meitav-tec CTU2524-AC-SUPER-02-WET Product information

Type
Product information
Fan low (3A)
Fan medium (3A)
Fan high (3A)
Temperature Sensors Logic
T1,0 - Return air sensor
T2,0 -Outdoor sensor
T3,0 - Indoor sensor
Deicing (Compressor and outdoor fan are inactive)
In Heat mode:
-0ºC/ºF < T2 < 16ºC/61ºF 5 minutes defrost / 22 minutes break
In Cool mode:
-0ºC/ºF < T3 < 8ºC/46.5ºF Deicing occurs until T3 rises above 8ºC/46.5ºF
Overheat protection:
In Heat mode (Compressor, H.Elements and Outdoor fan inactive):
Overheat starts when T3 > 68ºC/155ºF and stops when T3 < 55ºC/131ºF
In Cool mode (Compressor, Stop, Indoor and Outdoor fans active):
Overheat starts when T2 > 68ºC/155ºF and stops when T2 < 55ºC/131ºF
Note: T2 and T3 can be configured through the protocol to be used as indication only (without deicing
and overheat protection)
Compressor 1 (0.5A)
Compressor 2 (0.5A)
H.Pump/H.Element 1 (0.5A)
Outdoor Fan/H.El. 3 (0.5A)
H.Element 2 (0.5A)
Drawn: Danny
CTU2524-AC-SUPER-02-WET
File: CTU2524-AC-SUPER-02-WET.vsd
Software name: 10405506
Check sum :7E42
Date: 21.06.2010 1 Original
N L V1 X1 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 2 3 7 8 AO1 0
DI1 0DI3 0DI2 DI5 0DI4 DI7 0DI6 DI8 12V T1 0T2 0T3 0AI1 0AI2 5VDC A B
ON
12345678
ON
1234
12Vdc supply voltage – option
(30mA max)
T1 - Return air sensor
T2 – Outdoor sensor
T3 -Indoor Sensor
Communication cable
2x22AWG
Twisted, Shielded
Main Input
24VAC
Wall Panel
(option)
MAC Address DIP
switch (S1)
Configuration
DIP switch (S2)
Power LED
Not in use
AO2
o
RS485
Occupancy sensor
Feeding to
outputs
“WET”
8A Fuse
+12V
CONTROLLER
NNNN
“N”
BACnet
Important !
Disconnect power to the main board
before making any changes to DIP
switches/Jumpers, wiring the unit and/or
connecting the wall panel.
DIP switch Configuration (S2)
S2.1 HC (Heat–Cool) or HP (Heat Pump)
OFF - HP configuration
ON - HC configuration
In HC configuration: DO5 = H.Element 1, DO3 = H.Element 3
In HP configuration: DO5 = Heat Pump, DO3 = Outdoor Fan
S2.2 Electric Heater or Oil/Gas Heater (in HC)
ON - Oil/Gas
OFF - Electric
S2.3 – Instance number configuration
OFF - Instance number by protocol
ON - Instance number = MAC Address+600
S2.4 – “End of network” configuration
ON - End of network
OFF - Not end of network
ON
1234
Default
Fault 2 – Window contact (N.C.)
Fault 3 – Flow sensor (N.C.)
Digital input 1 – Indication only
Digital input 4 – Compressor delay
Digital input 5 – Fan speeds
Digital input 6 – Heat pump config.
Digital input 7 – Indication only
Digital inputs
DI1 Indication only thorough protocol
DI2 Window contact (N.C.)
Turn all outputs OFF or switch to Economy (selectable through protocol).
DI3 Flow Sensor (N.C.)
Fault 3 (Flow sensor) – Turn compressors and heat elements OFF.
DI4 3.5 Minutes Compressor delay (Open – with delay)
DI5 Fan speeds (Open – 3 Speeds, Close – 1 Speed)
DI6 Heat pump config (Open – Active in cool, Close – Active in heat)
DI7 Indication only thorough protocol
DI8 – Occupancy sensor
When the digital input is open for 10 minutes, all outputs turn OFF or controller
switch to economy (Selectable through protocol).
Short the (DI8,0) terminals, only when an occupancy sensor is not connected
21.06.2010
Print name: PS-2600-ASU
Checked: A.Star
Approved: A.Samocha
oT Ambient reading from panel or from Main Board
(T1,0)
FMH-X500-02 – JP2
“A” position – read temperature from main board.
“B” position – read temperature from panel.
ETN-X500-02 – JP2
OPEN – read temperature from main board.
SHORT – read temperature from panel.
B
Short
Open
A
3 81 2 7
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620