWCor
mmWC
PRESS.UNIT
Pa
SELECT
UP
DOWN
FLOW UNIT
m3/s
SELECT
UP
DOWN
7)Responseme:Selectresponsemebetween1.0–10s.
RESPONSE TIME
10 s
SELECT
UP
DOWN
8)Pushselectbuontosavechangesandtoexitmenu.
SELECT
EXIT MENU
SELECT
STEP 2: CONFIGURATION
STEP 3: ZEROING THE DEVICE
ManualPushbuonzeropointcalibraon
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)PushdownthezerobuonunltheLEDlight(red)turnsonand
thedisplayreads“zeroing.(seegure3)
c)Thezeroingofthedevicewillproceedautomacally.Zeroingis
completewhentheLEDturnso,andthedisplayreads0.
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
a) Disconnect both pressure tubes from the pressure ports labeled +
and –.
b) Push down the zero buon (joysck) unl the LED light (red)
turns on and the display reads “zeroing” (display opon only). (see
Figure 6)
c) The zeroing of the device will proceed automacally. Zeroing is
complete when the LED turns off, and the display reads 0 (display
opon only).
d) Reinstall the pressure tubes, ensuring the High pressure tube is
connected to the port labeled +, and the Low pressure tube is
connected to the port labeled −.
Press down buon
LED turns ON
Display reads “Zeroing”
LED
Figure 2
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
RECYCLING/DISPOSAL
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 4.0 2017
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, oodor other natural phenomenon,normalwear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthebuyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device,orifneeded,anewpartordevice,butnotinstallaonorex-
changecosts. Underno circumstanceistheseller liablefor damages