Controller AVA362 Remote PIR, AVA362 User manual

  • Hello! I'm your chat assistant and I've reviewed the provided document regarding the Addvent AVA362 Remote P.I.R Fan Timer Control. This document includes installation instructions, specifying requirements for its use with single or multiple fans with total load between 20-200W, and an adjustable run-on timer from 1 to 40 minutes. I'm ready to address any questions you might have about its installation or features.
  • What is the adjustable run-on time for the timer?
    What is the minimum contact separation for the fused spur?
    Where should the fused spur isolator be mounted?
077315 0521Unit 12, Access 18, Bristol, BS11 8HT Telephone: 0117 923 5375
The Addvent Remote P.I.R Fan Timer Control is suitable for use with any single or combination of
fans, providing the total electrical load is not more than 200W or less than 20W. This control unit
contains a run timer activated by a passive infra-red (P.I.R) detector. Typically, this would be used
in a changing room or bathroom to provide forced ventilation during the entire time the room is
occupied and continuing for a set period after the room is vacated.
The timer is user adjustable to provide a run-on period of between approximately 1 – 40 minutes.
Please read and thoroughly understand these instructions before starting work.
IMPORTANT: A double pole switched and fused spur must be used, having a contact separation
of at least 3mm in all poles, and a fuse rated at 3A. The fused spur isolator must be mounted
outside of any room containing the shower or bath. The AVA362 Remote P.I.R Fan Timer Control
must be installed outside of any shower cubicle and sufciently remote from any bath or sink unit
that water is not splashed onto the unit. It must not be accessible to any person using either the
shower or bath. All wiring must be xed securely. The conductors must have a minimum of 1 square
millimetre cross section. All wiring must comply with current IEE regulations. Switch off mains
supply before making any electrical connections.
If in any doubt, please contact a qualied electrician.
Installation Instructions for the
Addvent AVA362 Remote
P.I.R Fan Timer Control
AVA362
REMOTE PIR
CONTROLLER
FAN
FAN NEUTRAL
MAINS NEUTRAL
MAINS LIVE
FAN LIVE
NEUTRAL
LIVE
REMOTE DOUBLE POLE
FUSED ISOLATOR
CONTACT SEPARATION
MUST BE 3mm
MAXIMUM FUSE
RATING MUST 3A
WIRING DIAGRAM
FOR ADDVENT AVA362
REMOTE PASSIVE INFRA RED
CONTROLLER
077315 0521Unit 12, Access 18, Bristol, BS11 8HT Telephone: 0117 923 5375
The Addvent Remote P.I.R Fan Timer Control is suitable for use with any single or combination of
fans, providing the total electrical load is not more than 200W or less than 20W. This control unit
contains a run timer activated by a passive infra-red (P.I.R) detector. Typically, this would be used
in a changing room or bathroom to provide forced ventilation during the entire time the room is
occupied and continuing for a set period after the room is vacated.
The timer is user adjustable to provide a run-on period of between approximately 1 – 40 minutes.
Please read and thoroughly understand these instructions before starting work.
IMPORTANT: A double pole switched and fused spur must be used, having a contact separation
of at least 3mm in all poles, and a fuse rated at 3A. The fused spur isolator must be mounted
outside of any room containing the shower or bath. The AVA362 Remote P.I.R Fan Timer Control
must be installed outside of any shower cubicle and sufciently remote from any bath or sink unit
that water is not splashed onto the unit. It must not be accessible to any person using either the
shower or bath. All wiring must be xed securely. The conductors must have a minimum of 1 square
millimetre cross section. All wiring must comply with current IEE regulations. Switch off mains
supply before making any electrical connections.
If in any doubt, please contact a qualied electrician.
Installation Instructions for the
Addvent AVA362 Remote
P.I.R Fan Timer Control
AVA362
REMOTE PIR
CONTROLLER
FAN
FAN NEUTRAL
MAINS NEUTRAL
MAINS LIVE
FAN LIVE
NEUTRAL
LIVE
REMOTE DOUBLE POLE
FUSED ISOLATOR
CONTACT SEPARATION
MUST BE 3mm
MAXIMUM FUSE
RATING MUST 3A
WIRING DIAGRAM
FOR ADDVENT AVA362
REMOTE PASSIVE INFRA RED
CONTROLLER
/