  • I have reviewed the FläktGroup Quick Guide for the FICO-PRO control unit and FCBB slave units. This document contains connection diagrams, default input/output configurations, and commissioning instructions. I'm ready to answer your questions about its damper management capabilities, BMS integration, and other features outlined in the guide.
  • How many dampers can the FICO-PRO control unit manage?
    How many FCBB slave units can be connected to the FICO-PRO?
    What BMS interfaces does the FICO-PRO support?
    Does the FICO-PRO has on screen guide during commissioning?
FläktGroup DC_10345GB 20210423_R2 Specifications are subject to alteration without notice
CONTROL UNIT
FICO-PRO
QUICK GUIDE
More documentation can be found on the FläktGroup home page. Either
follow the links in this document or go to https://www.flaktgroup.com
and search for the part number of the product you are using.
FICO-PRO control unit is used for up to 256 dampers. The device can
operate in standalone mode or with up to 63 FCBB slave units connect-
ed. The device can be integrated to BMS through multiple interfaces
FICO-PRO
https://www.flaktgroup.com/en/search/?q=FICO-PRO
Up to 256 dampers
Modbus RTU
Modbus TCP
Bacnet IP (hardware)
GPRS (hardware)
DAMPER 1
55
FICO-PRO
60 61
42 43 44 45 46 473 4 5 6 48 49 50 51 52 53
230VAC
Digital inputs Analog LINK 1 LINK 2
L N PE
X1 X3 Y1G G0 S1 S2 D0 D1 D0 D1
12 S1 S2 S4 S6
Supply
voltage
230VAC
Fire damper
MODBUS RTU
Ventilation duct detector
UG-3-O
7 8
S4 S6
DAMPER 2
9 10 11 12
G G0 S1 S2
13 14
S4 S6
1 2 S1 S2 S4 S6
Fire damper
DAMPER 3
15 16 17 18
G G0 S1 S2
12 S1 S2 S4 S6
Fire damper
19 20
S4 S6
DAMPER 4
21 22 23 24
G G0 S1 S2
25 26
S4 S6
1 2 S1 S2 S4 S6
Fire damper
27 28 29 30
DETECTOR
G1 M1 G2 M2
2 1 5
2.2KOhm
2 1 5
2.2KOhm
X2 X4
54
PWR
G
33 34 35 36 37 38 39 40
NO C NC NO NC
NC NO
31 32
NO C
NC
41
C
REL 1 REL 2 REL 3 REL 4
ETH 2
1 2
ETH 1
C
62
CONNECTION DRAWING
FICO-PRO
42 43 44 45 46 47 48
Digital inputs Analog
X1 X3 Y1
X2 X4
33 34 35 36 37 38 39 40
NO C NC NO NC
NC NO
31 32
NO C
NC
41
C
REL 1 REL 2 REL 3 REL 4
C
Alarm Service FAN
External re alarm
External interlock
External test
Generic
60 61 62
230VAC
L N PE
Supply
230VAC
49 50 51 52 53 54
LINK 1 LINK 2
D0 D1 D0 D1
FICO-PRO
1 2 3
230VAC
L N PE
Supply
230VAC
34 35 36 37 38 39
LINK LINK
D0 D1 D0 D1
FCBB-2
1 2 3
230VAC
L N PE
Supply
230VAC
34 35 36 37 38 39
LINK LINK
D0 D1 D0 D1
FCBB-2
MODBUS RTU MODBUS RTU MODBUS RTU
Power cable
EQQ3x1,5
Communication cable
FQAR-PG 2x0.5 (1 twisted pair)
1..63 units
0..1200 m
60 61 62
230VAC
L N PE
Supply
230VAC
49 50 51 52 53 54
LINK 1 LINK 2
D0 D1 D0 D1
FICO-PRO
1 2 3
230VAC
L N PE
Supply
230VAC
36 37 38 39 40 41
LINK LINK
D0 D1 D0 D1
FCBB-4
1 2 3
230VAC
L N PE
Supply
230VAC
36 37 38 39 40 41
LINK LINK
D0 D1 D0 D1
FCBB-4
MODBUS RTU MODBUS RTU MODBUS RTU
Power cable
EQQ3x1,5
Communication cable
FQAR-PG 2x0.5 (1 twisted pair)
1..63 units
0..1200 m
Mains power 230V AC Power supply
REL1 (Fire alarm) FIRE alarm (NO/NC)
REL2 (Service alarm) SERVICE alarm (NO/NC)
REL3 (FAN) FAN - start stop relay (NO/NC)
REL4 (Generic) GENERIC (NO/NC)
X1 (EXT Alarm) Set external alarm external switch
X2 (EXT Interlock) Close unit from external switch
X3 (EXT Test) External input for testing of dampers
X4 (Generic) Generic input
DAMPER 1–4 Connection for 1..4 fire dampers
DETECTOR 1–2 Connection for 1..2 detectors
LINK 1 RS485 interface for BMS connection
LINK 2 RS485 interface connection for slave units
ETH 1 Fläktgroup Cloud TCP/IP port
ETH 2 Generic TCP/IP port
DEFAULT INPUT AND OUTPUT CONNECTIONS
2
FläktGroup DC_10345GB 20210423_R2 Specifications are subject to alteration without notice
Control unit FICO-PRO
COMMISSIONING
CONTROL UNIT FICO-PRO (FIRST COMMISSIONING)
Before starting with the control unit FICO-PRO settings, all installations of peripheral components shall be completed.
FICO-PRO has automatic reading of connected damper actuators and smoke detectors
Switch on the control unit FICO-PRO.
The commissioning will be assisted by the on screen guide according to the following steps:
ENGINEERING
Installation of this product must be carried out by a certi-
fied electrician. No work on mains powered devices can
be carried out before an engineer completely reads and
understands this manual.
Warning
Opening the cover of the device will expose areas where mains voltage
(230VAC) exist inside the product. Before any such action takes place,
mains power must always be switched off and can not inadvertently be
switched on
Special action needs to take place to ensure that any external connec-
tion to relay functions are also disconnected from mains before work is
started.
No accidental contact with mains voltage (supply or relay functions) are
allowed.
Failing to comply with this, may result in serious injury or death.
Use external protection for inductive load of relay functions
Use appropriate external fuse for over current protection of relay
outputs.
Do not mix SELV / PELV and line voltage on the same terminal
230VAC cables must be double insulated against safety extra-low
voltage (SELV) cables.
Fire damper motor cables and end position switches must be double
insulated against PELV and SELV cables.
Signal cables must be double insulated against PELV and SELV
cables.
SAFETY
When installing the product, national safety regulations
MUST be fulfilled for all phases of the installation. Failure
to comply with national safety regulations, may result in
personal injury, loss of life and property damage.
/