FläktGroup Optivent Ultra ULSA, ULDA Installation guide

Type
Installation guide
INSTALLATION, COMMISSIONING, MAINTENANCE
OPTIVENT® ULTRA VAV DAMPER
with 327VMZ-BN
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
2
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
Installation Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
In the straight tube
100 - 630 3 x D ± 8% or 1 l/s ± 5% ± 4%
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
Bend
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
100 - 250
315, 400
0 x D ± 10% or 1 l/s ± 8% ± 6%
T-piece 1
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
100 - 250
315 - 400
0 x D
1 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 125
160 - 250
315 - 400
0 x D
1 x D
-
± 10% or 1 l/s ± 8% ± 6%
MEASURING ACCURACY
For the best possible accuracy, it is recommended to install the air volume damper so that it is preceded by a straight duct, at least 3 x D safety dis-
tance.
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
*) recommended position
*)
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p. 8-9) to achieve the accuracies.
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
3
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
T-piece 2
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
T-piece 3
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 160
200 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
T-piece 4 (lid)
100 - 250
315 - 400
0 x D
2 x D
± 10% or 1 l/s ± 8% ± 6%
100 - 400 2 x D ± 10% or 1 l/s ± 8% ± 6%
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p. 8-9) to achieve the accuracies.
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
Lid
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
4
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
Reducer 2:1 and 3:1
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
Round sound absorber
BDER-30, -40, -44 and -60
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
Rectangular sound absorber
BDER-70, -71, -72 and -73
100 - 400 0 x D ± 10% or 1 l/s ± 8% ± 6%
3 x D
3 x D
3 x D
Valid when the damper blade opening is > 30%. Recommended maximum air velocity with shorter than 3 x D safety distances is 8 m/s.
Adequate safety distance is recommended after the type of flow disturbance (3 x D).
With sizes 500 and 630 should the safety distance be at least 3 x D.
The motor/ultrasound shall be placed as shown on the pictures above.
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p. 8-9) to achieve the accuracies.
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
5
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
Type of flow disturbance
(only applies to a single type of disturbance) Installation case Size Minimum
safety distance
Velocity in the duct (m/s)
0,5 - 1 > 1 > 4
ETPR fire damper
100 - 315
400
0 x D
3 x D
± 10% or 1 l/s
± 8% or 1 l/s
± 8%
± 5%
± 6%
± 4%
ELPO flue & ETPR-E-1 fire damper
125
(ELPO flue: 250)
4 x D
*)
2 x D
0 x D
± 8% or 1 l/s
± 10% or 1 l/s
± 5%
± 8%
± 4%
± 6%
*) recommendation
NOTE! Fire damper shaft parallel to the ELPO flue.
MEASURING ACCURACY
When using the minimum safety distance after the type of flow disturbance, the installation parameter must be set according to the commissioning
section (p. 8-9) to achieve the accuracies.
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
6
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
WIRING
No. Designation Colour Function
1 / - black Power supply 24VAC/DC
2~ / + red
3 Y white Setpoint signal 0-10 VDC
4 U orange Feedback signal 0-10 VDC
ACA - pink Communication (RS-485)
BCB + grey
1 2 3 4 A B
CA CBU~
+-- +
Y
BK RD WH OG PK GY
RS485 A
RS485 B
RS485 Common
230 V
24 V AC/DC
A B G G0 A B G G0 A B G G0 A B G G0
Actuator Actuator Actuator Actuator
230 V
24 V AC/DC
A B G G0 A B G G0 A B G G0 A B G G0
RS485 A
RS485 B
RS485 Common
Actuator Actuator Actuator Actuator
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
7
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
INSTALLATION
WIRING
Parallel control
EMSF control
CAV constant air volume
0...10/2...10 V DC
Bus control
24 V AC/DC
MM
A B1 2 3 4
WHBK RD OG PK GY
A B1 2 3 4
WHBK RD OG PK GY
+
-
24 V AC/DC
Bus control
~
1 2
BNBU
pM
GY
0-10 V
2-10 V
0-10 V
2-10 V
GT-MB
EMSF UL(S,D)A
327VMZ
4 A
WH WH
B A B1 2 3 4
Vmax S (GT) = Max (327VMZ) Min (327VMZ) = 0
WHBK RD OG PK GY
Bus control
24 V AC/DC
M
A B1 2 3 4
WHBK RD OG PK GY
Max = 0
Min = Setpoint
BU BN BK GY
327VMZ-BN
Y/ U/
ZPP
~
0-10V - CLOSE if Vmin=0
2-10V - CLOSE
Vmin
Vbtw
Vmax
Open
~
Y
U
AC 24
V
DC 24
V+
DC 0...10V
DC 2...10V
DC 0...10V
DC 2...10V
1N4007
A
B
Forced control
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
8
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
COMMISSIONING
FACTORY SETTINGS
Transmission mode BACnet
Address 1
Transfer rate 38400 bps
BACnet instance number 1
A = 3-digit display
B = Value selector
C = LED button
Single press
to change menu
Press and hold
to enter setup
Rotate
to change value
A
B C
2s
1Air flow unit selection
l/s m
3
/h
2Vmax value setup
Example:
Vmax = 150 l/s
Vmax = 1 250 l/s
Vmax = 12 500 l/s
3Vmin value setup
Example:
Vmin = 50 l/s
4Input signal range setup
2-10 V
0-10 V
5Communication address setup
Example:
Adr = 10
6Communication parameters
setup
BACnet
factory setting
Modbus
factory setting
7Installation parameter
setup
Factory setting:
Inst = 100
(straight duct 3D
2s
2s
❽ ❽
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
9
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
COMMISSIONING
Bend Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
4
126
132
125
126
119
120
121
118
125
122
120
125
120
122
119
120
116
120
119
124
115
116
122
121
1 x D
1
2
3
4
125
123
124
124
113
112
113
116
122
120
119
121
118
120
118
118
110
118
110
122
112
110
118
119
2 x D
1
2
3
4
117
117
113
113
108
106
107
108
118
117
116
117
115
117
116
116
106
116
108
111
105
104
114
113
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 1 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
125
132
128
125
120
119
114
128
122
126
120
117
122
120
1 x D
1
2
3
122
129
125
119
118
118
112
115
123
115
114
113
113
113
109
118
117
114
111
2 x D
1
2
3
117
125
119
110
110
110
108
108
115
110
109
109
109
111
107
115
113
109
109
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 2 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
102
96
96
98
95
93
98
96
98
96
95
100
101
100
99
97
98
99
103
98
98
1 x D
1 & 4
2
3
101
102
99
99
99
95
98
100
98
101
97
97
101
97
100
102
99
100
100
102
101
2 x D
1 & 4
2
3
102
100
98
96
96
96
99
99
101
100
100
99
100
99
100
101
99
102
103
103
101
With sizes 500 and 630 should the safety distance be at least 3 x D.
T-piece 3 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
131
126
130
121
117
114
117
118
124
131
122
123
115
1 x D
1 & 4
2
3
119
117
118
115
115
113
112
113
114
113
116
112
109
2 x D
1 & 4
2
3
114
111
110
108
107
107
108
111
112
106
109
105
109
108
108
108
108
109
105
104
105
With sizes 500 and 630 should the safety distance be at least 3 x D.
INSTALLATION PARAMETER SETTINGS (INST)
1
2
2
2
2
3
1
1
1
4
4
4
3
3
3
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
10
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
T-piece 4 (lid) Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1 & 4
2
3
134
130
122
119
115
120
124
126
122
119
1 x D
1 & 4
2
3
130
132
115
115
110
114
116
117
115
116
2 x D
1 & 4
2
3
119
122
123
109
109
109
106
108
109
110
109
108
110
109
111
112
110
105
105
104
106
With sizes 500 and 630 should the safety distance be at least 3 x D.
