FläktGroup ISYteq Touch 2.1 room controller Installation guide

Type
Installation guide
INSTALLATION AND MAINTENANCE MANUAL
ISYteq TOUCH 2.1
We reserve the right to make changes without prior notice
FläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
1. General use of the ISYteq Touch 2.1 ........................................3
2. Mechanical installation.................................................................3
2.1. Space requirements ................................................................................... 3
3. Physical environmental conditions ..........................................3
4. Directives ..........................................................................................3
5. Electrical safety ..............................................................................3
6. Electrical connections ..................................................................4
6.1. Power supply ................................................................................................ 4
6.1.1. Connection to the controller ............................................................. 4
6.1.1.1. Supply terminals of the controller unit ................................... 4
6.1.2. Connection of an external power supply ..................................... 4
6.2. Modbus communication interface ........................................................ 4
6.2.1. Modbus connection ............................................................................. 4
6.2.2. Bus termination ..................................................................................... 4
6.2.3. BIAS (pull-up and pull-down resistors) ........................................ 5
6.2.4. Cable length and type ......................................................................... 5
7. Built-in room-temperature sensor ...........................................5
8. Main menu ........................................................................................5
8.1. Main screen layout ..................................................................................... 5
8.2. Splash screen .............................................................................................. 5
8.3. Access protection .......................................................................................6
8.4. Standby screen ............................................................................................6
8.5. System menu ...............................................................................................6
8.5.1. Information menu (About us) ............................................................7
8.5.2. Menu display settings ..........................................................................7
8.5.2.1. Backlight.............................................................................................7
8.5.2.2. Language .......................................................................................... 8
8.5.2.3. Standby screen ............................................................................... 8
8.5.3. Bypass settings menu ........................................................................9
8.6. Modbus parameter setting menu .......................................................... 9
8.6.1. Modbus parameters .......................................................................... 10
8.7. Operating modes (profiles) .................................................................... 10
8.7.1. Bypass function ....................................................................................11
8.8. Operation types of the controller .......................................................... 11
CONTENTS
8.9. Setpoint menus ...........................................................................................11
8.9.1.2. Temperature setpoint heating with offset cooling ............ 12
8.9.1.3. Temperature setpoint cooling with offset heating ............ 12
8.9.1.4. Separate Temperature setpoint for heating & cooling .... 12
8.9.1. Changing the room temperature setpoint ................................. 12
8.9.1.1. Single temperature setpoint (heating & cooling) .............. 12
8.9.1.5. Relative temperature setpoint ................................................. 13
8.9.2. Changing the air volume flow rate ............................................... 13
8.9.2.1. Supply air volume flow .............................................................. 13
8.9.2.2. Extract air volume flow .............................................................. 13
8.9.3. Changing the duct pressure ............................................................14
8.9.3.1. Supply air duct pressure ............................................................14
8.9.3.2. Extract air duct pressure ...........................................................14
8.9.4. Changing the fan speed ....................................................................14
8.9.4.1. Supply air fan speed ....................................................................14
8.9.4.2. Extract air fan speed ...................................................................14
8.9.5. Changing the air quality target value ...........................................14
8.9.6. Changing the humidity setpoint .................................................... 15
8.9.6.1. Single setpoint for humidifying & dehumidifying .............. 15
8.9.6.2. Setpoint for humidifying with offset for dehumidifying ... 15
8.9.6.3. Setpoint for dehumidifying with offset for humidifying ... 16
8.9.6.4. Separate setpoint for humidifying & dehumidifying ........ 16
8.9.7. Changing the minimum amount of outdoor air ........................17
8.10. Alarms ............................................................................................................17
8.10.1. Acknowledging alarms ......................................................................17
8.10.2. Alarm symbols .....................................................................................17
8.10.3. Modbus communication error ....................................................... 18
8.10.3.1. No connection ............................................................................... 18
8.10.3.2. Modbus register not readable ................................................. 18
8.10.4. Error during parameter initialization ............................................ 18
8.10.5. The controller unit was switched off externally ...................... 18
9. List of all used symbols ............................................................. 19
3
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
1. GENERAL USE OF THE ISYTEQ TOUCH 2.1
The control panel has a 2.3” (5.84 cm) display with a touch sensitive
colour screen. The control panel is connected to the controller via a
communication interface (Modbus). Power can be supplied from the
controller or from an external power supply. The operating panel can
be installed using either a standard ISO flush-mounted or a surface-
mounted box. With the ISYteq Touch 2.1 operating panel all setpoints
available on the controller can be changed easily and quickly. The
number of the displayed setpoint menus depends on the equipment of
the controller.
