Ever UPS POWERLINE RT 1000/2000/3000 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
2
TABLE OF CONTENTS
TABLE OF CONTENTS ...................................................................................................................................... 2
INTRODUCTION ................................................................................................................................................. 3
GENERAL FEATURES OF THE UPS UNIT ................................................................................................... 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ............................................................................ 6
TECHNICAL DESCRIPTION .......................................................................................................................... 12
UNPACKING THE PRODUCT ...................................................................................................................... 12
What’s in the box? ........................................................................................................................................13
ELEMENTS OF THE UPS - REAR PANEL .................................................................................................. 15
POWERLINE RT 1000 .................................................................................................................................15
POWERLINE RT 2000 .................................................................................................................................16
POWERLINE RT 3000 .................................................................................................................................17
Battery module POWERLINE RT 1000 ........................................................................................................18
Battery module POWERLINE RT 2000/3000 ...............................................................................................19
HOW IT WORKS ............................................................................................................................................ 20
MENU AND FUNCTIONS ............................................................................................................................. 22
INSTALLATION ................................................................................................................................................ 24
MECHANICAL INSTALLATION ................................................................................................................. 25
INSTALLATION OF THE UPS AND BATTERY MODULES VERTICALLY ........................................... 25
ELECTRICAL SYSTEM ................................................................................................................................. 26
Input installation...........................................................................................................................................27
Output installation ........................................................................................................................................28
POWER CONNECTIONS ............................................................................................................................... 29
Connecting an external battery module ........................................................................................................29
Connecting the UPS to the mains .................................................................................................................30
UPS START-UP .............................................................................................................................................. 30
Initial procedure of starting the UPS up ......................................................................................................30
UPS Shut-down procedure ...........................................................................................................................31
DESCRIPTION OF OPERATION OF THE UPS ........................................................................................... 31
MODES OF OPERATION .............................................................................................................................. 31
Stand-by mode ........................................................................................................................................ 31
Bypass mode ........................................................................................................................................... 31
Mains mode............................................................................................................................................. 32
Back-up mode ......................................................................................................................................... 32
Frequency conversion mode ................................................................................................................... 32
ECO Mode .............................................................................................................................................. 33
Error mode .............................................................................................................................................. 33
ADDITIONAL FUNCTIONS .......................................................................................................................... 34
REMOTE EMERGENCY POWER OFF (EPO) / REMOTE ON/OFF (ROO) ............................................... 35
COMMUNICATION WITH EXTERNAL MANAGEMENT/CONTROL SYSTEMS ............................... 36
RS232 PORT AND STATUS SIGNALING.................................................................................................... 36
USB port ........................................................................................................................................................... 37
SNMP/HTTP NETWORK MANAGEMENT CARD ..................................................................................... 37
POWERSOFT .................................................................................................................................................. 37
OPERATING REMARKS ................................................................................................................................. 39
CLEANING ..................................................................................................................................................... 39
STORAGE OF THE UPS ................................................................................................................................ 39
TESTING BATTERIES ................................................................................................................................... 39
BATTERY REPLACEMENT ......................................................................................................................... 40
Replacing UPS internal batteries .................................................................................................................40
Battery disposal ............................................................................................................................................43
TECHNICAL PARAMETERS .......................................................................................................................... 44
TROUBLE SHOOTING .................................................................................................................................... 47
LEGAL REGULATIONS AND WARRANTY ................................................................................................ 48
DECLARATION OF CONFORMITY ............................................................................................................ 48
WARRANTY ................................................................................................................................................... 48
Instruction manual for POWERLINE RT 1-3 kVA UPS units
3 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
INTRODUCTION
Thank you for purchasing the EVER POWERLINE RT UPS. Please familiarise
yourself with this instruction manual before you begin using the device. This manual
contains all relevant information to ensure correct and safe operation of the unit.
Please read this manual carefully and thoroughly prior to using the EVER
POWERLINE RT. This will help to operate the unit and correctly and safely. This
EVER POWERLINE RT UPS system has been designed and engineered to provide
the highest standard of protection against power failure. We hope that the purchased
UPS will meet your expectations.
