Ever UPS POWERLINE DARK 10-200/33 Installation guide

Category
Uninterruptible power supplies (UPSs)
Type
Installation guide
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
2
INDEX
INDEX .................................................................................................................................................................... 2
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ............................................................................ 3
REQUIREMENTS CONCERNING THE PREPARATION OF THE POWER SUPPLY AND
RECEIVING INSTALLATION .......................................................................................................................... 3
INSTALLATION GUIDELINES ........................................................................................................................ 6
ELECTRICAL INSTALLATION ...................................................................................................................... 9
TECHNICAL ACCEPTANCE .......................................................................................................................... 13
NOTES ................................................................................................................................................................. 13
Installation guidelines for POWERLINE DARK 33 UPS units
3 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
Make sure to read the safety guidelines and recommendations in the UPS
unit's complete operating manual before commencing any connecting
operations.
REQUIREMENTS CONCERNING THE PREPARATION OF
THE POWER SUPPLY AND RECEIVING INSTALLATION
A) Transport requirement
CAUTION! Pay extra attention during the transport, unloading and
installation of the unit.
The UPS units must be transported in the position indicated on the packaging.
The device must be protected against weather conditions (rain).
Prolonged transportation and storage in temperatures below 0
C and above
25
C is not recommended, because it may shorten the battery's lifespan and
there is possibility of water vapour condensation.
The device's considerable weight and dimensions require adequate transport
conditions (sufficient number of workers, a forklift truck, a communication
pathway).
CAUTION! Contact the service department if any damage that might
affect the operation of the device is identified.
B) Location
CAUTION! The user is responsible for selecting the place of installation
and adequate working conditions.
It is recommended to install the UPS in a separate room (a working device emits
a monotonous sound and should be protected from unauthorized access).
The device should not be exposed to excessively low or high temperature,
because this may shorten the lifespan of batteries (optimal temperature is
18 ÷ 25 ºC).
The device should not be installed in rooms where dust, caustic or inflammable
atmosphere is present or in high humidity (the humidity is recommended to be
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
4
below 90%, with no condensation).
If the device is to be installed in the attic or on raised floor, the load bearing of
such structures must also be taken into account when selecting the place of
installation.
The floor's structure must prevent the device from collapsing.
The device's ventilation openings must not be covered.
The following clearances around the device are recommended:
- 0.8 m from each side - for devices not fixed to the floor,
- 1.0 m from each side - for devices fixed to the floor.
The room where batteries are installed must be adequately ventilated (also
applies to UPS units with external batteries).
CAUTION! The required air flow for ventilating the room
Q = 0.026 * C [m3/h] C - capacity in Ah
C) Power supply and receiving installation
The design and the installation itself must only be made by properly qualified
personnel.
CAUTION! The user shall provide anti-shock protection pursuant to the
local legal requirements.
CAUTION! Copper wire tips must not be used when connecting the PE
circuit to the UPS.
The UPS unit's power supply and receiving circuits must be separated.
It is recommended that the sockets for the guaranteed, isolated network are
differentiated in relation to the basic network.
Copper wires in high-strength insulation (e.g. sheathed cables) should be used for
the section between the UPS and the closest power distribution board or a similar
level of protection should be provided by means of other technical solutions (e.g.
installation trays or corrugated conduits).
Installation guidelines for POWERLINE DARK 33 UPS units
5 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
CAUTION! Connecting to the installation for the first time and the first
start-up must be done only by the authorized service. Failure to observe
this condition voids the warranty.
The method of selecting protection devices, the sections of wires and the required
disconnecting devices to be installed in the UPS unit's switching board are
specified in tables showing installation guidelines.
Due to operating and service reasons it is recommended to make an external
service bypass that is topologically consistent with the connection diagram of a
given UPS model (operating manual of the external bypass). Providing such a
system allows servicing the UPS without interrupting the supply to the devices!
Depending on the UPS unit, the installation should use 3 or 5 wires.
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
6
INSTALLATION GUIDELINES
The UPS unit's weight should be taken into account when choosing the installation
location. The UPS should only be used in rooms where the dust, temperature and
humidity conditions conform to the unit’s specification. Proper cooling conditions
must be provided to ensure the UPS unit’s correct operation. Consequently, the UPS
unit’s ventilating openings must be always uncovered and the distance between the
UPS and other items should be no less than 50 cm (minimal requirements for specific
models are presented in Table 1 and Table 2).
Parameters relevant for installation guidelines for specific UPS models are presented
in Table 1 and Table 2.
CAUTION! The UPS must not be installed near inflammable materials!
Once the UPS is placed in its target location, use the adjustable feet to fix the unit in
place. To do this, remove the feet by turning them clockwise with a wrench. Make
sure that all four feet are at the same height and that the UPS cannot be moved.
Installation guidelines for POWERLINE DARK 33 UPS units
7 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
Table 1. Installation guidelines for UPS POWERLINE DARK 33 10 40 kVA.