2. MECHANICAL INSTALLATION
The control panel is mechanically designed for indoor installation in a
standard flush box. If the room temperature is to be measured via the
integrated sensor in the control panel, an installation with a standard
surface-mounted device box is more suitable.
2.1. SPACE REQUIREMENTS
3. PHYSICAL ENVIRONMENTAL CONDITIONS
The control panel is specified for the following environmental
conditions.
#Feature Specification Note(s)
1Operating
temperature
0...40°C
2Storage
temperature
-30...60°C
3Humidity 10–95% RH No condense
4Vibration EN-60721-3-3 Test method: (3M5)
5UV radiation Not direct sunlight The operator panel is intended
to be mounted inside
4. DIRECTIVES
#Feature Specification Note(s)
1CE marking directive 93/68/EEC
2Low voltage directive 2014/35/EU Valid from 2016-04-20
3Machinery directive 2006/42/EC
4EMC directive
(Electromagnetic
compatibility)
2014/30/EU Valid from 2016-04-20
5Restriction of
Hazardous substances
(RoHs) directive
2002/95/EC
5. ELECTRICAL SAFETY
#Feature Specification Note(s)
1Installation class Class 3 l = Devices with PE
II = Insulation with plastics
III = under < 50VDC devices
2Overvoltage
category
CAT 1 1 = lsolating device
2 = Power from a wall socket
3 = Power from the fuse panel
4 = Power from distribution
lines
3Pollution degree Class 2 1 = Clean room or sealed
devices
2 = Office environment
3 = Unheated rooms
4 = Outdoor use
8.67 cm
8.67 cm
71 mm
71 mm
4
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
6. ELECTRICAL CONNECTIONS
The following figure shows the connections for the power supply
and the Modbus interface with switchable termination resistor. The
connection and meanings of the individual terminals are described by
the reference number in the following table.
6
1
2
3
4
5
Figure 1: Terminals and terminating resistor
Reference Terminal Pin Remark
1X6.1 VDD 12-48 VDC, Power consumption 0.5 W
2X6.2 A+ Modbus RX+/TX+
3X6.3 B- Modbus RX-/TX-
4X6.4 GND GND for power supply
5X7 Unused
6Bus
term
Switchable termination for Modbus
(RS485)
6.1. POWER SUPPLY
The power supply of the operating panel can be provided either by the
controller or by an external power supply (separate power supply unit).
6.1.1. CONNECTION TO THE CONTROLLER
If the control panel is to be supplied with power directly from the
controller, the power supply cable must be connected as shown in the
wiring diagram (Figure 2).
6.1.1.1. Supply terminals of the controller unit
Reference Terminal Pin Remark
1X5 VDD
2X5 GND
R1
120 Ω
BACnet MS/TP
Modbus Master
Modbus Slave
G0
G24
X5 X4
A+ B- Vdd GND
GND2
B2
A2
GND1
B1
A1
GND2
B2
A2
B1
A1
GND1
1 213W2
0,22 mm2
3W3
0,75 mm2
2
HMI2
3A2
Figure 2: Wiring diagram power supply and Modbus connections.
6.1.2. CONNECTION OF AN EXTERNAL POWER SUPPLY
A separate power supply unit for the operating panel should have at
least the following specifications:
DC output: 12-48 VDC, 0.5 W
6.2. MODBUS COMMUNICATION INTERFACE
The operating panel communicates with the controller via Modbus
protocol. The controller is already preconfigured at the factory with the
following Modbus settings:
Protocol: Modbus RTU (RS 485, 2-wire connection, Master)
Baud rate: 19200
Stop bits: 2
Parity: None
Data bytes: 8
Controller unit address: 1
Note: Normally, the Modbus settings of the controller as well as
for the operating panel are set at the factory so that the system is
immediately ready for operation if the cables are connected correctly.
6.2.1. MODBUS CONNECTION
The Modbus interfaces of the controller and the operating panel are
connected as shown in the wiring diagram Figure 2.
6.2.2. BUS TERMINATION
A Modbus connection must be terminated at both ends with a
terminating resistor (see wiring diagram Figure 2). On the controller
side, a 120 Ohm (1/4 Watt) must be applied in parallel to the Modbus
terminals (X4.7, X4.8). The control panel itself has a switchable
terminating resistor. Please check that the switch on the control panel
(see Figure 1, P. 5) for the terminating resistor is set to ”ON”.
5
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
6.2.3. BIAS (PULL-UP AND PULL-DOWN RESISTORS)
Both the controller and the control panel have integrated BIAS
resistors. There is therefore no need to switch on BIAS (pull-up and
pull-down resistors).
6.2.4. CABLE LENGTH AND TYPE
The maximum cable length between the controller and the control
panel is 100 m. The following cable types are recommended:
Nomak 2x2x0.5
KLMA 4x0.8
or equivalent cable types.
Note: This cable is also suitable for the power supply of the control
panel by the controller.
7. BUILT-IN ROOM-TEMPERATURE SENSOR
The control panel has a built-in temperature sensor. The temperature
range of this sensor is 0°C to 40°C. The measuring accuracy for
the specified range is given in Table 1. The installation location of
the control panel is also the measurement location of the room
temperature; therefore, it should be free of drafts and at the same time
a suitable measuring point for the room temperature. When using the
internal room temperature sensor, it is recommended to install the
control panel on the wall using a surface-mounted box. This will result
in faster temperature measurement.
If the installation location of the control panel is not suitable as
a measuring point for the room temperature, an external room
temperature sensor can be connected to the controller and placed in a
better location in the room.
Temperature range Accuracy °K
0.0–9.9°C ±3.0°K
10.0–19.9°C ±1.5°K
20.0–29.9°C ±1.0°K
30.0–40.0°C ±3.0°K
Table 1: Accuracy of the internal temperature sensor
8. MAIN MENU
8.1. MAIN SCREEN LAYOUT
The main screen is divided into the following areas:
Figure 3: Main screen layout
1. Button for the system menu
2. Button for the operating mode (profiles)
3. Indicator and button to acknowledge alarms
4. Button for the operating mode of the controller
5. Display range for the different setpoints
6. Button for scrolling up and down the different setpoints
8.2. SPLASH SCREEN
After connecting the power supply, the control panel starts with the
splash screen (Figure 4). This splash screen shows the firmware
version of the control panel and the company logo with a progress bar.
If an access lock for the operating panel is configured on the controller,
an input menu for a 3-digit pin is displayed after exiting the splash
screen (see chapter 8.3). If no access protection is configured, the
main menu (Figure 7) is shown after the start-up process.
Figure 4: Splash screen
6
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.3. ACCESS PROTECTION
The control panel can be protected against unauthorized access by
a 3-digit pin code. This access protection must be activated on the
controller and the desired pin code must be stored there. In the factory
default setting, the access protection is not activated, and the pin code
is preset to 999.
Note: If the pin was forgotten, it can only be changed or read from the
controller’s web page with the appropriate authorization.
The screen for entering the pins (see Figure 5) appears when the
access protection is activated, either directly after the splash screen or
when coming from the standby screen (chapter 8.5.2.3). Without any
operating action, the operating panel will be locked after 60 seconds
and the standby display will appear. Touching the standby screen will
not change directly to the setpoint menu, but to the pin entry screen.
Each of the displayed pins can be changed to the desired pin in
independent order using the arrow keys. Tap on the padlock symbol
in the lower right corner to confirm your entry. If the pin is correct,
the system switches to the last selected setpoint menu (see chapter
8.9). If the pin is wrong, the padlock symbol is displayed in red for a
moment.
Figure 5: Entry pin screen
8.4. STANDBY SCREEN
The control panel switches from the main screen to the standby
display after 60 seconds without any operation. In standby mode,
the brightness of the screen is dimmed, but the actual values of the
control can still be read. The symbols for the actual values (see Figure
6) on the left side of the display are the same symbols as the symbols
for the corresponding setpoints (see also chapter 9).
Which actual value should be displayed can be configured in the
system menu (see chapter 8.5.2.3). Touching the standby display will
either display the last selected setpoint menu or if the access lock is
activated, the input dialogue for the pin (see chapter 8.3).
Figure 6: Standby screen
8.5. SYSTEM MENU
The system menu (Figure 8) contains submenus for settings that affect
the control panel itself. This includes the configuration of the menu
language, the backlight, the bypass setting, as well as contact and
version information.
With the button in the upper left corner (see Figure 7), the system
menu is called up. In the system menu, select the desired menu from
the list with the and buttons, which will then be marked
yellow. By tapping on the marked menu, it will be called up. Use the
button (top left) to return to the main menu.
Figure 7: Main screen
Figure 8: System menu
7
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.5.1. INFORMATION MENU (ABOUT US)
The ”Information” menu can be accessed via the system menu. On
the first page of the ”About Us” menu, you can display the contact
information of the manufacturer and the company product version
number of the connected controller. On the second page, which can be
reached by clicking the button , the URL of the company web page
is displayed as QR code, the firmware version number of the control
panel and the controller. The button can be used to switch pages
and the button returns (see Figure 9 & Figure 10) to the system
menu.
Figure 9: Contact info as text
Figure 10: URL of the company website as QR code
8.5.2. MENU DISPLAY SETTINGS
In this menu, all settings can be made which affect the display itself.
Use the two buttons and to select the desired menu. By
touching the selected menu, you can access the settings menu. Button
takes you back to the ‚System menu‘.
Note: If the Modbus connection is interrupted, the firmware version
number of the controller is displayed as v0.00.00.00.
8.5.2.1. Backlight
In this menu, you can adjust the brightness of the backlight in percent
up to the maximum brightness. The buttons and are used
to increase or decrease the brightness in one percent steps. With
button , you can leave this menu without accepting the changed
brightness and with button you accept the brightness value and
leave the menu.
8
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.5.2.2. Language
In this menu, the menu language can be changed. The following
languages are available in the selection list:
English
Swedish
Finnish
German
French
Note: The languages displayed in the list are always in the respective
national language.
Use button and to select the language in the selection list.
With button , you can leave this menu without accepting the
changed language and with button you accept the selected
language and leave the menu.
8.5.2.3. Standby screen
In this system menu, you can define which actual value of the
control should be displayed on the standby display. The selection list
contains only process value entries which have been configured in the
controller.
List of all possible actual values:
None (black screen)
Temperature
Supply air volume flow
Exhaust air volume flow
Duct pressure supply air
Duct pressure exhaust air
Air Quality
Supply air fan speed
Exhaust air fan speed
Humidity
Example:
If only one supply air volume flow control is configured on the
controller, only the supply air volume flow is displayed as the actual
value in the selection.
With the buttons and the actual value is selected in the
selection list. With button you can leave this menu without
accepting the changed standby screen and with button the
selected actual value type is accepted, and the menu returns to the
system settings menu.
9
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.5.3. BYPASS SETTINGS MENU
In this menu, the operating mode and the duration of the bypass
function can be changed.
Once the desired bypass parameter has been selected and tapped
with the arrow keys, use buttons and to select the operating
mode or to change the duration.
Use the button to leave this menu without accepting the changed
bypass parameters. Use the button to accept the selected bypass
parameter and return to the system menu.
The following operating modes can be selected in bypass mode:
OFF Device is switched off (frost protection mode)
P1 Profile 1
P2 Profile 2
P3 Profile 3
P4 Profile 4
P5 Profile 5
How the bypass is activated and which function it fulfills is described
in chapter 8.7.1.
8.6. MODBUS PARAMETER SETTING MENU
The operating unit communicates with the controller via an RS485
Modbus RTU protocol. How to connect the operating panel to a
controller is described in section 2.2.1. The following Modbus settings
apply as factory settings of the controller and the operating panel:
Controller Modbus address (slave): 1
Baud rate 19200
Number of data bits 8
Number of stop bits 2
Parity None
Note: If the control panel is correctly connected to the controller and
with the factory default settings, the Modbus connection between
controller and control panel should work immediately, no further
settings are required.
The menu for setting the Modbus parameters is hidden, among other
things to prevent accidental changes to the Modbus parameters. To
access the menu for Modbus settings, the QR code in the menu ”About
us” (chapter 8.5.1) must be touched 5 times within 2 seconds.
In this menu, all Modbus settings can then be made. Use the two
buttons and to select the desired Modbus parameter. By
touching the selected menu, the settings menu of the selected
parameter is opened. With the button you can return to the ”About
us” menu.
10
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.6.1. MODBUS PARAMETERS
The Modbus parameters are correctly set at the factory. As there are
no other Modbus participants on the bus, there is no reason to change
the parameters. The pre-set Modbus parameters ensure that the
system can be operated immediately if the connection between the
controller and the operating panel is correct.
If it is necessary to change the Modbus parameters, the following
section will explain the baud rate as an example. All other parameter
menus follow this principle.
In this menu, the desired baud rate can be selected. Use buttons
and to select the desired baud rate from the list.
With button you can leave this menu without accepting the baud
rate and with button you accept the selected baud rate and leave
the menu.
Note: Please make sure that when changing the Modbus parameters,
the equivalent parameters are set on the controller unit.
8.7. OPERATING MODES (PROFILES)
With the button in the upper right corner (see Figure 11) the operating
modes of the controller can be changed. Tap this button to scroll
through the operating modes one by one, as shown in Figure 11. The
selected operating mode will only be accepted and activated after 3
seconds.