A series of hi-tech, on-line (VFI) UPS units (uninterruptable power system), designed
with double conversion topology, for excellent protection of the connected receivers.
The UPS protects sensitive equipment and systems from common problems such as
power outages, drops and interruptions in the mains, surges and other faulty
conditions in the power supply line.
EVER POWERLINE RT series UPS units are mainly used with network devices,
servers, workstations and other electric, electronic and IT devices.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
Alongside their excellent performance and reliability, the POWERLINE RT range of
UPS units offers a number of other advantages which include:
On-line real double conversion and sine wave output voltage.
Possibility of selection of high performance operation (ECO).
Scalability (extension) of autonomous operation time thanks to the ability of
connecting more battery modules to the UPS (up to 4 units - optional).
Remote Emergency Power Off (Remote EPO) functionality which interrupts
power supply from the UPS output to loads in extreme situations or in
emergency (e.g. fire).
Remote On/Off (ROO) function for remotely starting and shutting down the UPS.
Wide range of input voltage.
Users can choose to install the unit in one of the two variants: Rack or Tower.
Compact size (excellent power to size ratio).
Standard communication functions: an RS 232 communication port, a USB
communication port.
Optional extension cards provide additional communication functionalities.
The POWERLINE RT UPS systems consist of the following functional blocks:
rectifier,
inverter,
battery set,
microprocessor-based control system with measurement circuits,
automated by-pass system (static BYPASS),
Instruction manual for POWERLINE RT 1-3 kVA UPS units
5 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
Fig. 1: Simplified block diagram of the UPS unit
The series of on-line UPS units with double conversion topology provides excellent
protection of the connected receivers, e.g. IT systems, and filters interferences in the
power supply line. The AC input may be corrected depending on the wave of the
power supply voltage by a high power factor correction circuit. Thanks to PWM
control, the input voltage may take the form of clean, stable sine.
If the mains parameters are faulty, the controller will shut down the AC/DC section
and promptly start the DC/DC unit, in order to maintain the uninterrupted operation of
the DC/AC section (inverter). Once the mains parameters are back to correct values,
the DC/DC section stops and AC/DC takes over again. This way, if the UPS is on,
the receiver is always protected by the inverter, with no interruptions.
The UPS features an external bypass to provide power to receivers directly from the
mains, in case the UPS is damaged.
The UPS has a built-in battery charger that will be charging the battery if the network
parameters are acceptable, except when the unit is in the back-up mode or in the
battery test mode.
BKF relay
Charger
Batteries
EMI
filter
DC bus
External battery
pack connector
EMI
filter
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
6
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General information
CAUTION! Before starting the procedures described in this manual,
please read the general safety instructions (including the instructions
found in this document), health & safety information, environmental
protection information and legal regulations that may apply. Always
observe the instructions and recommendations found in these
documents.
CAUTION! It is strictly forbidden for the user to perform any repairs, as
this would constitute a health hazard and may result in death. Any
repairs and replacement of batteries should be carried out only by
suitably qualified service technicians, with professional licences required
by law.
CAUTION! The unit should be operated and stored in conditions
complying with the requirements set in the specification (technical
documentation).
CAUTION! The device is completely disconnected from the mains only
when the power lead is removed from the mains socket (the plug is
removed from the mains socket).
CAUTION! The unit is equipped with an internal power source (batteries)
or it may operate in combination with a fixed, external source of power
(battery packs). Dangerous voltage may be present at the output
terminal(s), even if the unit has been disconnected from the mains.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
7 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
CAUTION! The user should place warning labels on all remotely
installed primary isolation switches in order to warn electrical service
technicians that the circuit is powered by a UPS unit. The following (or
equivalent) text should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS
CIRCUIT.
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the
unit's electrical connections must remain covered (with applicable
covers). Failure to observe this requirement may create hazard
potentially resulting in injury or death for persons who touch such
connectors. It may also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may
cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! The POWERLINE RT range of UPS units is not intended to
work directly with medical equipment, life-supporting equipment or any
other equipment that may have effect on health.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
8
B) Installation information and requirements
CAUTION! The POWERLINE RT range of UPS units may only be
installed and maintained by suitably qualified service technicians.
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working
and handling electrical equipment up to 1 kV voltage.
