FläktGroup IPSUM Cable User guide

Category
Coaxial cables
Type
User guide
AIR MANAGEMENT
IPSUM
®
CABLE GUIDE
AIR COMFORT IPSUM®
» CABLE GUIDE
IPSUM® Optimizer IPSUM® Connection unit IPSUM® Router
FläktGroup support: www.flaktwoods.co.uk
See our global website for international support issues
www.flaktgroup.com
+ 46 (0) 36 19 30 03
Unauthorized personnel are not permitted to carry out work on the IPSUM® system.
Individual works should only be carried out by people that are competent or
qualied to do so.
ALWAYS observe local rules and regulations.
When working at heights, all safety requirements and regulations should be
observed.
Make sure that you have read and understood these instructions before starting
to install the IPSUM® system. The owner of the system or the engineer installing it
is responsible for ensuring compliance with the applicable safety regulations.
IPSUM® is an energy and comfort optimisation system and is not a re safety
system. However, IPSUM® includes some re-related functions designed to
support a separate re system.
Warning!
1. General
2. Power and Control
2.1 IPSUM® Main components
2.1.1 IPSUM® Sytem Optimizer/Router
2.1.2 IPSUM® Connection Unit
2.2 Cable lengths
Devices with Modbus communication
Non communication devices
2.3 Cable requirements and power consumptions for devices connected to the IPSUM® Connection Unit
2.4 Calculating the minimum cross sectional area
3. Networks
3.1 TIA/EIA-485 (RS-485)
3.1.1 TIA/EIA-485 (RS-485) Network topologies
3.1.2 Optimizer to Connection Unit wiring (EIA/RS-485), compact mode
3.1.3 Optimizer to Router wiring (EIA/RS-485), full mode
3.1.4 Router to Connection Unit wiring (EIA/RS-485), full mode
3.2 Ethernet (TCP/IP)
3.2.1 Optimizer to Router wiring (Ethernet Private network), full mode
3.2.2 Optimizer to Router wiring (Ethernet Shared network), full mode
3.3 Network de nitions and requirements in detail
3.3.1 EIA/TIA-485 (RS-485)
Cabling
TIA/EIA-485 Speci cation
Topology
Cable Length
3.3.2 Ethernet (TCP/IP)
Cabling
TIA/EIA-568 Speci cation
Cable Length
4. Appendix
4.1 Exampel of cable for Power and Control
4.2 Exampel of cable for TIA/EIA-485 (RS485)
4.3 Exampel of cable for Ethernet
4.4 Standard VAV Application
4.5 Chilled Beam Application
Content
9489 GB 2015.01.14 3 We reserve the right to alter speci cations.
Cable Guide IPSUM®
Cable Guide
9489 GB 2016.01.08 4 We reserve the right to alter speci cations.
IPSUM®
This document is a guide on the different types, sizes, and lengths of cables that can be used for the IPSUM® System, as well
as network topology requirements and useful tips. This does not replace the requirement of an electrician or over-ride any of
the local country regulations and is provided as a guide only.
The document is split into two section covering the cables used for an IPSUM® installation. The  rst covering Power & Control
(0 - 10 V, 24 V & 230 V) and the second covering networks (TIA/EIA-485 (RS-485) & Ethernet).
At the end of the document are appendixes with cable suggestions and typical installations.
1. General
1
Cable Guide
9489 GB 2016.01.08 5 We reserve the right to alter speci cations.
IPSUM®
2
2.1 IPSUM® Main components
2.1.1 IPSUM® System Optimizer/Router
The IPSUM® System Optimizer/Router can both be powered
from either 230 Vac or 24 Vac/dc. The selection is made
using a dip-swich.
When 230 V is used, a phase, neutral and a protective
ground (earth) must be connected. Please follow your
country’s/region’s standard for the wire colours. In the
European Union the phase (L) should be connected to a
brown wire, the neutral (N) to a blue wire and the protective
ground (earth) to the yellow/green wire.
The maximum cable cross sectional area when 230 V
is used is 2.5 mm2 and the recommended minimum is 1.5
mm2. Use cables which are rated for at least 250 V.
The maximum cable cross sectional area when 24 V is
used is 1.5 mm2 and the recommended minimum is 0.5
mm2. Use cables rated for use in low voltage systems.
2.1.2 IPSUM® Connection Unit
The maximum cable cross sectional area when screw termi-
nals are used is 1.5 mm2 and the recommended minimum is
0.5 mm2.