Most of the operating modes have changeable profiles (profile 1- 5),
which determine which operating modes and which setpoints are valid
for the controller. The operating modes , scheduler and bypass
have no profiles and therefore are exceptions. The operating mode
switches off the system (frost protection mode), the scheduler
activates the profiles according to a previously defined timer program.
The bypass function (see chapter 8.7.1) can be activated for a
previously defined period.
Figure 11: Changing operation modes
Note: After switching a profile, the setpoints are taken over from the
new profile, so that the displayed setpoint may change in the setpoint
range of the display. Any changes made by a user are temporarily
retained until another profile is switched over.
Note: The timer program can only be viewed and changed via the
controller’s web interface.
11
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.7.1. BYPASS FUNCTION
A bypass function is suitable for activating a desired operating mode
(profile) once for a defined period. The set operating mode is bypassed
for a period. After the period has expired, the system switches back to
the previous operating mode.
The difference between an automatic timer and the bypass function is
explained in the following example.
Example:
Two profiles have been defined for an office room, one when the office
is occupied by employees (Office Time profile) and one when there
are no people in the office (Free Time profile). The automatic timer is
activated and switches the Office Time profile from 8:00 to 17:00 to
active and from 17:00 the system is switched from the automatic timer
to the Free Time profile since there are usually no more employees
in the office. If employees want to stay in this office longer than 5:00
p.m., they could activate the desired operating mode (profile) manually,
with the disadvantage that when leaving the office, the profile that was
active before should be set. An easier solution in this case would be
to activate the desired operating mode for a certain period. After this
period has elapsed, the system automatically switches back to the
previous operating mode.
Changes of the bypass operating mode or profile and the duration for
the bypass are described in chapter 8.5.3.
Note: The bypass function can also be started from the controller web
page. In this case, the bypass operation is displayed on the control
panel. The bypass function can be canceled at any time from the
control panel.
8.8. OPERATION TYPES OF THE CONTROLLER
The operation types of the controller can be switched cyclically with
each tap on the button 4 (see Figure 3). The following operation types
are available:
Automatic’ means that the controller decides
independently, depending on the current temperature,
whether heating or cooling is required.
‘Heating only’ means that if the current temperature
falls below the setpoint, heating is active. Otherwise, the
system remains neutral (no active heating or cooling).
‘Cooling only’ means that if the current temperature
rises above the setpoint, cooling is active. Otherwise the
system remains neutral (no active heating or cooling).
’Night purge’ means that before active heating or cooling
sequences are started, under certain outdoor and
indoor air conditions, the ERS (if present) or the outdoor
air (passive) is used for cooling and in rare cases for
heating.
8.9. SETPOINT MENUS
The different setpoint menus can be selected by the two buttons
or (area 6 in Figure 3). The list of target values is
cyclic (see Figure 12), i.e. it starts again from the beginning at the end
of the list. Only those setpoints are displayed that correspond to the
equipment or configuration of the installation/controller. If the desired
setpoint is selected via buttons and , tapping the
setpoint (area 5 in Figure 3) will bring up a menu where the setpoint
can be changed.
With the buttons , the setpoint can be increased or
decreased. If the button is held down for more than 2 seconds, a
repeat function is activated. The longer the button is pressed, the
faster the value is changed. Button accepts the target value and
button allows to leave the target value menu without accepting the
changed value.
All setpoint menus are described in the following chapters.
Figure 12: Example of a cyclic setpoint list
12
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.9.1. CHANGING THE ROOM TEMPERATURE SETPOINT
Five different types of temperature setpoints can be configured on
the controller. The room temperature setpoint menu is only displayed
in the list if a room temperature control has been activated on the
controller. The setpoint types are described in the following chapters.
Temperatures are displayed in the unit configured in the controller. The
limit values for the room temperature come from the controller and are
set at 5 to 45°C at the factory.
8.9.1.1. Single temperature setpoint (heating & cooling)
A single temperature setpoint means that it is intended for both the
heating and the cooling circuit.
8.9.1.2. Temperature setpoint heating with offset cooling
In the following diagram, you can see the principle of a temperature
setpoint for the heating circuit with an offset for the cooling circuit. In
the neutral zone, the controller remains passive. If the temperature
setpoint for the heating circuit is changed, the setpoint for the cooling
circuit is shifted by the value of the offset. The size of the neutral zone
therefore remains the same.
Heating neutral Cooling
Heating neutral Cooling
8.9.1.3. Temperature setpoint cooling with offset heating
In the following diagram, you can see the principle of a temperature
setpoint for the cooling circuit with an offset for the heating circuit. In
the neutral zone, the controller remains passive. If the temperature
setpoint for the cooling circuit is changed, the setpoint for the heating
circuit is shifted by the value of the offset. The size of the neutral zone
therefore remains the same.
