PURGING THE FINNED HEAT EXCHANGERS OF AIR
Purging can be purged of air either automatically or manually.
MEASURES TO BE TAKEN IF THERE IS RISK OF FREEZING
If the water in a coil should freeze, the coil will burst. This will allow the
water to run out of the system, which may causewater damage.
Freezing is likely to occur in ventilation systemsunder the following
conditions at low outdoor air temperatures:
1. The temperature of the heatingmediumis too low
The temperature of the heating medium is too low Freezing is
especially likely to occur in the autumn and in the spring. Adjust
the water temperature to suit the outdoor air temperature.
2. The finned heat exchanger is oversized
Set the water temperature to a lower setting so that the water
flow will increase.
3. Theheat supplytothe airheater ceasesor is reduced
If the supply of heat to the air heater is expected to cease or be
significantly reduced, the outdoor air intakemust then be adequately
closed and all the fans must be stopped.
EQAZ-18
Manual
air purging
valve
EQAZ-19 Automatic
air purging valve
NOTE!
If the heat supply has ceased or decreased,
open the air recirculation damper.
The pressure in the premises may then drop
to sub-atmospheric value, even though
the fans are not running.
Outdoor air will then be drawn through
the unit and may cause freezing and con-
sequent bursting.
The anti-freeze protection must not be
adjusted to such a low temperature that
freezing is likely to occur.
If the building is left unheated for a longer
period of time in the winter, the water must
be drained from both the pipework and
the heat exchangers.
Don't refit the plugs to the heat exchangers
before the systems is to be refilled with
water. Tomake certain that the heat exhanger
is completely drained of water, blow com-
pressed air through it.
DRAINAGE
The heat exchanger cannot be drained completely. Antifreeze must
therefore be added to the liquid if there is risk of freezing.
FINS
Use the QLAZ-14-1 fin comb to straighten any deformed fins.
QLAZ-14-1 fin comb
Caution!
To avoid injuries, wear protective gloves
wheneverworkingwith the fin comb.
CONDENSATE DRAINAGE FOR THE EQRF
The finned heat exchangers are provided with 32 mm dia. drain
connections for connection to a water trap with a depth of at least
150 mm. Preferably use the EQAZ-08water trap (see separate
instruction).
Watertrap EQAZ-08-1
Under atmospheric Above atmospheric
Watertrap EQAZ-08-2