meitav-tec PYRO_STAG - zone staggering controller Product information

  • Hello! I am an AI chatbot trained to assist you with the meitav-tec PYRO_STAG - zone staggering controller Product information. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
N L V1 X1 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 2 3 7 8 AO1 0 AO2
DI1 T1 0 T2 0 T3 0 AI1 0 AI2 5VDC A B
ON
12345678
ON
1234
Date:
Title:
1
Drawn: Danny
Checked: A.Star
Approved:U.Ulanovsky
CTU/DeIcer/SEQ/01
File: CTU_DeIcer_seq_01.vsd
24 VAC
Fuse 8A
LED Power
Sequence
ON
Communication cable
2x22AWG
Twisted, Shielded
Communication cable
2x22AWG
Twisted, Shielded
DI1 0 DI3 0DI2 DI5 0DI4 DI7 0DI6 DI8 12V
S1 Configuration S2 Configuration
DIP Switch S2 - Configuration
S2.1 – On/Off switch
Off - Device disable
On - Device active
S2.2 - Not in use
S2.3 - Not in use
S2.4 - Not in use
*The drawing shows the default configuration.
ON
1234
Digital output 1
Digital input 1 – De-Icer input signal (N.O.)
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Digital input 7
Digital input 8
Digital output 2
Digital output 3
Digital output 4
Digital output 5
Digital output 8
Digital output 7
Digital output 6
Not in use
Digital input 2
Important !
1. Disconnect power to the main board before making any
changes to DIP switches/Jumpers and while wiring the
unit.
2. Never connect 2 outputs with the same number (for
example: do not connect DO1 and DO5)
3. when device is Disable, all outputs work as if there is a
direct connection from the power-box to the heaters.
24VAC, 0.8A each
Not in use
DIP Switch S1 – Timing
S1.1 - # of outputs work in staggering
On - 2 outputs
Off - 4 outputs
S1.2 - Outputs linkage
On – no linkage, 1,2,3,4 outputs works
seperately
Off – outputs 1 & 3 and 2 &4 are linked
S1.3 + S1.4 + S1.5 – Sequence step timer
Off Off Off - 60 seconds
Off Off On - 5 minutes
Off On Off - 10 minutes
Off On On - 20 minutes
On Off Off - 30 minutes
On Off On - 45 minutes
On On Off - 60 minutes
On On On - 120 minutes
S1.6 – 30 seconds delay between outputs On/
Off activation
On - with delay
Off - no delay
S1.7 + S1.8 – Off Delay # of cycles
Off Off - no delay cycles
Off On - 1 delay cycle
On Off - 2 delay cycles
On On - 3 delay cycles
ON
87654321
BACNET protocol
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com
Not in use
N
N
NN
14.10.2012
Print name: PS2600-ASU
Software name:12410701
Check sum : AA5E
Original 14.10.2012
OPTIONAL
12341234
Outputs always
work
Outputs work
in sequence
Not in use
Must remain open
Common -
Feeding Voltage to outputs
CONTACTORS CONTROL
/