EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
2
TABLE OF CONTENTS
INTRODUCTION .................................................................................................................................................................... 3
GENERAL FEATURES OF THE UPS UNIT ....................................................................................................................... 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ................................................................................................ 5
TECHNICAL DESCRIPTION ............................................................................................................................................. 11
UNPACKING THE PRODUCT ......................................................................................................................................... 11
What’s in the box? ......................................................................................................................................................... 11
ELEMENTS OF THE UPS REAR PANEL .................................................................................................................... 12
BATTERY MODULE DESIGN REAR PANEL ............................................................................................................ 13
PDU (optional equipment) .................................................................................................................................................. 13
HOW IT WORKS ............................................................................................................................................................... 14
USER INTERFACE MENU STRUCTURE ....................................................................................................................... 16
UPS status menu ............................................................................................................................................................ 17
Event log menu .............................................................................................................................................................. 18
Measurements menu ...................................................................................................................................................... 19
Control menu ................................................................................................................................................................. 20
Identification menu ........................................................................................................................................................ 22
Settings menu ................................................................................................................................................................. 22
OPERATION MODES AND WARNINGS ....................................................................................................................... 25
PROTECTION .................................................................................................................................................................... 27
Overload protection ....................................................................................................................................................... 27
Short-circuit protection .................................................................................................................................................. 27
Against overvoltage (Anti-surge) ................................................................................................................................... 28
Thermal protection ........................................................................................................................................................ 28
EPO ............................................................................................................................................................................... 28
UPS UNIT INSTALATION .................................................................................................................................................. 29
ELECTRICAL SYSTEM ON THE PREMISES ................................................................................................................ 29
UNPACKING THE PRODUCT ......................................................................................................................................... 29
INSTALING THE UPS UNIT ............................................................................................................................................ 30
Connecting elements ...................................................................................................................................................... 30
Backfeed protection ....................................................................................................................................................... 31
INSTALLATION OF THE UPS WITH A BATTERY MODULE .................................................................................... 32
INSTALLATION OF THE UPS WITH A BATTERY MODULE RACK VERSION ................................................... 34
DISCONNECTING THE BATTERY MODULE .............................................................................................................. 35
INSTALLATION OF THE PDU (optional equipment) TOWER VERSION .................................................................. 36
INSTALLATION OF THE PDU (optional equipment) RACK VERSION ..................................................................... 39
Starting up the UPS unit (power supply from the mains) ............................................................................................... 40
Starting the UPS up from the battery (cold start) .......................................................................................................... 41
Switching off the UPS .................................................................................................................................................... 41
Switching from MAINS mode to BYPASS mode (service bypass) by means of PDU .................................................. 41
Switching from BYPASS mode (service bypass) to MAINS mode by means of PDU .................................................. 42
PARALLEL SYSTEMS......................................................................................................................................................... 42
INSTALLATION PARALLEL CARD .............................................................................................................................. 43
INSTALLATION OF THE SYSTEM ................................................................................................................................ 45
SYSTEM START-UP ......................................................................................................................................................... 47
SWITCHING OFF THE SYSTEM ..................................................................................................................................... 48
ADDITIONAL FUNCTIONALITIES OF THE UPS UNIT ............................................................................................... 49
DRY CONTACTS .............................................................................................................................................................. 49
DRY IN ........................................................................................................................................................................... 49
DRY OUT ....................................................................................................................................................................... 49
COMMUNICATION WITH EXTERNAL MANAGEMENT/CONTROL SYSTEMS ................................................... 50
COMMUNICATION USING RS232 OR USB .................................................................................................................. 50
SNMP/HTTP NETWORK MANAGEMENT CARD ........................................................................................................ 50
Installation of the management card .............................................................................................................................. 51
OPERATING INSTRUCTIONS .......................................................................................................................................... 52
TESTING BATTERIES...................................................................................................................................................... 53
INTERACTION WITH ELECTRICAL GENERATORS .................................................................................................. 53
STORAGE, MAINTENANCE AND TRANSPORT.......................................................................................................... 54
DISPOSAL ......................................................................................................................................................................... 54
TECHNICAL PARAMETERS ............................................................................................................................................. 56
DIAGNOSTICS OF ERRORS REPORTED BY THE UPS ............................................................................................... 58
LEGAL REGULATIONS AND WARRANTY ................................................................................................................... 62
DECLARATION OF CONFORMITY ............................................................................................................................... 62
WARRANTY ..................................................................................................................................................................... 62
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
3
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
INTRODUCTION
Thank you for purchasing the EVER POWERLINE RT PLUS UPS system. This UPS
unit has been designed and engineered to provide the highest standard of protection
against power failure. We hope that the purchased UPS unit will meet your
expectations.