8.9.1.4. Separate Temperature setpoint for heating & cooling
In the following diagram, you can see the principle if separate
temperature setpoints exist for the heating and the cooling circuit. In
the neutral zone, the controller remains passive. If you change the
setpoint for the heating or cooling circuit, the size of the neutral zone,
changes as well.
Heating neutral Cooling
Figure 13: Single temperature setpoint
13
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.9.1.5. Relative temperature setpoint
In the case of a relative setpoint, on a base temperature setpoint (
labeled as B in Figure 14), if the temperature value is positive, the value
is added to the base setpoint and if it is negative, it is subtracted from
the base setpoint. The base setpoint comes from the controller and
can only be changed there. The limit values for the relative temperature
setpoint are specified by the controller and are set at the factory to
-5.0 to +5.0 K.
Example 1:
Basic setpoint: 21.0°C
Relative setpoint: +1.5 K
Resulting setpoint: 22.5°C
Example 2:
Basic setpoint: 21.0°C
Relative setpoint: -1.5 K
Resulting setpoint: 19.5°C
Figure 14: Relative temperature setpoint
8.9.2. CHANGING THE AIR VOLUME FLOW RATE
The setpoint menus for the air volume flow rates are only displayed
in the list if either a supply air and/or an exhaust air volume flow
rate control has been activated on the controller. Air volume flows are
displayed in the unit configured on the controller (m
3
/h, m
3
/s, l/s).
The limit values for the air volume flows come from the controller and
are already set to the corresponding unit sizes at the factory.
8.9.2.1. Supply air volume flow
Figure 15: Setpoint menu supply air volume flow
Figure 16: Setpoint menu extract air volume flow
8.9.2.2. Extract air volume flow
Heating Cooling
14
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
Figure 18: Setpoint menu extract air duct pressure
Figure 20: Setpoint menu extract air fan speed
Figure 21: Setpoint menu for air quality
Figure 17: Setpoint menu supply duct pressure
Figure 19: Setpoint menu supply air fan speed
8.9.3.2. Extract air duct pressure
8.9.4.2. Extract air fan speed
8.9.3. CHANGING THE DUCT PRESSURE
The setpoint menus for the duct pressures are only displayed in the
list if either a supply air and/or an exhaust air duct control has been
activated on the controller.
The limit values for the duct pressure come from the controller and are
already set to the corresponding unit size in the factory.
8.9.3.1. Supply air duct pressure
8.9.4. CHANGING THE FAN SPEED
The setpoint menus for the fan speeds, adjustable as a percentage of
the maximum speed, are only displayed in the list if a manual setting
of the supply air and/or exhaust air fan speed has been activated on
the controller.
The limit values for the fan speed come from the controller and are
factory pre-set.
8.9.4.1. Supply air fan speed
8.9.5. CHANGING THE AIR QUALITY TARGET VALUE
The setpoint menu is only displayed if a underlying air quality control
has been configured on the controller. The limit values for the air
quality setpoint come from the controller and are factory set to 0 -
3000 ppm. If CO2 sensors are configured on the controller, the values
are displayed in ppm (part per million). For all other types of air quality
(VOC) sensors, the values are displayed in percent (%).
15
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
Figure 22: Single setpoint for humidifying & dehumidifying (automatic mode)
Figure 23: Single setpoint for humidifying
Figure 24: Single setpoint for dehumidifying
Figure 25: Single setpoint menu relative humidity
Figure 26: Setpoint for humidifying
Figure 27: Offset for dehumidifying
8.9.6. CHANGING THE HUMIDITY SETPOINT
The setpoint menu for the humidity (humidification and
dehumidification) is only displayed in the list if one of the humidity
controls is activated on the controller. On the controller, the
humidity control can be configured for either humidification and/
or dehumidification. In addition, the humidity can be displayed as
absolute (g/kg) or relative (%) value.
The limit values of the humidity setpoint come from the controller and
are factory defaults.
8.9.6.1. Single setpoint for humidifying & dehumidifying
A single humidity setpoint can be a setpoint for humidification and
dehumidification (automatic) or just for humidification or just for
dehumidification, depending on what has been set in the profile on the
controller (see figures below). If the setpoint is only for humidification
or dehumidification, the other part becomes the neutral zone (see
Figure 23 and Figure 24).
8.9.6.2. Setpoint for humidifying with offset for dehumidifying
If the controller is configured for a setpoint for humidification and an
offset for dehumidification, the humidity control behaves as shown
in the figure below If the humidification setpoint is changed, the
dehumidification setpoint is simultaneously changed by the set offset.