PARAMETERS / MODEL
POWERLINE DARK 33
Model 10k
Model 15k
Model 20k
Model 30k
Model 40k
Apparent / active power
10 kVA
10 kW
15 kVA
15 kW
20 kVA
18 kW
30 kVA
27 kW
40 kVA
36 kW
POWER SUPPLY PARAMETERS
Power system topology
3P5W
Rated voltage
3 x 400 V AC
Rated current
18 A
28 A
35 A
55 A
70 A
Rated frequency
input
50 Hz
Minimum input wire size
2.5 mm2
6 mm2
10 mm2
16 mm2
25 mm2
Mains line
protections
Switch fuse
- Fm
20 A gG
32 A gG
40 A gG
63 A gG
80 A gG
Bypass line
protections
Switch fuse
- Fb
20 A gG
32 A gG
40 A gG
63 A gG
80 A gG
OUTPUT PARAMETERS
Output system topology
3P5W
Rated output voltage
3 x 400 V AC
Rated current
15 A
23 A
30 A
45 A
60 A
Minimum output wire size
2.5 mm2
6 mm2
10 mm2
16 mm2
25 mm2
Output line
protections
Switch
disconnect
or - Qout
20 A
32 A
40 A
63 A
80 A
ENVIRONMENTAL PARAMETERS
Heat release under nominal
operating conditions
< 1800 BTU / h
< 2700 BTU / h
< 3300 BTU / h
< 4900 BTU / h
< 5200 BTU / h
Operating temperature 1)
0 ÷ 40 °C
Storage temperature
-40 ÷ +70 °C
Humidity
< 95 %
Altitude above sea level
< 1000 m
MECHANICAL PARAMETERS
Dimensions
(H x W × D)
715 x 250 x 840 mm
1335 x 350 x 738 mm
1400 x 500
x 840 mm
UPS unit's weight 2)
140 kg
177 kg
228 kg
Minimum operating clearance 3)
Front: > 800 mm
Sides: > 500 mm
Rear: > 500 mm
Note: The manufacturer reserves the right to change the above listed parameters without notice.
REMARKS:
1) 5 ÷ 35 °C with internal batteries. Constant exposure to ambient temperature over +25°C reduces the battery’s lifespan.
2) Unit's weight for a typical battery set VRLA 12 V / 7 Ah for 10-15kVA and VRLA 12 V / 12 Ah for 20-40kVA. The weight
depends on the type and number of batteries.
3) The following service clearances around the device are recommended: front > 1000 mm, side: > 1000 mm, rear: > 1000 mm.
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
8
Table 2. Installation guidelines for UPS POWERLINE DARK 33 60 200 kVA.
PARAMETERS / MODEL
POWERLINE DARK 33
Model 60k
Model 80k
Model 100k
Model 120k
Model 150k
Model 200k
Apparent / active power
60 kVA
54 kW
80 kVA
72 kW
100 kVA
90 kW
120 kVA
108 kW
150 kVA
135 kW
200 kVA
180 kW
POWER SUPPLY PARAMETERS
Power system topology
3P5W
Rated voltage
3 x 400 V AC
Rated current
96 A
128 A
159 A
191 A
239 A
319 A
Rated frequency
input
50 Hz
Minimum input wire size
35 mm2
70 mm2
120 mm2
120 mm2
150 mm2
240 mm2
Mains line
protections
Switch fuse
- Fm
100 A gG
160 A gG
200 A gG
200 A gG
250 A gG
355 A gG
Bypass line
protections
Switch fuse
- Fb
100 A gG
160 A gG
200 A gG
200 A gG
250 A gG
355 A gG
OUTPUT PARAMETERS
Output system topology
3P5W
Rated output voltage
3 x 400 V AC
Rated current
91 A
121 A
152 A
182 A
227 A
303 A
Minimum output wire size
35 mm2
70 mm2
120 mm2
120 mm2
150 mm2
240 mm2
Output line
protections
Switch
disconnect
or - Qout
100 A
160 A
200 A
200 A
250 A
355 A
ENVIRONMENTAL PARAMETERS
Heat release under nominal
operating conditions
< 9700
BTU / h
< 10300
BTU / h
< 12800
BTU / h
< 19400
BTU / h
< 19200
BTU / h
< 25600
BTU / h
Operating temperature 1)
0 ÷ 40 °C
Storage temperature
-40 ÷ +70 °C
Humidity
< 95 %
Altitude above sea level
< 1000 m
MECHANICAL PARAMETERS
Dimensions
(H x W × D)
950 x 600
x 980 mm
1150 x 600 x 980 mm
1400 x 600
x 980 mm
1600 x 650 x 960 mm
UPS unit's weight 2)
203 kg
253 kg
315 kg
337 kg
383 kg
Minimum operating clearance 3)
Front: > 800 mm
Sides: > 500 mm
Rear: > 500 mm
Note: The manufacturer reserves the right to change the above listed parameters without notice.
REMARKS:
1) Constant exposure to ambient temperature over +25°C reduces the battery’s lifespan.
2) UPS unit's weight without batteries.
3) The following service clearances around the device are recommended: front > 1000 mm, side: > 1000 mm, rear: > 1000 mm.