The maximum cable cross sectional area when RJ con-
nectors are used is AWG24 (0.205 mm2) and the recom-
mended minimum is AWG26 (0.128 mm2). The RJ connectors
have two pins for each of the power conductors so the
maximum area can be doubled allowing longer cable lengths
or higher loads.
The RJ45-plug has eight conductors and the RJ12-plug
has six conductors. Use cables rated for use in low voltage
systems.
The communication cables have special requirements, see
the Network section of this guide.
On the following page is a graphic for quick selection of
cable sizes based on cable length, product types, and their
quantities.
2.2 Cable lengths
Devices with Modbus communication
Since these devices are on a stub of the network, the cable
lengths to these are primarily not determined by the power of
the devices but of the maximum allowed stub length of 20 m.
These devices are the Room Controller, EMxx and RWxx,
numbers 6, 7, 8 and 9 in the picture on the following page.
Non communication devices
The cable lengths to these are determined by the power
consumption of the device and the number of devices con-
nected the terminal. These devices are, see the picture on
next page.
2. Power and Control
Cable Guide
9489 GB 2016.01.08 6 We reserve the right to alter speci cations.
IPSUM®
AWG CSA (mm2)
# Device Code Pcs AWG26 AWG24 0,5 0,75 1 1,5
1Transformer (50Va) STRZ-24 1- - 6 m 10 m 13 m 20 m
2Thermal Actuator STRZ-70 114 m 22 m 55 m 83 m 111 m 166 m
27 m 11 m 27 m 41 m 55 m 83 m
4- - 13 m 20 m 27 m 41 m
8 - - 6 m 10 m 13 m 20 m
3External temperature
sensor
STRZ-05 1>100 m >100 m >100 m >100 m >100 m >100 m
Condensation STRZ-16 1
Window Contact STRZ-38 1
4CO2 sensor STRZ-18 128 m 44 m 111 m 166 m 222 m 333 m
5 P.I.R STRZ-09 1>100 m >100 m >100 m >100 m >100 m >100 m
2>100 m >100 m >100 m >100 m >100 m >100 m
6 Measuring device EMSF 120 m 20 m 20 m 20 m 20 m 20 m
7 Optivent Dampers & Active
diffusers
Emxx/RWxx 118 m 20 m 20 m 20 m 20 m 20 m
29 m 14 m 20 m 20 m 20 m 20 m
4- - 18 m 20 m 20 m 20 m
8 - - 9 m 13 m 20 m 20 m
8 VAV Chilled Beam (actua-
tor)
IQAZ-23 128 m 44 m 111 m 166 m 222 m 333 m
214 m 22 m 55 m 83 m 111 m 166 m
4- - 27 m 41 m 55 m 83 m
8 - - 13 m 20 m 27 m 41 m
9 Room Controller STRA-04/14/24 120 m 20 m 20 m 20 m 20 m 20 m
CCN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2 AE2 AS1 AE1 AS
04 34 24 14 3323 13 03 22 42 32 11 01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
768
9
3
45
2
1
2
Maximum cable lengths (m) for devices attached to the connection unit.
Cable Guide
9489 GB 2016.01.08 7 We reserve the right to alter speci cations.
IPSUM®
2.3 Cable requirements and power consumptions for devices connected to
the IPSUM® Connetcion Unit
The green rows are accessories and are connected to the green area on the Connection Unit.
The purple rows are products and are connected to the purple area on the Connection Unit.
The orange rows are controllers and connected to the orange area on the Connection Unit.
* These are individual limits per device type, the total power (Va) should not exceed 50 Va for all devices
(Which may reduce the individual limits when different device types are connected).
** Not connected at the same time (Either STRA, EMSF or none).
*** Only two of the three can be connected at the same time.
**** Less cables can be used if not all the functionality is required but this is not recommenced as it limits adding functions later.
For details on using less cores please see section 4 of the ”Installation Guide” (Document Number 9402).
Load limitations for cables in IPSUM®
Regardless of cable lenght the below chart show the maximum
recommended load for the cable to make sure they do not overheat.
Cross Section Area [mm2] Maximum load [VA], 24V
AWG26 0,128 mm2 9 VA
AWG24 0.205 mm214 VA
0,5 mm236 VA
0,75 mm248 VA
1,0 mm250 VA
1,5 mm250 VA
Description Code
Power
Consumption
[VA]
Maximum number allowed
per IPSUM Connection Unit *
Cable type and wires needed
1Transformer (50VA) STRZ-24 50 12-wire
2Thermal Actuator STRZ-70 6 8 " 6-wire with RJ
2-wire with terminals
3External temperature
sensor STRZ-05 0 1" 6-wire with RJ
2-wire with terminals
Condensation detector STRZ-16 0 1*** " 6-wire with RJ
2-wire with terminals
Window contact STRZ-38 0 1*** 6-wire with RJ
2-wire with terminals
4 CO2-sensor STRZ-18 3 1 " 6-wire with RJ
3-wire with terminals
5Occupancy detector
(P.I.R) STRZ-09 0,1 1*** 6-wire with RJ
4-wire with terminals
6Optivent Dampers &
Optimix Active Diffusers EMxx/RAxx 4,5
"10 with room controller
2 with EMS
10 without Room Controller
and EMSF
" Shielded with twisted pair
8-wire with RJ
5-wire with terminals
7 VAV Chilled beam Wega/Nova/Stella 3
"16 with room controller
5 with EMSF
16 without Room Controller
and EMSF
3-wire
8 Measuring device EMSF 3,5 1** 3-wire
9 Room Controller STRA-04/14/24 2,5 1**
Shielded with twisted pair
8 + 6-wire with RJ ****
8 + 5-wire with terminals ****
2
Cable Guide
9489 GB 2016.01.08 8 We reserve the right to alter speci cations.
IPSUM®
2.4 Calculating the minimum cross
sectional area
For trouble-free operation it is important to ensure that the
vol-
tage drop between the connection unit and the device is
kept below the speci ed limits.
The minimum area for the cable is given by the following
formula:
A = 0.0015 x L x P
where
A = Cross sectional area (CSA) mm2
L = Cable length in m
P = Power consumption of the device in VA
The power consumption of the devices is given in the table on
the previous page of this document.
Example 1
A 15 meter cable is required between an IPSUM® connection
unit and an STRZ-70 thermal actuator.
From the table reference, we can  nd that the power con-
sumption of the device is 6 VA.
So the minimum required cable cross sectional area is:
A=0.0015*L*P
0.0015 x 15 x 6 = 0.135 mm2
So a cable with at least that cross sectional area is required.
If two (or more) devices are connected in a daisy-chain then
the  rst cable from the connection box must be sized for
the total power. In theory it may be possible to reduce the
size of the cable for subsequent sections but in general we
do not recommend that, and suggest the same cable is used
throughout.
2
Cable Guide
9489 GB 2016.01.08 9 We reserve the right to alter speci cations.
IPSUM®
3. Networks
Correct installation of an TIA/EIA-485 (RS-485) network
Incorrect installation of an TIA/EIA-485 (RS-485) network (avoid)
Daisy chain
Ring Star network
Backbone with stars or clusters
Backbone with stubs
You can see where the daisy chain and the stubs are used in the IPSUM® System below:
PE NL GO/-G/+GO/-G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+ GO/- G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04
3
4
24 1
4
3323
13
03 2
2
42 3
2 11
01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04
3
4
24 1
4
3323
13
03 2
2
42 3
2 11
01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
PE NL GO/-G/+ Ethernet Alarm
Output
24vac/dc
24vac/dc230vac/ In 24vac/dc
GO/-G/+
In Out Fire Free
Cooling
CCB/-A/+
EIA-485
Active
Passive
Termination
Ethernet
Termination
CB/-A/+Active
Passive
EIA-485
Termination
CB/-A/+Active
Passive
EIA-485
SA Fan
0-10v
EA Fan
0-10v
Temp
0-10v
+ -+ -+ - SD Card HMI Ethernet
Comm/
Reset
Power Supervisor
SystemControllerAir Handling Unit
Controller
Supervisor
Air Handling Unit / System
230vac
IPSUM System Optimizer
daisy chain
daisy chain
stubs stubs
3.1 TIA/EIA-485 (RS-485)
3.1.1 TIA/EIA-485 (RS-485) Network topologies
The correct topology is essential to ensure the reliable function of TIA/EIA-485 networks.
3
Cable Guide
9489 GB 2016.01.08 10 We reserve the right to alter speci cations.
IPSUM®
3.1.2 Optimizer to Connection Unit Wiring TIA/EIA-485 (RS-485), Compact mode
3.1.3 Optimizer to Router Wiring TIA/EIA-485 (RS-485), Full mode
The connections are A/+ to A/+, B/- to B/- and C to C. The maximum overall length from the Optimizer to the last Connection
Unit is 1,000 meters. The Termination dip-switch should be “Active” on the Opitimizer and the last Connection Unit with all other
Connection Units set to “Passive”. The maximum number of Connection Units that can be connected to the Optimizer is 30
(Based on 1 x STRA and 2 x Optivent/Optimix Products per Connection Unit).
