4
Installation and maintenance instruction
FläktGroup DC_8638GB 20180305_R0 We reserve the right to make changes without prior notice
= Air heater for hot water
= Shut-off valve
= 2-way throttling valve, manual
= 2-way control valve, automatic
= 3-way control, valve automatic (the unfilled arrow
point always indicates a fully open valve)
= Thermometer
= Non-return valve
= Measuring tapping
= Pump (the point of the arrow indicates the direction
of the flow)
= Direction of the flow
SYMBOLS USED IN FIGS.4-5 AND 7-15
GENERAL INFORMATION CONCERNING CONTROL
For best result each heating coil should be provided with its own
circulation pump (see Fig. 3). This ensures an even circulation of the
water in the air heater, regardless of the position of the control valve;
and provides the following important benefits:
1. Appreciably less risk of freezing, due to the fact that the water
velocity in the coil is always sufficiently high.
2. Substantially better regulating characteristics. This is a conseuence
of the advantageous ratio between the pressure drop across the
control valve and the pump discharge pressure. This ratio is also
known as the valve authority “A”.
In the case of an air heater fitted with its own circulation pump and
connected as shown in Fig. 3, the valve authority is always 100%.
Fig. 4. Air heater with circulation pump.
Example: Assume that the air heater does not have its own circulation
pump (see Fig. 4). With a pressure drop across the control valve and
air heater of 400 and 600 mm WG respectively, the authority will be:
A = = 0,4 = 40%
400
400 + 600
Boiler
Fig. 5. Air heater without circulation pump.
As will be seen from the chart (Fig. 6), the water flow qr will not be
significantly reduced when the opening h is reduced from the fully
open position. In order to reduce the water flow qr by 50%, the valve
opening must be reduced to 0.37.
Control is further complicated by the fact that the heating capacity of
an air heater is not proportional to the water flow, the heating capacity
in normal cases is reduced by 15%.
In the example above, it will be seen that when the valve opening is re-
duced to 0.37, as much as 85% of the heating capacity is obtained. A
significant reduction in heating capacity is therefore obtained only over
a very small part of the valve stroke.
If the pressure drop across the control valve is low in relation to
that across the air heater, regulation will be even less efficient. At a
pressure drop of 55 mm WG in the example above, the authority will
be only 10%. According to Fig. 6, the valve opening must be reduced to
0.18 in order to obtain half the water flow, while the heating capacity
will still be 85%.
As mentioned previously, each air heater should be provided with its
own circulation pump and should be connected as shown in Fig. 4.
100
80
60
40
20
00 0,2 0,4 0,6 0,8 1,0
A = 10%
A = 40%
A = 100%
3154 38;1 EUE FIG
Valve opening, h
Water flow qr, %
Fig. 6