Installation guidelines for POWERLINE DARK 33 UPS units
9 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
ELECTRICAL INSTALLATION
Depending on whether a bypass line is used, the electrical installation should be
done according to the diagram in Fig. 1 or Fig. 2.
* If a non-factory module is used, a fuse must be applied in the positive and negative
pole lines, as per Table 3.
Fig. 1. Installation diagram for POWERLINE DARK 33
with main line
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
10
* If a non-factory module is used, a fuse must be applied in the positive and negative pole lines, as per Table 3.
Fig. 2. Installation diagram for POWERLINE DARK 33
main line and bypass line
Markings used on installation diagrams:
Fm, Fb, Fsb switch fuses,
Qout, Qsb switch disconnectors,
PP1, PP2, PP3 emergency power off keys (EPO),
A, B, C, D connecting wires.
The Fb switch fuse is installed only if a bypass input is used.
The battery stand should be connected to the POWERLINE DARK 33 60-200 kVA
UPS according to the diagram in Fig. 3.
Installation guidelines for POWERLINE DARK 33 UPS units
11 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
Fig. 3. Diagram for connecting the battery stand to the UPS
POWERLINE DARK 33 60-200 kVA
Fbat1, Fbat2 switch fuses,
Fz jumper (cylindrical metal insert „N”)
The list of protection and sections of wires used in specific locations, depending on
the UPS model, is shown in Table 3.
Table 3. Protections and wire sections
MODEL
Fm, Fb,
Fsb
Fbat1, Fbat2
Qout
Qsb
A
B
C
D
POWERLINE DARK 33
10 kVA
20 A gG
25 A 440 V DC
20 A
2.5 mm2
4 mm2
10 mm2
10 mm2
POWERLINE DARK 33
15 kVA
32 A gG
32 A 440 V DC
32 A
6 mm2
4 mm2
10 mm2
10 mm2
POWERLINE DARK 33
20 kVA
40 A gG
50 A 440 V DC
40 A
10 mm2
10 mm2
10 mm2
10 mm2
POWERLINE DARK 33
30 kVA
63 A gG
63 A 440 V DC
63 A
16 mm2
16 mm2
16 mm2
16 mm2
POWERLINE DARK 33
40 kVA
80 A gG
100 A 440 V DC
80 A
25 mm2
35 mm2
25 mm2
35 mm2
POWERLINE DARK 33
60 kVA
100 A gG
160 A 440 V DC
100 A
35 mm2
70 mm2
35 mm2
70 mm2
POWERLINE DARK 33
80 kVA
160 A gG
200 A 440 V DC
160 A
70 mm2
95 mm2
70 mm2
95 mm2
POWERLINE DARK 33
100 kVA
200 A gG
250 A 440 V DC
200 A
120 mm2
120 mm2
120 mm2
120 mm2
POWERLINE DARK 33
120 kVA
200 A gG
315 A 400 V DC
200 A
120 mm2
185 mm2
120 mm2
185 mm2
POWERLINE DARK 33
150 kVA
250 A gG
355 A 400 V DC
250 A
150 mm2
240 mm2
150 mm2
240 mm2
POWERLINE DARK 33
200 kVA
355 A gG
425 A 400 V DC
355 A
240 mm2
300 mm2
240 mm2
300 mm2
CAUTION! The battery stand should be grounded.
CAUTION! Only LgY wires should be used for the UPS unit's
installations
CAUTION! Phase rotation order should be maintained when connecting
power supply lines. This principle applies to all components of the
bypass switching board and the connection to the UPS.
Installation guidelines for POWERLINE DARK 33 UPS units
2022-09-12 14:18 Technical Assistance, phone: +48 61 6500 400 www.ever.eu
12
The UPS has been designed to operate in a TN installation.
The listed requirements apply for a local UPS switching board
placed directly on the device. Local requirements should be
observed when selecting wire sections.
CAUTION! Only trained personnel may switch the power supply to the
external bypass. Failure to observe the prescribed switching procedure
may damage the UPS. The description of operation of the external
bypass is found in a separate document “Operating Manual for External
Bypass for POWERLINE DARK 33 UPS Units 10-200 kVa”.
Installation guidelines for POWERLINE DARK 33 UPS units
13 www.ever.eu Technical Assistance, phone: +48 61 6500 400 2022-09-12 14:18
TECHNICAL ACCEPTANCE
The following activities must be performed when commissioning the installed device,
in the presence of a person authorized to perform the acceptance:
Measuring the voltage of batteries.
Measuring the output voltage in the mains mode.
Testing the transition of the UPS from the mains mode to the battery mode,
ensuring the continuity of supplying power to the recipients (the tests should be
performed at the target load of the guaranteed circuit, if possible).
Measuring the output voltage in the battery mode.
If a bypass was made, the personnel appointed by the UPS buyer should be
trained in its operation.
The technical acceptance should be confirmed with an acceptance protocol and
the required documentation (warranty, operating manual) should be provided to
the buyer.
NOTES
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13