The connections are A/+ to A/+, B/- to B/- and C to C. A maximum overall length from the Optimizer to the last Router is 1,000
meters. The Termination dip-switch should be “Active” on the Optimizer and the last Router with all other Routers set to
”Passive”. The maximum number of Routers that can be connected to an Optimizer is 30 (Combined on TIA/EIA-485 (RS-485),
Ethernet – Private or Ethernet – Shared).
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04 34 24 14 3323 13 03 22 42 32 11 01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04 34 24 14 3323 13 03 22 42 32 11 01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
PE NL GO/-G/+ Ethernet Alarm
Output
24vac/dc
24vac/dc230vac/ In 24vac/dc
GO/-G/+
In Out Fire Free
Cooling
CCB/-A/+
EIA-485
Active
Passive
Termination
Ethernet
Termination
CB/-A/+Active
Passive
EIA-485
Termination
CB/-A/+Active
Passive
EIA-485
SA Fan
0-10v
EA Fan
0-10v
Temp
0-10v
+ -+ -+ - SD Card HMI Ethernet
Comm/
Reset
Power Supervisor
SystemControllerAir Handling Unit
Controller
Supervisor
Air Handling Unit / System
230vac
IPSUM System Optimizer
PE NL GO/-G/+ GO/-G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+ GO/- G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+ Ethernet Alarm
Output
24vac/dc
24vac/dc230vac/ In 24vac/dc
GO/-G/+
In Out Fire Free
Cooling
CCB/-A/+
EIA-485
Active
Passive
Termination
Ethernet
Termination
CB/-A/+Active
Passive
EIA-485
Termination
CB/-A/+Active
Passive
EIA-485
SA Fan
0-10v
EA Fan
0-10v
Temp
0-10v
+ -+ -+ - SD Card HMI Ethernet
Comm/
Reset
Power Supervisor
SystemControllerAir Handling Unit
Controller
Supervisor
Air Handling Unit / System
230vac
IPSUM System Optimizer
3
Cable Guide
9489 GB 2016.01.08 11 We reserve the right to alter speci cations.
IPSUM®
Abbreviation Description Cable screening Pair shielding
UTP or U/UTP Unshielded Twisted Pair None None
STP or U/FTP Shielded Twisted Pair None Foil
FTP or F/UTP Foil Twisted Pair Foil None
S-FTP or SF/UTP Screened Twisted Pair Foil, braiding None
3.1.4 Router to Connection Unit Wiring TIA/EIA-485 (RS-485), Full mode
The connections are A/+ to A/+, B/- to B/- and C to C. The maximum overall length from the Router to the last Connection
Unit is 1,000 meters. The Termination dip-switch should be “Active” on the Router and the last Connection Unit with all other
Connection Units set to ”Passive”. The maximum number of Connection Units that can be connected to a Router is 30
(Based on 1 x STRA and 2 x Optivent/Optimix Products per Connection Unit).
PE NL GO/-G/+ GO/- G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04
3
4
24 1
4
3323
13
03 2
2
42 3
2 11
01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
C
CN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2
AE
2
A
S1
AE
1 A
S
04
3
4
24 1
4
3323
13
03 2
2
42 3
2 11
01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
3.2.1 Optimizer to Router Wiring (Ethernet – Private Network), Full mode
The Routers have two Port Ethernet Switches built-in to allow daisy chaining from the Optimizer to the Routers without the
need of an external switch (fewer cables, fewer power supplies, e.t.c.). The maximum length between devices is 100 meters.
The maximum number of Routers that can be connected to an Optimizer is 30 (Combined on TIA/EIA-485 (RS-485),
Ethernet – Private or Ethernet – Shared).
PE NL GO/-G/+GO/-G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+ GO/- G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+ Ethernet Alarm
Output
24vac/dc
24vac/dc230vac/ In 24vac/dc
GO/-G/+
In Out Fire Free
Cooling
CCB/-A/+
EIA-485
Active
Passive
Termination
Ethernet
Termination
CB/-A/+Active
Passive
EIA-485
Termination
CB/-A/+Active
Passive
EIA-485
SA Fan
0-10v
EA Fan
0-10v
Temp
0-10v
+ -+ -+ - SD Card HMI Ethernet
Comm/
Reset
Power Supervisor
SystemControllerAir Handling Unit
Controller
Supervisor
Air Handling Unit / System
230vac
IPSUM System Optimizer
3.2 Ethernet (TCP/IP)
The ethernet cables are divided in to categories (e.g. CAT5, CAT6) based on frequency bandwith and type of shielding used.