This manual contains all relevant information to ensure correct and safe operation of
the unit. Please read this manual carefully and thoroughly prior to using the EVER
POWERLINE RT PLUS unit. This will help you operate the unit correctly and safely.
The POWERLINE RT PLUS units were designed for computer servers, small
computer networks, workstations and other electrical, electronic ad IT systems. With
the universal rack / tower housing, the UPS orientation can be changed quickly.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
The POWERLINE RT PLUS UPS units are ON-LINE (VFI) class devices, designed to
work with equipment supplied from ~ 230 VAC single-phase electric power mains.
They provide energy for practically any device whose power rating is not greater than
the UPS unit's power rating.
Alongside their excellent performance and reliability, the POWERLINE RT PLUS
UPS units offer a number of other advantages:
Output active power is equal to apparent power (PF=1).
On-line operation with real double conversion, sine wave output voltage
(ensuring top quality VFI-SS-111 parameters).
The universal rack / tower housing, thanks to which the UPS orientation can be
changed quickly. The LCD's rack / tower mode selection is done via software.
Availability of the ECO mode further improves the efficiency of the power
supply system (through the ability to differentiate between periods with varying
degrees of safeguards).
HID USB communication interface - the UPS can operate with other devices
without the necessity to install software.
Scalability (extension) of autonomous operation time thanks to the ability of
connecting up to 6 battery modules to the UPS.
Possibility to increase the quantity of output sockets by connecting to a PDU.
Power scaling thanks to optional parallel operation (with up to 3 units).
The Start-on-battery function enables the UPS to be started even if power from
the mains is not available ("Cold start").
Remote Emergency Power Off (Remote EPO) functionality which interrupts
power supply from the UPS output to loads in extreme situations or in
emergency (e.g. fire).
Manageable outputs (1 section optional equipment PDU).
Dry Contacts as standard.
Wide range of input voltage.
Adjustable battery charging current from LCD panel and PowerSoft software.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
5
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General considerations
CAUTION! Before starting the procedures described in this manual,
please read the general safety instructions (including the instructions
found in this document), health & safety information, environmental
protection information and legal regulations that may apply. Always
observe the instructions and recommendations found in these
documents.
CAUTION! The user is strictly forbidden from performing any repairs, as
this would constitute a health hazard and may result in death. Any
repairs and replacement of batteries should be conducted only by
qualified service technicians properly authorized pursuant to the valid
legal regulations.
CAUTION! The unit should be operated and stored in conditions
complying with the requirements set in the specification (technical
documentation).
CAUTION! The device is completely disconnected from the mains only
when the power lead is removed from the mains socket (the plug is
removed from the mains socket).
CAUTION! The device works with an external source of continuous
energy (battery modules). Its output may be live, even if it is not
connected to the mains.
CAUTION! The user should place warning labels on all remotely
installed primary isolation switches in order to warn electrical service
technicians that the circuit is powered by a UPS unit. The following (or
equivalent) text should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS
CIRCUIT.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
6
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements, unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the
unit's electrical connections must remain covered (with applicable
covers). Failure to observe this requirement may create hazard
potentially resulting in injury or death for persons who touch such
connectors. It may also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may
cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! The POWERLINE RT PLUS UPS units are not intended to
work directly with medical equipment, life-supporting equipment or any
other equipment that may have effect on health.
B) Installation information and requirements
CAUTION! The POWERLINE RT PLUS UPS units may only be installed
and maintained by suitably qualified service technicians.
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working
and handling electrical equipment up to 1 kV voltage.
CAUTION! Before connecting any cables or making any connections
within the UPS unit or in the electrical system, make sure there is no
dangerous voltage on electrical terminals and cables in the system.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
7
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
CAUTION! The UPS may only be connected to a power system with
indicated rated voltage, with a suitable grounding connection installed.
The facility's electrical system to which the UPS unit is connected must
be fitted with overload and short-circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS
unit's input side, and only TN-S configuration is allowed on the UPS
unit's output side.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be
completely dry before installation and operation. The acclimatization time should
be at least 2 hours.
UPS units and battery packs must not be installed in humid environment.
UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads,
cables, connectors, sockets and plugs, as well as that of the unit itself.
The unit must be connected to a power circuit with a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked),
the unit must be disconnected from the mains before installation or connecting to
other equipment. The power lead may only be reconnected after making all
required connections.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
8
The electric system's grounding conductor leads the leakage current away from
the receivers. The leakage currents of all loads connected to the UPS unit's
output are combined in the UPS unit's power lead. The summary leakage current
may trigger protective devices (RCD) and result in disconnecting power to the
loads.
The UPS is connected in a permanent manner. Consequently, the fixed wiring
should feature a circuit breaker.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when
touching two surfaces with different electrical potentials.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in
which the UPS is operating.
To minimize the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All instructions must be executed step by step. If any problems emerge when
executing the instructions given in this document, please contact EVER service
support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective
grounding.
There may be voltage on the UPS unit's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the unit's internal batteries and/or battery packs).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
9
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
WARNING: This is a C3 category UPS. For commercial and industrial use in
secondary environment. Additional precautions or limitations in installation may be
required to prevent the emission of interferences.
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Only qualified service
technicians may perform maintenance works.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from
the mains (from terminals of the electrical power supply), parts inside the UPS
unit remain connected to the batteries, which may create hazards. Disconnect the
battery and/or battery packs before carrying out any servicing and/or
maintenance. Make sure there is no dangerous voltage on the DC circuit internal
elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.
CAUTION - Risk of electric shock! Dangerous voltage may be present between
the battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
remove jewelry, watches, rings and other metal items,
only use tools with insulated handles.
When replacing the battery, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
Always dispose of used batteries according to relevant instructions.
WARNING: Disposing of batteries in a fire may result in explosion.
WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and
parameters.
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
10
E) Transport and packaging requirements
Exercise particular care when transporting the equipment, due to its heavy weight.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be
recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the battery has not been recharged. In such
cases always contact service support.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
11
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
TECHNICAL DESCRIPTION
UNPACKING THE PRODUCT
The UPS unit must be properly examined upon delivery or handover. Although the
product is carefully packaged, the appliance could have been damaged due to
shocks experienced during transport. Should any product damage be discovered, the
carrier or the vendor must be notified immediately, and a protocol must be made,
with photos of the damage.
Keep the packaging for future transport operations.
CAUTION! Water vapor may condensate on the UPS unit's elements if
packaging is removed from the device in low temperatures. Do not install
the UPS until its interior and housing are completely dry (electric shock
risk).
What’s in the box?
Check carefully the contents of the packaging. The packaging should contain:
- the UPS unit,
- tower type supports (2 pcs) for installing the unit vertically,
- 1 x USB cable,
- a warranty card,
- a user's guide,
- EPO jumper
- Dry contact jumper
- Side brackets (2 pcs) for mounting the UPS in the cabinet (Rack). The brackets
must be used together with the Rack Kit (optional equipment).
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
12
ELEMENTS OF THE UPS REAR PANEL
Figure 1 present the elements found in rear panels of POWERLINE RT PLUS
6000 / 10000 units.
Fig 1: View of the rear panel of POWERLINE RT PLUS 6000 /10 000
1. Intelligent card slot (SNMP card,
dry contact)
2. USB communication port
3. Dry contact
(1 dry IN, 1 dry OUT)
4. RS232 communication port
5. EPO connector
6. RJ11 connect to PDU
7. Parallel card (optional)
8. Output circuit fuse sockets
IEC 320 C13 (10 A)
9. Output sockets IEC 320 C13 (10 A)
10. Input / Output terminal (4pole IPL, IPN,
OPL, OPN, PE is screw)
11. EBM connector
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
13
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
BATTERY MODULE DESIGN REAR PANEL
Figure 2 present the elements found in rear panels of battery module for
POWERLINE RT PLUS 6000 / 10000 units.
Fig 2: View of the rear panel of the battery module for
POWERLINE RT PLUS 6000 /10 000
1. Fuse board cover
2. EBM plug
3. EBM connector
PDU (optional equipment)
An external PDU panel can be connected to UPS, which is equipped with a manual
BYPASS switch and additional IEC 320 C13 and IEC 320 C16 sockets. The PDU
elements are shown in Figs. 3-4.
Fig 3: View of the PDU front panel
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
14
Fig 4: View of the PDU - rear panel
1. Non-controlled output sockets:
2x IEC 320 C13 (10 A)
1x IEC 320 C19 (16 A)
2. Controlled output sockets:
2x IEC 320 C13 (10 A)
1x IEC 320 C19 (16 A)
3. Maintenance bypass switch
4. Maintenance switch cover
5. Input / Output terminal connected to power and
load (4pole IPL, IPN, OPL, OPN. PE is screw)
6. Input switch
7. Input / Output terminal connected to UPS
(4pole IPL, IPN, OPL, OPN. PE is screw)
8. RJ11 (connect to UPS, only for RT UPS)
HOW IT WORKS
The user interface is the control panel (Fig. 5), in which there are: LCD display with
LEDs indicating the status of the power supply and function keys. Table 1 presents
the description of the buttons of the control panel. The significance of individual LED
indicators and the ways in which each mode of operation is signalled is shown in
table 2. The UPS unit also uses sound chimes for individual device states
(see Table 3).
The front panel of the UPS unit presents useful information on the current functional
state of the UPS unit: the operation mode, the input and output voltage values, the
load level, the battery charge level, alarms and messages.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
15
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
Fig 5: View LCD POWERLINE RT PLUS 6000 /10 000
Table 1. Functions of the control panel buttons
Button
Function
Descriptions
Turn on
When the unit is powered on and stayed in Bypass mode, press this
button for >1s can turn on the UPS.