CAUTION! Before connecting any cables or making any connections
within the UPS unit or in the electrical system, make sure there is no
dangerous voltage on electrical terminals and cables in the system.
CAUTION! The UPS may only be connected to a power system with
indicated rated voltage, with a suitable grounding connection installed.
The facility's electrical system to which the UPS unit is connected must
be fitted with overload and short-circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS
unit's input side, and only TN-S configuration is allowed on the UPS
unit's output side.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be
completely dry before installation and operation. The acclimatization time should
be at least 2 hours.
UPS units and battery packs must not be installed in humid environment.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
9 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads,
cables, connectors, sockets and plugs, as well as that of the unit itself.
The unit must be connected to a power circuit with a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked),
the unit must be disconnected from the mains before installation or connecting to
other equipment. The power lead may only be connected again after making all
required connections.
The electric system's grounding conductor leads the leakage current away from
the receivers. The leakage currents of all loads connected to the UPS unit's
output are totalized in the UPS unit's power lead. The summary leakage current
may trigger protective devices (RCD) and result in disconnecting power to the
loads.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when
touching two surfaces with different electrical potentials.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in
which the UPS is operating.
To minimise the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
10
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All these instructions must be executed step by step. If any problems emerge
when executing the instructions given in this document, please contact EVER
service support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective
grounding.
There may be voltage on the UPS unit's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the unit's internal batteries and/or battery packs).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
WARNING: This is a C3 category UPS. For commercial and industrial use in
secondary environment. Additional precautions or limitations in installation may be
required to prevent the emission of interferences.
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Only qualified service
technicians may perform maintenance works.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from
the mains (from terminals of the electrical power supply), parts inside the UPS
unit remain connected to the batteries, which may create hazards. Disconnect the
battery and/or battery packs before carrying out any servicing and/or
maintenance. Make sure there is no dangerous voltage on the DC circuit internal
elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.
CAUTION - Risk of electric shock! Dangerous voltage may be present between
the battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
remove jewelry, watches, rings and other metal items,
only use tools with insulated handles.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
11 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
When replacing batteries, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
Always dispose of used batteries according to relevant instructions.
WARNING: Disposing of batteries in a fire may result in explosion.
WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and
parameters.
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
E) Transport and packaging requirements
Exercise particular care when transporting the equipment, due to its heavy weight.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be
recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the batteries have not been recharged. In
such cases always contact service support.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
12
TECHNICAL DESCRIPTION
UNPACKING THE PRODUCT
Keep the packaging for future transportation operations.
The UPS unit must be properly examined upon delivery or handover. Although the
product is solidly packaged, the appliance could have been damaged due to shocks
experienced during transport. If any of the units is damaged during transportation, a
complaint for transportation damage should be filed. Should any product damage be
discovered upon receiving the product, the carrier or the vendor must be notified
immediately (a complaint should be filed).
CAUTION! The product is supplied with the batteries connected.
CAUTION! Water vapor may condensate on the UPS unit's elements if
packaging is removed from the device in low temperatures. Do not install
the UPS until its interior and housing are completely dry (electric shock
risk).
CAUTION! The appliance is heavy. Considerable care is required when
it is being unpacked or moved.
Exercise caution when moving or unpacking the device. Refrain from
unpacking its individual elements until they are required for installation.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
13 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
What’s in the box?
Check carefully the contents of the packaging. The packaging should contain:
a) UPS POWERLINE RT 1000, 2000:
- the UPS unit,
- 2 sets of Tower supports for installing the unit vertically,
- 1 x power cord CEE7/7 - IEC 320 C13, 10A,
- 2 x power cords IEC C13 - IEC C14 10A,
- 1 x USB cable,
- 1 x RS232 cable (communication with PC),
- 1 x RS232 cable (status signaling),
- warranty card,
- user's guide.
b) UPS POWERLINE RT 3000:
- the UPS unit,
- 2 sets of Tower supports for installing the unit vertically,
- 1 x power cord CEE 7/7 - IEC 320 C19, 16A,
- 2 x power cords IEC C13 - IEC C14 10A,
- 1 x power cord IEC C19 - IEC C20 16A,
- 1 x USB cable,
- 1 x RS232 cable (communication with PC),
- 1 x RS232 cable (status signaling),
- warranty card,
- user's guide.
c) Rack Kit for installing UPS units / battery modules in rack cabinets
(optional):
- a set of elements for installing the unit in a rack cabinet:
- 2 front rack supports with installation accessories,
- 2 sliding rack guides (with profiles and their screws),
- a printed manual with pictures for installing UPS units / battery modules in rack
cabinets, with instructions for placing the - LCD panel horizontally.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
14
d) SNMP card (optional):
- SNMP card,
- 1 x cable RJ - RS232,
- a CD with software,
- a warranty card.
e) Battery module POWERLINE RT 1000 & 2000/3000:
- 1 battery module,
- 1 power cord,
- 1 battery module detection cable for automatic detection of the number of
connected modules (RJ11),
- 2 sets of Tower supports for installing the unit horizontally,
- an element for linking the battery module with another module or the UPS,
- a warranty card.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
15 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
ELEMENTS OF THE UPS - REAR PANEL
POWERLINE RT 1000
1. RS232 port
2. USB port
3. ROO/EPO terminals
4. Fan
5. RJ11 port battery module detection
6. Power supply socket for connecting an
external battery module
7. SNMP card slot
8. Input circuit safeguard
automatic fuse
9. Power supply input socket
10. Non-controlled output socket 10A
11. Controlled output sockets
(group 1 and 2) 10A
12. Earthing clamp
Fig. 2: View of the rear panel elements in POWERLINE RT 1000 UPS.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
16
POWERLINE RT 2000
1. SNMP card slot
2. Fan
3. Power supply socket for
connecting an external battery
module
4. RJ11 port battery module
detection
5. RS232 port
6. Input circuit safeguard
- automatic fuse
7. Power supply input socket
8. Non-controlled output socket 10A
9. Controlled output sockets
(group 1 and 2) 10A
10. ROO/EPO terminals
11. USB port
12. Earthing clamp
Fig. 3: View of the rear panel elements in POWERLINE RT 2000 UPS.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
17 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
POWERLINE RT 3000
1. SNMP card slot
2. Fan
3. Fan
4. Power supply socket for
connecting an external
battery module
5. RJ11 port battery
module detection
6. RS232 port
7. Input circuit safeguard
automatic fuse
8. Power supply input socket
9. Non-controlled output
socket 10A
10. Controlled output sockets
(group 1 and 2) 10A
11. Output socket 16A
12. ROO/EPO terminals
13. USB port
14. Earthing clamp
Fig. 4: View of the rear panel elements in POWERLINE RT 3000 UPS.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
18
Battery module POWERLINE RT 1000
1. Battery module power supply socket
2. RJ11 port battery module detection
3. Battery module power supply socket
4. Fuse 70 A / 80 V DC
Fig. 5: View of the rear panel elements in POWERLINE RT 1000 UPS battery module.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
19 www.ever.eu Pomoc Techniczna, tel.: +48 61 6500 400 2016-07-13 12:09
Battery module POWERLINE RT 2000/3000
1. Battery module power supply socket
2. RJ11 port battery module detection
3. Battery module power supply socket
4. Fuse 70 A / 80 V DC
Fig. 6: View of the rear panel elements in POWERLINE RT 2000 / 3000 UPS battery module.
Instruction manual for POWERLINE RT 1-3 kVA UPS units
2016-07-13 12:09 Technical Support, tel.: +48 61 6500 400 www.ever.eu
20
HOW IT WORKS
Fig. 7 shows POWERLINE RT front panel elements. The UPS features a 4-key
control panel, an LCD display and signaling LEDs.
Fig. 7: View of the front panel elements in POWERLINE RT UPS.
1. Green LED - input voltage is available.
2. Orange LED - signalization of bypass and ECO modes, and warnings
displayed on the LCD, e.g. in overload conditions.
3. Red LED - signalization of the most critical messages related to the unit's
operation, e.g. short circuit, internal error.
4. LCD display
5. Exit -
6. Scroll -
7. Start / shut down key. Back-up mode LED (key with green backlight)
8. Confirmation key
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48