Ever UPS POWERLINE RT PLUS 6000/10000 Installation guide

Type
Installation guide
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units
2022-09-08 15:47 Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu
2
TABLE OF CONTENTS
TABLE OF CONTENTS ...................................................................................................................................... 2
SAFETY REMARKS ........................................................................................................................................... 3
REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM ....... 3
INSTALLATION GUIDELINES ........................................................................................................................ 5
ELECTRICAL SYSTEM ................................................................................................................................... 7
TECHNICAL ACCEPTANCE ............................................................................................................................ 9
NOTES ................................................................................................................................................................... 9
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit
3 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2022-09-08 15:47
SAFETY REMARKS
Read and understand the safety remarks and guidelines in the (full) Instruction
Manual of this UPS before attempting any switching operations.
REQUIREMENTS FOR PREPARATION OF THE POWER
SUPPLY AND RECEIVER SYSTEM
A) Shipping requirements.
CAUTION! Extreme caution is required during shipping, unloading and
installation of the device.
Transport the UPS units in the upright position as indicated on the packaging.
Protect the device against weather (i.e. protect from rain).
Prolonged shipping or storage below 0
C and/or above 25
C is NOT
recommended due to the battery life and the condensation hazard.
The devices are heavy and large. This require proper transport and handling
facilities (an adequate number of helpers, a forklift truck and properly
dimensioned handling routes).
CAUTION! Contact the Technical Service if any damage is found that
may affect proper performance of this device.
B) Location
CAUTION! Selection of the installation site and assurance of proper
operating conditions for the device are the user's responsibility.
Install the UPS in a separate room (to isolate the constant noise during operation
and protect the device from unauthorised access).
Do not expose the device to extreme (high and/or low) temperatures. Extreme
temperatures may shorten the battery life (the optimum temperature range is +18
to +25 ºC).
Do not install the device in rooms with dusty, corrosive and/or flammable
atmosphere or where the atmospheric humidity is high (the recommended
humidity is 90% without condensation).
If the device is installed on false/technical access floors, consider the structural
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units
2022-09-08 15:47 Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu
4
strength of the installation location.
The base structure must prevent collapsing under the device weight.
Do not cover any ventilation openings of the device.
Ensure proper ventilation of the room where the batteries are installed (this also
applies to units with integrated batteries).
CAUTION! Required air flow venting room
Q = 0,013 * C [m3/h] C - capacity in Ah
C) Power supply and receiver systems
The systems shall be designed and erected only by properly licensed and
qualified personnel.
CAUTION! The user shall ensure that the electrocution protection
system meets the applicable requirements of local laws.
CAUTION! Do not connect the PE line to the UPS with copper cable
tips.
The power supply and receiver lines of the UPS shall be isolated.
It is recommended to specifically mark/label the connection outlets to distinguish
those of the isolated UPS network from the mains system outlets.
Connect the UPS to the nearest mains switching board with copper wires in
reinforced shields (e.g. coated cables) or assure an equivalent level of
mechanical protection by applying other engineering measures (e.g. cable trays
or pipes).
CAUTION! Only the Authorised Technical Service may connect the
device to the system and commission it. Otherwise the warranty shall be
void.
The selection of safeguards, wire sizes and disconnector and isolation devices for
installation at the UPS switching room are shown in the installation guidelines
tables.
It is recommended to install an external bypass system (for the service bypass)
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit
5 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2022-09-08 15:47
the topology of which matches the connection diagram of the UPS (see the
instruction manual for the external bypass system) for operating and maintenance
purposes. The bypass system will enable servicing and maintenance of the
device without power interruptions!
The connection system shall be 3 or 5-wire, depending on the UPS model.
CAUTION! Once the connection system has been erected, suitable
verification measurements shall be carried out on the responsibility of
the device buyer.
INSTALLATION GUIDELINES
Consider the device weight when choosing the installation site. The UPS shall only
be operated in rooms where the dust, temperature, and humidity levels are within the
device specifications. Appropriate cooling conditions must be ensured for the UPS to
work properly. For this reason, the ventilation openings of the UPS must be kept
clear and open at all times, and the clearance between the UPS and other objects
shall not be less than 10 cm (see Table 1 for the minimum requirements).
The parameters relevant to the installation guidelines for specific UPS models are
shown in Table 1.
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units
2022-09-08 15:47 Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu
6
Table 1. Installation guidelines for the POWERLINE RT PLUS 6 10 kVA UPS.
PARAMETERS / MODEL
POWERLINE RT PLUS
POWERLINE RT PLUS 6000
POWERLINE RT PLUS 10 000
Apparent / active power
6 kVA / 6 kW
10 kVA / 10 kW
POWER SUPPLY PARAMETERS
Power system topology
1P3W
Rated voltage
230 V AC
Rated current
27,4 A
45,8 A
Rated frequency input
50 Hz
Minimum input wire size
4 mm2
10 mm2
Mains line
protection
Switch fuse
- Fm
32 A gG
50 A gG
OUTPUT PARAMETERS
Output system topology
1P3W
Rated output voltage
230 V AC
Rated current
26,1 A
43,5 A
Minimum output wire size
4 mm2
10 mm2
Output line
protection
Switch
disconnect
or - Qout
32 A
50 A
ENVIRONMENTAL PARAMETERS
Heat release under nominal
operating conditions
< 1100 BTU / h
< 1800 BTU / h
Operating temperature 1)
0 ÷ 40 °C
Storage temperature
0 ÷ 40 °C
Humidity
< 95 %
Elevation
< 1000 m
MECHANICAL PARAMETERS
Dimensions
(height × width × depth)
86 (2U) x 438 x 573 mm
UPS weight
13,3 kg
15,2 kg
Minimum operating clearance
Front: > 100 mm
Sides: > 100 mm
Back: > 100 mm
Note: The manufacturer reserves the right to change the above parameters without notice.
UWAGI:
1) Constant exposure of the battery module to temperatures of +25°C reduces the battery life. Recommended working
temperature: 15 25 °C
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit
7 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2022-09-08 15:47
ELECTRICAL SYSTEM
Prepare the electrical system according to the diagram shown in Fig. 1.
Figure 1. Installation diagram of the POWERLINE RT PLUS 6-10 kVA UPS
Installation diagram symbols:
Fm, Fsb Switch fuses,
Qout, Qsb Switch disconnectors,
PP1, PP2, PP3 Emergency power-off (EPO) push-buttons,
A, B Connection wires.
The list of safeguards and wire sizes used in specific locations for specific UPS
models is shown in Table 2.
Table 2. Safeguards and wire sizes.
MODEL
Fm
Fsb
Qout
Qsb
A
B
POWERLINE RT PLUS 6 kVA
32 A gG
32 A gG
32 A
32 A
4 mm2
10 mm2
POWERLINE RT PLUS 10 kVA
50 A gG
50 A gG
50 A
50 A
10 mm2
10 mm2
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units
2022-09-08 15:47 Pomoc Techniczna, tel.: +48 61 6500 400 www.ever.eu
8
CAUTION! Use LgY wires for the UPS cables.
CAUTION! Follow the phase rotation order when collecting the power
supply line. This applies to all components of the BYPASS switchboard
and the UPS connection.
This UPS has been designed for operation in TN systems
The exact requirements are specified for a local UPS switching
room located directly at the device. Follow the applicable local
requirements when selecting the wire sizes.
CAUTION! Only trained personnel may switch power to the external
bypass system. Switching operations carried out against this procedure
may result in damage to the UPS. The external bypass system operation
is described in a separate documentation, "Instruction manual for the
external bypass system of the POWERLINE RT PLUS 6-10 kVA UPS
units".
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit
9 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2022-09-08 15:47
TECHNICAL ACCEPTANCE
In order to commission the installed device for operation, do the following in witness
of a person authorised for technical acceptance:
Measure the battery voltage.
Measure the output voltage in the mains operating mode.
Test the UPS switching from mains to batteries without interruption of the load
power supply (if possible, test at the target load of the UPS circuit).
Measure the output voltage in the battery operating mode.
If a bypass is installed, train the personnel designated by the buyer in the bypass
operation.
Confirm the completed technical acceptance with the acceptance report and
release the necessary documentation (i.e. the warranty and the Instruction
Manual) to the buyer.