Turn off
Press this button >3s can turn off the UPS.
Cold start
Starting the
UPS without
the mains
voltage
To start the UPS up when there is no voltage in the mains press and
keep this button depressed for over 100 ms. Within < 15 s, press and
hold button again for at least 1s the UPS will switch to battery
operation.
Clear fault
When the unit is in fault mode, press this button for >1s to stop alarm
and clear fault
Scroll up
Press this button for >100ms&<1s to scroll up the menu option.
Scroll down
Press this button for >100ms&<1s to scroll down the menu option.
Enter next
menu tree
Press this button for >100ms&<1s to select the present menu option,
or enter next menu, but do not change any setting.
Select one
menu option
Press this button for >100ms&<1s to select the present menu option,
or enter next menu, but do not change any setting.
Confirm the
present setting
Press this button for >1s to confirm the edited options and change the
setting.
Enter to main
menu
When the default UPS status screen is displayed, press this button
for more than 1 second to enter the main menu.
Mute buzzer
Press this button for > 2s to mute the buzzer temporarily, once new
warning /fault is active or UPS reenters into bypass mode or battery
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
16
mode, buzzer will work again
Exit main
menu
Press this button for > 100ms & < 2s to exit the present menu to
default system status display menu or the higher level menu without
executing a command or changing a setting
Table 2. Visual signaling of specific states of the UPS unit
Status UPS
NORMAL LED
(green)
BATTERY LED
(orange)
BYPASS LED
(orange)
FAULT LED
(red)
Standby Mode
Bypass Mode
Turning on UPS
Δ
Δ
Δ
Δ
Online Mode
Battery Mode
ECO Mode
Battery test
Δ
Δ
Δ
Δ
Fault
Warning
: Lightened constantly
Δ: Lightened circularly (NORMAL-BATTERY-BYPASS-FAULT-NORMAL-… )
: Flashing
: Depended on the fault / warning status or other status (LED Lightened constantly or flashing)
Table 3. Sound signals for specific states of the UPS unit
Event
Acoustic signal
Fault active
Continous
Over Load Warning active
2 Beep every second
Other Warning active
Beep every second
Battery Mode
Beep every 4 seconds, if battery low, buzzer Beep every second
BYPASS Mode
Beep every 2 minutes
USER INTERFACE MENU STRUCTURE
The menu structure of POWERLINE RT PLUS units is show in Fig. 6. The structure
of the main menu consists of 6 branches (menus): menu UPS status, menu Event
log, menu Measurements, menu Control, menu Identification, menu Settings.
To navigate to the main menu in the tree from, press and hold the button for
less than 1 s in the default functional state screen of the UPS unit.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
17
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
By press or <1s to the next windows in the submenu.
When pressing <1s the display would enter to selected next menu.
To go back to the previous main menu window, press for at least 1 s.
All screens shown on the LCD display are described in further sections of the
manual.
Fig 6: Main menu tree
UPS status menu
The primary UPS Status menu window consists of the same elements as the default
UPS functional state summary menu. By press or <1s to the next windows in
the submenu. The status menu structure is show in Fig. 7.
To go back to the previous main menu window, press for at least 1 s.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
18
Fig 7: Status menu
Event log menu
By pressing (<1s) on the menu of Event log, the display would enter the next
event menu tree.
All the previous events, alarm and fault have been recorded here. The information
includes the illustration, the event code, and the precise time of UPS when the event
happened (fig. 8).
By press or <1s, all the events could be displayed one by one. The max
number of record is 100, when the number is larger than 100, the latest will replace
the previous.
To go back to the previous main menu window, press for at least 1 s.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
19
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2020-03-20 13:06
Fig 8: Event log menu
Measurements menu
By pressing (< 1s) on the menu of Measurement, the display would enter the
next measurement menu tree (fig. 9). This menu displays the following values:
battery remaining time (window visible only when this function is activated in the
Settings menu), output voltage and frequency, output current, load level, input
voltage and frequency, etc.
By press or <1s to the next windows in the submenu.
To go back to the previous main menu window, press for at least 1 s.
EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
20
Fig 9: Measurements menu
Control menu
To enter the next Control menu window, press in the Control menu (fig. 10). This
menu allows the user to activate the following operations:
1. Running the battery test: the command to perform a quick (10-second) battery
test. Before testing, check that the UPS is in network mode without active alarms
and that the load connected to the UPS is higher than 10%.
2. Shutdown of a UPS operating in parallel system. The menu is visible only when
parallel power supplies are connected.
3. Failure status reset: in case of a failure, the UPS unit enters the failure mode and
a sound alarm is generated. To return to the normal state, navigate to the
mentioned menu and reset the error status. The UPS unit will finish generating
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56