The most common abbreviations for shielding are detailed in the table below.
3
Cable Guide
9489 GB 2016.01.08 12 We reserve the right to alter speci cations.
IPSUM®
3.2.2 Optimizer to Router Wiring (Ethernet – Shared Network), Full mode
The Routers can also be connected to the customers existing network (Shared) along with the Optimizer. This removes the need
for a separate network just for the HVAC system (fewer cables, fewer power supplies, e.t.c.). The maximum length between the
LAN (Switch) and the devices is 100 meters. The maximum number of Routers that can be connected to an Optimizer is 30
(Combined on TIA/EIA-485 (RS-485), Ethernet – Private or Ethernet – Shared).
* Hotel Management System
PE NL GO/-G/+GO/-G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dc cd/cav42nI /cav032
In Out
CB/- A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
PE NL GO/-G/+GO/-G/+ Ethernet
1
Ethernet
2
24vac/dc
24vac/dccd/cav42nI /cav032
In Out
CB/- A/+Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
Termination
CB/-A/+Active
Passive
EIA-485
IMHdr
a
C DS
Comm/
Reset
rosivrepuS / rezimitpOrewoP
SystemController
Controller
Optimizer / Supervisor
System
230vac
IPSUM System Router
Client´s
ethernet HMS*
BMS
SCADA
PE NL GO/-G/+ Ethernet Alarm
Output
24vac/dc
24vac/dc230vac/ In 24vac/dc
GO/-G/+
In Out Fire Free
Cooling
CCB/-A/+
EIA-485
Active
Passive
Termination
Ethernet
Termination
CB/-A/+Active
Passive
EIA-485
Termination
CB/-A/+Active
Passive
EIA-485
SA Fan
0-10v
EA Fan
0-10v
Temp
0-10v
+ -+ -+ - SD Card HMI Ethernet
Comm/
Reset
Power Supervisor
SystemControllerAir Handling Unit
Controller
Supervisor
Air Handling Unit / System
230vac
IPSUM System Optimizer
3.3 Network defi nitions and requirements in detail
3.3.1 TIA/EIA-485 (RS-485)
Cabling
The Modbus/RTU and BACnet MS/TP cabling must use
twisted pair conductors and the cable should ful l the EIA-
485 speci cation for 2-wire systems. A single twisted pair
must always be used for the data, and another conductor
must be used for a signal reference ground between de-
vices. Do not use a shield drain wire for the signal reference
grounding.
If RJ45 or RJ12 connectors are used, the maximum wire
gauge is AWG24. If the screw terminals are used, the maximum
cross sectional area of the wire is 1.5 mm2. The area
correlates with a maximum cable length and quality of signal.
Therefore the area should not be less than AWG26/ 0.129 mm2.
Avoid crossing high voltage cables, the cables must be
kept separate from major interference sources such as gen-
erators, relays or frequency transformers. If the installation
is in an environment with lots of interference Fläkt Woods
recommends that the screw terminals are used instead of
the RJ connectors, then a larger cross sectional area can be
used to secure reliable communication.
Shielded cables should be used if the environment has
sources of interference.
TIA/EIA-485 Specifi cation
TIA/EIA-485 is a standard which speci es the physical layer of
the OSI model for the generator and receiver used in a
balanced serial transmission system. EIA-485 is a half-duplex
multi-point communication network, meaning the data can be
transmitted in both directions on a signal carrier, but only in
one direction at a time.
The data is transmitted via two signal lines. The lines are
used for both transmission and reception. Logical stage of
the signal is de ned as a difference of the signal lines. The
differential interpretation combined with a single twisted pair
provides effective protection against interference. Note that
the naming of the lines varies. The signal lines may need to be
swapped around to get the communication working. Incor-
rect polarity cannot harm either device.
Topology
The recommended network structure has one trunk cable
to which devices are connected directly or by short stubs.
The stub is de ned as a distance from a device to the trunk
cable. EIA-485 does not de ne the maximum stub length,
but it re-commends that the stubs should be as short as
possible. A long stub reduces the quality of the signal mainly
by causing unwanted re ections. According to the Modbus
speci cation, a stub must never be longer than 20 m.
The transmission line must be terminated near each of
the two ends of the bus to avoid re ection. IPSUM® System
Optimizer, Router, and Connection Unit all have built-in ter-
mination resistors. The termination can be easily activated
by moving a dip-switch.
