Installation instruction
FläktGroup DC_9152GB 20180319_R0 Specifications are subject to alteration without notice
FREEZING PROTECTION
When the heat exchanger is used for out door air <0 °C some form
of anti-freeze liquid should be used to protect the finned heat exchang-
ers against the risk of damage by freezing. All finned heat exchangers
can be equipped with surface type or insertion type sensors. The
location of the insertion sensor should be in accordance with the
instruction plate on the side of the unit section.
LQRF HEAT RECOVERY UNIT
The finned heat exchangers are provided with 32 mm dia. drain
connections for connection to a water trap with a depth of at least 100
mm. Preferably use the LQAZ-08 water trap.
PURGING THE FINNED HEAT EXCHANGERS OF AIR
The LQRF can be purged of air either automatically or manually.
Watertrap LQAZ-08
LQAZ-19 automatic
air purging valve
LQAZ-18
manual
air purging
valve
LQAZ-20-1 nipple
DRAINAGE
The heat exchanger cannot be drained completely. Antifreeze must
therefore be added to the liquid if there is risk of freezing.
FINS
Use the QLAZ-20 fin comb to straighten any deformed fins.
CAUTION!
To avoid injuries, wear protective gloves
wheneverworkingwith the fin comb.
QLAZ-20 fin comb
LQAZ-18 manual air purging valve