Rectangular sound absorber
BDER-70, -71, -72 and -73 Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
96
89
96
94
93
95
94
92
99
96
97
98
97
101
99
100
100
100
100
100
100
1 x D
1
2
3
98
93
101
96
94
97
98
94
100
98
99
98
98
99
99
100
100
100
100
100
100
2 x D
1
2
3
101
95
102
99
96
99
101
97
101
98
99
100
99
99
100
100
100
100
100
100
100
With sizes 500 and 630 should the safety distance be at least 3 x D.
ETPR fire damper Min. safety
distance
Installation
case
Size
100 125 160 200 250 315 400
0 x D
1
2
3
111
112
110
97
95
103
94
101
104
99
101
105
96
106
109
95
96
106
1 x D
1
2
3
111
111
110
95
95
103
95
100
102
100
101
103
97
100
101
100
97
102
2 x D
1
2
3
106
110
106
98
95
100
97
98
99
101
102
101
102
102
99
99
98
99
With sizes 400 - 630 should the safety distance be at least 3 x D.
ELPO flue & ETPR-E-1 fire damper
Size Installation
case
Minimum safety distance
4 x D 2 x D 0 x D
125 1 - 4 100 111 Do not use! *)
*) Note that a double disturbance creates a lot of turbulence and a straight tube before the damper must be used.
COMMISSIONING
INSTALLATION PARAMETER SETTINGS (INST)
2
1
4
3
Lid
FläktGroup DC_10685GB 20221101_R0 Specifications are subject to alteration without notice.
11
OPTIVENT
®
ULTRA with 327VMZ-BN - Installation, Commissioning, Maintenance
COMMISSIONING
COMMUNICATION PARAMETERS (ADR)
Modbus RTU
Parameter Baudrate Parity Stop bits
b1 1200 None 2
b2 1200 Even 1
b3 1200 Odd 1
b4 2400 None 2
b5 2400 Even 1
b6 2400 Odd 1
b7 4800 None 2
b8 4800 Even 1
b9 4800 Odd 1
b10 9600 None 2
b11 9600 Even 1
b12 9600 Odd 1
b13 19200 None 2
b14
1)
19200 Even 1
b15 19200 Odd 1
b16 38400 None 2
b17 38400 Even 1
b18 38400 Odd 1
b19
2)
1200 None 1
b20
2)
2400 None 1
b21
2)
4800 None 1
b22
2)
9600 None 1
b23
2)
19200 None 1
b24
2)
38400 None 1
b25
2)
76800 None 1
b26
2)
115200 None 1
b27 76800 None 2
b28 76800 Even 1
b29 76800 Odd 1
b30 115200 None 2
b31 115200 Even 1
b32 115200 Odd 1
1)
default Modbus communication parameter
2)
not according Modbus specification
BACnet MS/TP
Parameter Baudrate
bc1 9600
bc2 19200
bc3
1)
38400
bc4 57600
bc5 76800
bc6 115200
1)
default BACnet communication parameter
The product can be (mechanically) cleaned with nylon brush when the
ductwork is cleaned as shown in the pictures below. No other mainte-
nance is required.
MAINTENANCE
WWW.FLAKTGROUP.COM ULSA, ULDA 10685
»
Learn more on www.flaktgroup.com
or contact one of our oices
FG_DC_10685GB_ULSA_ULDA BACnet_IN-MA_20221101_R0 © Copyright 2022 FläktGroup
FläktGroup is the European market leader for smart and energy eicient Indoor Air
and Critical Air solutions to support every application area. We oer our customers
innovative technologies, high quality and outstanding performance supported by
more than a century of accumulated industry experience. The widest product range
in the market, and strong market presence in 65 countries worldwide, guarantee
that we are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diusion | Air Distribution | Air Filtration
Air Management & ATD’s | Air Conditioning & Heating | Controls | Service
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12