3
Cable Guide
9489 GB 2016.01.08 13 We reserve the right to alter speci cations.
IPSUM®
In compact mode, the IPSUM® System Optimizer is a mas-
ter to the products on the system side. The system network
starts from the Optimizer and from there all Connection Units
must be connected in series. The built-in termination resis-
tor of the Optimizer and the last Connection Unit must be
activated.
In full mode, the IPSUM® System Optimizer is a master
to the Routers and the Routers are masters to the products
on the system side, meaning the Optimizer does not have
direct contact to the components. The Optimizer network
starts from the Optimizer and from there all Routers must be
connected in series. The built-in termination resistor of the
Optimizer and the last Router must be activated. The system
networks start from each Router and from there all Connec-
tion Units must be connected in series. The built-in termina-
tion resistor of each Router and each of the last Connection
Units must be activated.
The network topology must not be a star, a ring, or a
backbone with stars or cluster (See above for example illus-
trations of these topologies). It is dif cult to determine where
two ends of the bus are when these topologies are used,
therefore the bus cannot be properly terminated. A star
structure may also cause harmonic noise to the signal. Any
star, ring, and backbone with stars or cluster must be removed
from the network.
Cable Length
The theoretical maximum length of the cable depends on the
communication speed and the cable properties such as
characteristic impedance and wire gauge. The Modbus
speci cation de nes the maximum length for the cable as
1,000 meters when the wire gauge is suf cient. AWG 24 is
always suf cient for the Modbus data. When the baud rate
is 19,200 or higher, characteristic impedance with a value of
100 Ohms is recommended.
The stubs should be as short as possible to avoid signal
re ection on the line. The maximum stub length depends on
the signal velocity of the cable and the rise time of the driver.
The higher the values are, the shorter the stub lengths allowed.
The maximum stub length in the IPSUM® System is limited
by the Modbus speci cation and should therefore never be
longer than 20 m.
The maximum length also depends on the quality of the
conductors, the environment and how much of the twisted
pair is unwound at each connection point. The actual maxi-
mum length may therefore be shorter than de ned in the
Modbus speci cation. The higher the communication speed
the more sensitive the system is.
According to the Modbus speci cation, Category 5 (Cat5)
or better cables may also be used in TIA/EIA-485 system.
The maximum cable length is then 600 meters. TIA/EIA-485
rated cables should be used over Cat5 cables in particular
when the system has a lot of rooms and branches or when
the environment has sources of interference.
3.3.2 Ethernet (TCP/IP)
Cabling
Both the IPSUM® System Optimizer and IPSUM® System
Routers can be connected to the client network or a private
network using TCP/IP protocol. In this case the cables must
ful l Category 5 as de ned in the EIA-568 standard.
Shielded cables should be used if the environment has
sources of interference.
TIA/EIA-568 Specifi cation
TCP/IP is a packet-based communication protocol for the
Internet. The communication protocol can also be used in
private networks such as intranets. The protocol de nes
how the message is divided into smaller packets and how
the packets are addressed to the right destination.
Cable Length
The maximum length between the devices is 100 meters.
3
Cable Guide
9489 GB 2016.01.08 14 We reserve the right to alter speci cations.
IPSUM®
4. Appendix
Manufacturer Cable Code CSA IPSUM® Use Description/Comments
Belden 22101 AWG14 From 230V to transformer, Optimizer
and Router
3 Cores
Nexan H05V2V2-F 2 0.75 mm²
1.00 mm²
1.50 mm²
From transformer to Connection
Unit
From Connection Unit to thermal
valve, external temperature sensor,
window contact, and condensation
detector
2 Cores
Nexan H05V2V2-F 3 0.75 mm²
1.00 mm²
1.50 mm²
From 230V to transformer, Optimizer
and Router
From Connection Unit to EMSF,
Wega/Nova/Stella and CO2 sensor
3 Cores
Nexan H05V2V2-F 3 0.75 mm²
1.00 mm²
1.50 mm²
From 230V to transformer, Optimizer
and Router
Nexan H05V2V2-F 4 0.75 mm²
1.00 mm²
1.50 mm²
From Connection Unit to occupancy
detector
4 Cores
Lapp Group ÖLFLEX 0026100
ÖLFLEX 0026119
ÖLFLEX 0026130
ÖLFLEX 0026149
0.5 mm²
0.75 mm²
1.00 mm²
1.50 mm²
From transformer to Connection
Unit
From Connection Unit to thermal
valve, external temperature sensor,
window contact and condensation
detector
Classic FD 810
2 Cores
Lapp Group ÖLFLEX 0026101
ÖLFLEX 0026120
ÖLFLEX 0026131
ÖLFLEX 0026150
0.5 mm²
0.75 mm²
1.00 mm²
1.50 mm²
From 230V to transformer, Optimizer
and Router
From Connection Unit to EMSF,
Wega/Nova/Stella and CO2 sensor
Classic FD 810
3 Cores
Lapp Group ÖLFLEX 0026102
ÖLFLEX 0026121
ÖLFLEX 0026132
ÖLFLEX 0026151
0.5 mm²
0.75 mm²
1.00 mm²
1.50 mm²
From Connection Unit to occupancy
detector.