Example:
Dehumidification setpoint is changed from 50 to 55%, with a set offset
of 5%, the dehumidification setpoint changes from 55 to 60% at the
same time.
Humidifying Dehumidifying
Humidifying neutral
neutral Dehumidifying
neutral DehumidifyingHumidifying
16
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.9.6.3. Setpoint for dehumidifying with offset for humidifying
If the controller is configured for a setpoint value for dehumidification
and an offset for humidification, the humidity control behaves as
shown in the figure below If the setpoint for dehumidification is
changed, the humidification setpoint changes by the set offset at the
same time.
Example:
Dehumidification setpoint is changed from 21 to 26%. If the set offset
is 5%, the humidification setpoint changes from 23 to 28% at the same
time.
neutral DehumidifyingHumidifying neutral DehumidifyingHumidifying
Figure 28: Offset of the humidifying Figure 30: Separate setpoint for humidifying
Figure 29: Setpoint for the dehumidifying Figure 31: Separate setpoint for dehumidifying
8.9.6.4. Separate setpoint for humidifying & dehumidifying
If the controller is configured for two separate setpoints, one for
humidification and one for dehumidification, then the humidity
control behaves as shown in the figure below If the setpoint for
dehumidification is changed, the value of the humidification setpoint
remains unchanged. Only the size of the neutral zone changes.
Example:
Humidification setpoint is changed from 45 to 47%, then the set
dehumidification setpoint remains unchanged at 50%.
17
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
Figure 32: Setpoint menu for the minimum amount of outdoor air
8.9.7. CHANGING THE MINIMUM AMOUNT OF OUTDOOR AIR
The setpoint menu for the minimum outdoor air rate is only displayed
in the list if a damper control is activated which either expects the
minimum damper position in percent or calculates the damper position
depending on the specified outdoor air rate in percent and the current
fan speed. Depending on the configuration of the controller, the damper
position can be entered as a percentage and the controller tries to
hold the minimum outdoor air rate with fan speed, or the outdoor air
rate is entered either in m
3
/h, m
3
/s or l/s and the damper position is
controlled accordingly.
The limit values for the minimum percentage of outdoor air come from
the controller and are pre-set at the factory.
8.10. ALARMS
Alarms or fault situations of the connected controller are indicated as
collective alarms by an alarm symbol (bell) in the lower-left corner
of the display (see also Figure 3, section 3). If an alarm symbol is
displayed, the responsible service department should be notified
immediately to avoid consequential damage to the unit.
There are two types of alarms, a tripping and non-tripping collective
alarm. Tripping alarms cause either a shutdown or partial shutdown
of the unit. Further information on the cause of the fault can only be
obtained via the controller’s web interface.
8.10.1. ACKNOWLEDGING ALARMS
The alarm icon is also the button for acknowledging the tripping
alarms on the controller. After the button is pressed, the alarm symbol
turns white for a short moment as a confirmation of acknowledgement.
An acknowledgement of the alarm is only successful if the cause(s)
of the error(s) that led to the alarm on the controller is eliminated. If
an alarm is still pending, the alarm symbol is displayed. In the case of
non-tripping alarms whose cause(s) has (have) been eliminated on the
controller, the alarm symbol on the display disappears automatically.
Note: For tripping alarms whose cause has already been eliminated on
the controller unit, the alarm symbol is displayed until the alarm has
been acknowledged by the user.
8.10.2. ALARM SYMBOLS
The different colours of the alarm icon (bell) represent the following
alarm categories:
An error situation has occurred on the controller. The controller
reports an non-tripping alarm. This alarm does not require an
acknowledgement with the alarm button. This alarm will no longer be
displayed once the problem has been solved on the controller side.
A serious error situation has occurred at the controller unit, the
controller unit reports a tripping alarm. After this serious error has
been resolved and the red alarm symbol is still visible on the display,
an acknowledgement must be made by the user (see chapter 8.10.1)
so that the system can return to normal operation.
18
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
8.10.3. MODBUS COMMUNICATION ERROR
When a Modbus communication error occurs, the following error
screens appear.
8.10.3.1. No connection
A connection error can have the following causes.
Different or wrong Modbus configuration. The controller and the
operating unit have different Modbus communication parameters
such as baud rate, number of data bytes, parity or number of stop
bits. The Modbus station address of the controller may also be
configured incorrectly. The factory default settings of the controller
and the operating unit are listed in chapter 8.6 and normally do not
require any changes for Modbus communication.
The cable between the controller and the operating panel was not
connected correctly.
The bus termination on the operator panel is not activated or
additional termination resistor on the controller side has not been
attached to the terminal.
8.10.3.2. Modbus register not readable
If this error screen appears, the firmware of the control panel is not
compatible with the controller unit. Modbus registers are accessed
that are not present on the controller unit. This usually means that
the control panel has a newer software version than the controller.
The system will therefore only function to a limited extent or not at all.
Please inform the service staff immediately.
8.10.4. ERROR DURING PARAMETER INITIALIZATION
This error screen should not appear during operation. If it does, it
indicates that a micro SD card was detected during the start-up
process of the control panel and that the parameters or data loaded
from this card may have one of the following error causes:
CRC Error when reading data from the micro SD card
General read errors of the micro SD card
The version of the parameter file does not match the one on the
micro SD card.
Note: If the micro SD card has been removed from the control panel,
this error should no longer occur. If this or any other error occurs,
please inform the service staff immediately.
8.10.5. THE CONTROLLER UNIT WAS SWITCHED OFF EXTERNALLY
The controller unit was switched off either via the controller’s web
page or via a special input on the controller. If the following screen is
displayed, the controller unit can no longer be controlled via the control
panel. This is not an error situation! If the system has been switched
on again in this way, the main menu is visible, and the system can be
controlled via the control panel again.
19
We reserve the right to make changes without prior noticeFläktGroup DC-10475-GB 2021-10-27_R1
ISYteq Touch 2.1 – Installation and maintenance manual
9. LIST OF ALL USED SYMBOLS
The following table lists all the symbols used on the control panel with
their meaning.
Symbol Meaning
Supply air volume flow setpoint and the actual value (see
chapter 8.9.2.1)
Exhaust air volume flow setpoint and the actual value (see
chapter 8.9.2.2)
Supply duct pressure setpoint and the actual value (see
chapter 8.9.3.1)
Exhaust duct pressure setpoint and the actual value (see
chapter 8.9.3.2)
Supply air fan speed setpoint and the actual value (see
chapter 8.9.4.1)
Exhaust air fan speed setpoint and the actual value (see
chapter 8.9.4.2)
Air quality target and the actual value (see chapter 8.9.5)
Operating mode: Automatic timer (see chapter 8.7)
Operating mode: Unit in frost protection mode (off) (see chapter
8.7)
Operating mode: Profile 1 (see chapter 8.7)
Operating mode: Profile 2 (see chapter 8.7)
Operating mode: Profile 3 (see chapter 8.7)
Operating mode: Profile 4 (see chapter 8.7)
Operating mode: Profile 5 (see chapter 8.7)
Operating mode: Bypass (see chapter 8.7)
Dehumidification setpoint (see chapter 8.9.6.3)
Dehumidification offset (see chapter 8.9.6.2)
Humidification setpoint (see chapter 8.9.6.2)
Humidification offset (see chapter 8.9.6.3)
Humidity setpoint (see chapter 8.9.6.1)
Setpoint for outdoor air amount (see chapter 8.9.7)
Symbol Meaning
Single temperature setpoint or actual value (see chapter
8.9.1.1)
Temperature setpoint cooling circuit (see chapter 8.9.1.3)
Temperature offset cooling circuit (see chapter 8.9.1.2)
Temperature setpoint heating circuit (see chapter 8.9.1.2)
Temperature offset heating circuit (see chapter 8.9.1.3)
Relative temperature setpoint (see chapter 8.9.1.5)
Controller mode: Automatic (see chapter 8.8)
Controller mode: Heating only (see chapter 8.8)
Controller mode: Cooling only (see chapter 8.8)
Controller mode: Night Purge (see chapter 8.8)
Tripping collective alarm (see chapter 8.10.2)
Non-tripping collective alarm (see chapter 8.10.2)
WWW.FLAKTGROUP.COM
» Learn more on www.flaktgroup.com
or contact one of our offices
FläktGroup is the European market leader for smart and energy efficient Indoor Air
and Critical Air solutions to support every application area. We offer our customers
innovative technologies, high quality and outstanding performance supported by more
than a century of accumulated industry experience. The widest product range in the
market, and strong market presence in 65 countries worldwide, guarantee that we
are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diffusion | Air Distribution | Air Filtration
Air Management | Air Conditioning & Heating | Controls | Service
FG_DC_10475GB_ISYteq touch 2.1_IN-MA_2021-10-27_R1 © Copyright 2021 FläktGroup
ISYteq TOUCH 2.1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

FläktGroup ISYteq Touch 2.1 room controller Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI