meitav-tec CTU-1800-PM2-3S-FC-Super Product information

  • I have reviewed the datasheet for the meitav-tec Controller CTU1800-PM2-3S-FC-SUPER. This document provides detailed information on the controller's configuration, fault handling, and temperature sensor logic. It outlines how to configure fan modes, valve timing, and system behavior based on various sensor inputs. I am ready to answer your questions about this device.
  • What does Fault 1 indicate?
    What does Fault 2 indicate?
    How can I configure the open/close time of the valves?
N L V1 X1 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 V2
COM
PO1
COM
PO2 PO3
COM
PO4 1 2 3 7 8 AO1 0 AO2
DI1 0 DI3 0DI2 DI5 0DI4 DI7 0DI6 DI8 12V T1 0 T2 0 T3 0 AI1 0 AI2 5VDC A B
ON
12345678
ON
1234
12Vdc supply voltage
option (30mA max)
Fault 4
Fault 3
Fault 2
Fault 1
Used to configure
the open/close
time of the valve
Return air sensor
Change over sensor
Indoor coil sensor
Not in use
Communication cable
2x22AWG
Twisted, Shielded
Main Input
230Vac Not in use
Fan low
Fan medium
Fan high
Not in use
Not in use
Common
Common
230Vac, 3A
Heat
Valve
24Vac, 2.5VA
Panel output
(option)
Not in
use
MAC Address
DIP switch (S1)
Configuration
DIP switch (S2)
Power
LED
Not in
use
ON
1234
DIP switch Configuration (S2)
S2.1 Fan ON / Auto fan configuration in cool
ON - Auto fan in cool(always)
OFF - Fan ON in cool (always)
S2.2 2-pipe / 4-pipe system
ON - 4-pipe
OFF - 2-pipe
S2.3 Fan ON / Auto fan configuration in heat
ON - Auto fan in heat (always)
OFF - Fan ON in heat (always)
S2.4 “End of network” configuration
ON - End of network
OFF - Not end of network
Date:
Title:
No.Revision Date
Drawn: P.Rechtman
Checked: O.Volovitch
Approved: E.Roy
CTU1800-PM2-3S-FC-SUPER
23/12/2007
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com File: CTU1800-PM2-3S-FC-SUPER-REV2.vsd
DI2,0 DI3,0 DI4,0 Time (sec.)
Unshort Unshort Unshort 5
Short Unshort Unshort 60
Unshort Short Unshort 90
Short Short Unshort 150
Unshort Unshort Short 200
Short Unshort Short 240
Unshort Short Short 300
Short Short Short 400
Configure the open/close time of the valves
Short / Open the DI2,0 ; DI3,0 ; DI4,0 ;
according to the following table.
Cool
Valve
24Vac, 2.5VA
Open
Close
DI1,0 Unshort always
Not in
use
Unshort
always
Default
Open
Close
Print name: PS-2600
Temperature Sensors Logic
T1,0 - Return air sensor
The ambient (room) temperature can be sensed via the return air sensor.
T2,0 - Change-over sensor
Mode is automatically selected, based on the water temperature sensed by T2 (2-pipe system
only) T2 > 30°C Heat , T2 < 20°C Cool
T3,0 - Indoor coil sensor
Soft-start in Heat
When T3 rises above (or equals) 36°C The indoor fan will start working (according to FAN
ON or AUTO FAN state)
When the temperature drops below 32°C The indoor fan will turn OFF.
*When T3 is not connected:
- If AUTO FAN is selected, the indoor fan will start working 30 seconds after demand for heat.
- If FAN ON is selected, the indoor fan will work continuously.
Faults
Fault 1 - DI5,0 (N.C)
Closed (default) - System outputs work
normally.
Open - All system outputs turn off (fan speeds,
cool and heat valves).
Sample devices - Window contact, door switch.
Fault 2 - DI6,0 (N.C)
Closed (default) - "Fan only" mode – available.
Open - "Fan only" mode - not available.
Comments - Fan Only mode can be viewed
through panel .
Fault 3 - DI7,0 (N.C)
Closed/Open - Fault indication only.
Comments - The fault status (Open or Close) is
viewed through the software.
Fault 4 - DI8,0 (N.C)
Closed (default) - System outputs work
normally.
Open - When the input is open for 10 minutes -
all system outputs turn off (fan speeds,
cool and heat valves…).
Sample devices - Occupancy sensor.
2 Faults explanation 23.12.07
1 26.02.07Original
/