Classic FD 810
4 Cores
4.1 Exampel of cable for Power and Control
44
Cable Guide
9489 GB 2016.01.08 15 We reserve the right to alter speci cations.
IPSUM®
4
4.2 Exampel of cable for TIA/EIA-485 (RS485)
Twisted pair cables must be used for data cables. Some of the well-known cable manufactures are Alpha Wire, Batt Cables,
Belden, Draka, Nexans and Lapp Kabel. Some cable details are below for quick reference.
Manufacturer Cable Code CSA Description/Comments
Belden 9842 24AWG 2 Twisted Pairs, Polyethylene Insulation.
Belden 3106A 22 AWG 1 Twisted Pair + 1 core, Datalene Insulation.
Belden 3107A 22AWG 2 Twisted Pairs, Datalene Insulation.
Batt Cables 91084 24AWG 2 Twisted Pairs, Polyethylene Insulation.
Batt Cables 91421 24AWG 2 Twisted Pairs, Polyethylene Insulation. LSZH
Alpha Wire 6455 22AWG 2 Twisted Pairs, Foam HDPE Insulation.
Nexans TRONIC-CY-TP (LiYCY-TP) 2x2x0.25 0.25 mm22 Twisted Pairs, PVC insulation
Draka NOMAK 2x2x0,5+0.5 0.5 mm22 Twisted Pairs, PVC insulation
Draka Datajamak 2x(2+1)x0.24 0.24 mm22 Twisted Pairs, PVC insulation
LappKabel UNITRONIC 2x0.22 0.22 mm22 Twisted Pairs, PVC insulation
Useful Links
Belden
http://www.belden.com/products/industrialcable/eia-485.cfm
Batt Cables
http://www.batt.co.uk/products/view/423/RS485-Overall-Shielded-&-Braid-Cable-9841--9844
Alpha Wire
http://www.alphawire.com/en/Products/Cable/Alpha-Essentials/Communication-and-Control-Cable
Nexans
http://www.nexans.se/eservice/Sweden-sv_SE/navigate_231543/TRONIC_CY_TP_LiYCY_TP_.html
LabbKabel
http://products.lappgroup.com/online-catalogue/data-communication-systems/cables-for-bus-systems-rs485rs422.html
Cable Guide
9489 GB 2016.01.08 16 We reserve the right to alter speci cations.
IPSUM®
4
Manufacturer Cable Code Description/Comments
Alpha Wire Xtra-Guard U/UTP, F/UTP and SF/UTP
Batt Cables See link below U/UTP and F/UTP
Belden DataTuff Shielded and Unshielded cables
Nexans LANmark U/UTP and F/UTP
LabbKabel Etherline SF/UTP
Useful Links
Alpha Wire
http://www.alphawire.com/en/Products/Cable/Xtra-Guard-Performance-Cable/Xtra-Guard-Industrial-Ethernet
Batt Cables
http://www.batt.co.uk/products/category/20/Structured-Cabling-UTP
Belden
http://www.belden.com/products/industrialcable/ethernet-cables.cfm
Nexans
http://www.nexans.co.uk/eservice/UK-en_GB/navigate_227799/LAN_copper_cables.html
LabbKabel
http://products.lappgroup.com/online-catalogue/data-communication-systems-for-ethernet-technology/accessories-for-
industrial-networking/lan-cables-for-structured-industrial-cabling.html
4.3 Exampel of cable for Ethernet
There are a lot of cable manufacturer’s who offer ethernet cables. Some well-known manufacturer’s who offer both unshielded
cables (For use in normal operation enviroments) as well as shielded cables (For use in more demanding enviroments) are
below for quick reference.
4
Cable Guide
9489 GB 2016.01.08 17 We reserve the right to alter speci cations.
IPSUM®
4
4.4 Standard VAV Application
The room contains an EMSS  ow variator installed in the
supply air duct to control and measure the supply air  ow
and an EMSS  ow variator in the extract air duct to control
and measure the extract air  ow. Cooling, heating and ven-
tilation are controlled by the STRA-04 room controller with
occupancy detectors and CO2 sensor.
List of Components
1. IPSUM® Connection Unit
2. STRA-04
3. EMSS  ow variators
4. STRZ-70 Actuator and valve for heating
5. STRZ-09 Occupancy detector
6. STRZ-24 Transformer
7. STRZ-18 CO2 Sensor
Cable Code:
H05V2V2-F 2
Cable length:
10 m
Cable Code:
ÖLFLEX 0026100
Cable length:
56 m
Cable Code:
ÖLFLEX 0026102
Cable length:
110 m
Cable Code:
ÖLFLEX 002610
Cable length:
3,3 km
Cable Code:
Belden 9843
Cable length:
20 m
Cable Code:
Belden 9844
Cable length:
20 m
Cable Code:
Belden 9844
Cable length:
20 m
Cable Code:
Belden 9844
Cable length:
20 m
CCN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2 AE2 AS1 AE1 AS
04 34 24 14 3323 13 03 22 42 32 11 01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
1
6
4
7 5
2
3
Cable Guide
9489 GB 2016.01.08 18 We reserve the right to alter speci cations.
IPSUM®
4
CCN/O GO G
P.I.R
Y GO G
CO2
B/-A/+ Active
Passive
EIA-485 In
CB/- A/+
EIA-485 Out
Termination
noitacinummoCseirosseccArewoP
ControllerProducts
2:1CR1:1CR2 AE2 AS1 AE1 AS
04 34 24 14 3323 13 03 22 42 32 11 01
GO GGOGOG
Heat Cool
GYGOG Ext.
Temp
Cond. /
Window
Y
24vac
In
24vac
Out
Cond.
Window
IPSUM Connection Unit
4.5 Chilled Beam Application
The room contains a Wega/Nova/Stella Chilled Beam with
a motorized VAV function (MEC) for regulating the supply
air  ow and a transfer air terminal device for the extract air.
Cooling, heating and ventilation are controlled by the
STRA-14/24 room controller with occupancy detectors and
CO2 sensor.
List of Components
1. IPSUM® Connection Unit
2. STRA-14/24
3. Wega/Wega power/Nova/Stella
4. IQAZ-23 (MEC) Actuator for the VAV function in a chilled beam
5. STRZ-70 Actuator and valve for cooling or heating
6. STRZ-09 Occupancy detector
7. STRZ-24 Transformer
8. STRZ-18 CO2 Sensor
Cable Code:
H05V2V2-F 2
Cable length:
10 m
Cable Code:
ÖLFLEX 0026100
Cable length:
56 m
Cable Code:
ÖLFLEX 0026102
Cable length:
110 m
Cable Code:
ÖLFLEX 002610
Cable length:
3,3 km
Cable Code:
Belden 9843
Cable length:
20 m
Cable Code:
Belden 9844
Cable length:
20 m
Cable Code:
ÖLFLEX 0026101
Cable length:
110 m
1
7
5
8 6
2
34
4
Notes
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
………………………………………………………………………………………………………………………………………………………………
WWW.FLAKTGROUP.COM IPSUM CABLE GUIDE | 9489 GB | 20160108
» To learn more about our offering and get in contact with your
nearest sales representative please visit www.flaktgroup.com
WE BRING
BETTER AIR
TO LIFE
With over a century of innovation and expertise to share with our
customers, FläktGroup is a global leader in Air Technology products
and solutions. We specialise in the design and manufacturing of a
wide range of products and solutions for Air Movement, Air Treatment,
Air Distribution, Air Management and Air Diffusion with focus on two
major benefi ts – Air Comfort and Fire Safety. With market presence
in 65 countries we are in a unique position to be a local supplier
and an international partner in our customer’s projects.
Our product brands such as SEMCO®, eQ®, eQ Prime®, JM Aerofoil®,
Econet®, Veloduct®, Optivent®, Optimix®, Econovent® and Cleanvent®
are well-known and trusted by customers all over the world to
deliver high quality and energy effi cient solutions.
FWG-IPSUM Cable Guide-GB-2016.01.08 9489GB © Copyright 2015 Fläkt Woods Group
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

FläktGroup IPSUM Cable User guide

Category
Coaxial cables
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI