meitav-tec CTU-4524-P-3S-FC-SUPER Product information

Category
Security device components
Type
Product information
N L V1 X1 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 2 3 7 8 AO1 0
DI1 0DI3 0DI2 DI5 0DI4 DI7 0DI6 DI8 12V T1 0T2 0T3 0AI1 0AI2 5VDC A B
ON
12345678
ON
1234
12Vdc supply voltage –
option (30mA max)
Fault 2
Return air sensor
Change over sensor
Indoor coil sensor
Not in use
Communication cable
2x22AWG
Twisted, Shielded
Main Input
24Vac Not in use
Fan low
Fan medium
Fan high
24Vac, 3A
Panel output (option)
MAC Address
DIP switch (S1) Configuration
DIP switch (S2)
Power LED
Not in use
ON
1234
DIP switch Configuration (S2)
S2.1 – Fan ON / Auto fan configuration in cool/heat
ON - Auto fan in Cool
OFF - Fan ON (always) in Cool
S2.2 – 2-pipe / 4-pipe system
ON - 4-pipe
OFF - 2-pipe
S2.3 ON - Auto fan in Heat
OFF - Fan ON (always) in Heat
S2.4 – “End of network” configuration
ON - End of network
OFF - Not end of network
Date:
Title:Drawn: A.STAR
Checked: O.Volovitch
Approved: E.Roy
CTU4524-P-3S-FC-SUPER
29.03.09
meitav tec
Tel: +972-3-9626462
Fax: +972-3-9626620
e-mail: support@meitavtec.com File: CTU4524-P-3S-FC-SUPER.vsd
Digital Inputs
Not in use
Default
Print name: PS-2600
Temperature Sensors Logic
T1,0 - Return air sensor
The ambient (room) temperature can be sensed via the return air sensor.
T2,0 - Change-over sensor
Mode is automatically selected, based on the water temperature sensed by T2 (2-pipe system
only) T2 > 30°C / 86°F Heat , T2 < 20°C / 68°F Cool
T3,0 - Indoor coil sensor
Soft-start in Heat
When T3 rises above (or equals) 36°C / 97°F The indoor fan will start working (according to
FAN ON or AUTO FAN state)
When the temperature drops below 32°C / 90°F The indoor fan will turn OFF.
*When T3 is not connected:
- If AUTO FAN is selected, the indoor fan will start working 30 seconds after demand for heat.
- If FAN ON is selected, the indoor fan will work continuously.
Occupancy
Sensor
2. DI6,0 -FAN Short – Fan Only mode available
(Selectable through controller)
Open – Fan Only mode not available
1. DI5,0 -Fault 1 input (N.C.)
When open – all outputs OFF (no delay)
3. DI7,0 -Fault 2 input (N.C.)
Only for indication through the protocol
Fault 1
Fan
Software name: 08210508
Check sum : 7519
29.03.09
1 Original
AO2
;FMH/X500;ETN/X500
IRP/X500
Pump Output
24Vac, 1A
o
RS485 RS485
Modbus ProtocolModbus Protocol
4. DI8,0 -Occupancy Sensor
When the DI8 input (N.C) is open for 10
minutes, all outputs turn Off.
V2 COM PO1 COM PO2 PO3 COM PO4
Not in use
XGoG XGoG
~
110Vac/24Vac
0-10Vdc
0-10Vdc
CoolHeat
  • Page 1 1

meitav-tec CTU-4524-P-3S-FC-SUPER Product information

Category
Security device components
Type
Product information

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI